Chapter 7. PARAMETER SETUP ■ Setup data settings “S E t” No. Item Code Item Factory Setting User Setting Setting 1 C0 1 Control action (CH1) 0 0: Reverse action (heat) 1: Direct action (cool) [Note] On heat/cool models, “– – – –” is displayed and setting is not possible. On other models, external switch input can invert direct/ reverse action on the setting of C 0 1. 2 C02 Input 1 temperature unit 0 3 C03 Input 1 range type 0 4 C04 Input 1 range decimal point position Not fixed 5 C05 Input 1 range lower limit (0%) Not fixed 6 C06 Input 1 range upper limit (100%) Not fixed 7 C07 Input 1 root extraction dropout 0.0 8 C08 Input 1 linearization table approximation 0 9 C0q SP1 lower limit 0%FS 10 C 10 SP1 upper limit 100%FS 0: °C 1: °F [Note] When the input 1 range type is linear, “– – – –” is displayed and setting is not possible. 0 to 73 0 to 20: Thermocouple 32 to 40, 48 to 56: Resistance temperature detector 64 to 73: Linear (dc current, dc voltage) [Note] Refer to the input 1 range table. Operation according to a setting not listed in this table is not fixed. 0 to 3 [Note] When the input 1 range type is non-linear, “– – – –” is displayed and setting is not possible. When the input 1 range type is changed from nonlinear to linear, the original non-linear range values remain. -1999 to +9999U [Note] When the input 1 range type is non-linear, “– – – –” is displayed and setting is not possible. When the input 1 range type is changed from nonlinear to linear, the original non-linear range values remain. The relationship between the analog inputs and readout values can be inverted by inverting the upper and lower limit values. 0.0 to 10.0% (ratio to input range) [Note] 0.0 disables square root extraction. When the input 1 range type is non-linear, “– – – –” is displayed and setting is not possible. 0: Disabled 1: Enabled [Note] Table data setting (a, b) is used for the linearization table. -1999 to upper limit U [Note] Changing the input 1 range has no effect on the range. However, note that a general reset sets the range to the 0%FS value of the input 1 range. Lower limit to 9999U [Note] Changing the input 1 range has no effect on the range. However, note that a general reset sets the range to the 0%FS value of the input 1 range. 7-32