Download DCP31 User`s Manual

Transcript
Chapter 7. PARAMETER SETUP
■ Setup data settings “S E t”
No.
Item Code
Item
Factory
Setting
User
Setting
Setting
1
C0 1
Control action (CH1)
0
0: Reverse action (heat)
1: Direct action (cool)
[Note]
On heat/cool models, “– – – –” is displayed and setting is
not possible.
On other models, external switch input can invert direct/
reverse action on the setting of C 0 1.
2
C02
Input 1 temperature
unit
0
3
C03
Input 1 range type
0
4
C04
Input 1 range
decimal point
position
Not fixed
5
C05
Input 1 range lower
limit (0%)
Not fixed
6
C06
Input 1 range upper
limit (100%)
Not fixed
7
C07
Input 1 root extraction dropout
0.0
8
C08
Input 1 linearization
table approximation
0
9
C0q
SP1 lower limit
0%FS
10
C 10
SP1 upper limit
100%FS
0: °C
1: °F
[Note]
When the input 1 range type is linear, “– – – –” is
displayed and setting is not possible.
0 to 73
0 to 20: Thermocouple
32 to 40, 48 to 56: Resistance temperature detector
64 to 73: Linear (dc current, dc voltage)
[Note]
Refer to the input 1 range table. Operation according to
a setting not listed in this table is not fixed.
0 to 3
[Note]
When the input 1 range type is non-linear, “– – – –” is
displayed and setting is not possible.
When the input 1 range type is changed from nonlinear to linear, the original non-linear range values
remain.
-1999 to +9999U
[Note]
When the input 1 range type is non-linear, “– – – –” is
displayed and setting is not possible.
When the input 1 range type is changed from nonlinear to linear, the original non-linear range values
remain.
The relationship between the analog inputs and
readout values can be inverted by inverting the upper
and lower limit values.
0.0 to 10.0% (ratio to input range)
[Note]
0.0 disables square root extraction.
When the input 1 range type is non-linear, “– – – –” is
displayed and setting is not possible.
0: Disabled
1: Enabled
[Note]
Table data setting (a, b) is used for the linearization
table.
-1999 to upper limit U
[Note]
Changing the input 1 range has no effect on the range.
However, note that a general reset sets the range to
the 0%FS value of the input 1 range.
Lower limit to 9999U
[Note]
Changing the input 1 range has no effect on the range.
However, note that a general reset sets the range to
the 0%FS value of the input 1 range.
7-32