Download 023K - Advanced Energy
Transcript
BA_REFUSOL 008K-023K_V11.3_EN Minimum spacing between single cores! L3 L1 PE L2 N Single cores should not be laid along magnetic materials. Note: The sum total of the ohmic and inductive voltage drops on the power supply line at nominal load should not exceed 1% of the line voltage. It must be ensured that the line inductance remains < 30 µH. 4.14 Interface Port RS485 * * * * RS485 OUT RS485 IN Pin 1 Bus termination+ Pin 1 Reference + Pin 2 RS485+ OUT Pin 2 RS485+ IN Pin 3 RS485- OUT Pin 3 RS485- IN Pin 4 Bus termination – Pin 4 Reference – Bus termination (wire jumper) The RS485 interface supports the USS protocol (Universal Serial interface protocol) which can be used for transmission of data, for example, to a data logger of a remote monitoring system. Figure No. 19 Standard interface connection When using this interface, please note that each device using the bus requires a unique address. Bus termination is made by means of wire bridges on X14 to the last bus user (inverter “n“). 29