Download Capstone Microturbines
Transcript
CHAPTER 7 PERFORMANCE Capstone Table 7-1. Capstone Model C200 Microturbine Performance Summary Parameter C200 Low Pressure NG All Other C200 Net Power Output 190 (+0/-4) kW net 200 (+0/-4) kW net Net Efficiency (LHV) 31 (r 2)% 11,600 kJ/kWh (11,000 Btu/kWh) 10,700 kJ/kWh (10,200 Btu/kWh) 2,400,000 kJ/hr (2,280,000 Btu/hr) 33 (r 2)% 10,900 kJ/kWh (10,300 Btu/kWh) 10,200 kJ/kWh (9,700 Btu/kWh) 2,400,000 kJ/hr (2,280,000 Btu/hr) Nominal Net Heat Rate (LHV) Nominal Generator Heat Rate (LHV) Nominal Steady State Fuel Flow (HHV) (1) (2) Notes: (1) The ratio of Higher Heating Value (HHV) to Lower Heating Value (LHV) is assumed to be 1.1. (2) Onload fuel flows can be up to two times higher than the steady state values. How to Use This Section The following pages present several tables and graphs for determining the nominal net power output, efficiency, and exhaust characteristics for various operating conditions. Table 7-5 at the end of this section provides an example calculation. The basic method is summarized below: x Look up the efficiency, exhaust temperature, and exhaust mass flow for a given temperature using Table 7-2. x Estimate the power output using Figure 7-2 for a given temperature and elevation. x Apply inlet pressure loss power and efficiency correction factors (if any) using Table 7-3. x Apply back pressure power and efficiency correction factors (if any) using Table 7-4. x Calculate nominal net power output and fuel input for the given operating conditions. x Define parasitic loads (Fuel Gas Booster, water pump, etc.). x Estimate exhaust temperature and flow for the given operating conditions. In addition to the steps above, tolerances for a given application must be considered. Refer to the Consider Tolerances section of this document for more information. Ambient Temperature Table Nominal net power output, efficiency, and exhaust characteristics versus ambient temperature at sea level for the Capstone C200 high pressure natural gas model microturbine are presented in Table 7-2. These values are estimated from nominal performance curves. 410066 Rev C (June 2009) Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without incurring any obligation either with respect to equipment previously sold or in the process of construction. 7-4