Download Model UP750 Program Controller User`s Manual for
Transcript
<Toc> <3. Programming> 3-26 ■ Controller Behavior at the Start of Program Operation You can determine how the controller should behave at the start of program operation. 1. Letting the controller run from a starting target setpoint A starting target setpoint refers to a setpoint from which program operation begins. The controller operates in such a manner that the setpoint changes to the final target setpoint over the segment time set for segment 1, irrespective of what the PV value is. Setpoint Segment 1 Segment 2 Final target setpoint Starting target setpoint Program setpoint Time Segment time Start of program operation <Controller Settings> Set the STC (Start Code) program parameter to “0”. 2. Letting the controller start from the current setpoint and run according to time settings defined for segment 1 This method is not available if the SEG.T (Segment Setting Method) parameter is set to “ramp setting.” Starting Point of Operation a b c d e Setpoint a Controller Behavior Begins to run from point a according to the time setting defined for segment 1. Begins to run from point b according to the time setting defined for segment 1. Begins to run from point c according to the time setting defined for segment 1. Begins to run from point d according to the time setting defined for segment 1. Begins to run from point e according to the time setting defined for segment 1. Final target setpoint b Program setpoint c d e Segment Start of 1 program operation Segment Segment Segment 2 3 4 Segment 5 Time <Controller Settings> Set the STC (Start Code) program parameter to “2”. IM 05E01B02-46E 1st Edition : May 31,2000-00