3 SPECIFICATIONS MELSEC-Q 3.5.44 Alert 1 to 4 mode setting (buffer memory address 192 to 195, 208 to 211: Un\G192 to Un\G195, Un\G208 to Un\G211) This setting is available in the setting mode only. To activate the change, turn on Setting change command (YnB). (1) The alert mode is set. (2) The values of Alert 1 to 4 are set in the following buffer memory addresses. • Channel 1: 38 to 41 • Channel 2: 70 to 73 (3) The correspondences between buffer memory addresses and channels are listed below. Mode setting item Alert 1 Alert 2 Alert 3 Alert 4 CH1 192 193 194 195 CH2 208 209 210 211 (4) The following table lists the alert modes and setting values. Refer to Section 3.2.10 for the alert functions of the Q62HLC. Alert mode Setting Upper limit input alert 1 Lower limit input alert 2 Upper limit deviation alert Lower limit deviation alert Upper/lower limit deviation alert Within-range alert 3 4 5 6 Alert mode Upper limit input alert with wait Lower limit input alert with wait Upper limit deviation alert with wait Lower limit deviation alert with wait Upper/lower limit deviation alert with wait — Setting Alert mode Setting 7 — — 8 — — 9 10 11 — Upper limit deviation alert with re-wait Lower limit deviation alert with re-wait Upper/lower limit deviation alert with re-wait — 12 13 14 — (5) The alert function is not executed with the default value 0. 3.5.45 Scaling value (buffer memory address 196, 212: Un\G196, Un\G212) (1) The value which scaled the measured value (PV) is stored. (2) The scaling method differs depending on thermocouple input or micro voltage/voltage/current input. For details of the scaling function, refer to Section 3.2.14. 3 - 101 3 - 101