Page 10 of 56
Report No. 21116651 001
IEC 60335-2-80
Clause
Requirement - Test
10
POWER INPUT AND CURRENT
10.1
Power input at normal operating temperature, rated
voltage and normal operation not deviating from
rated power input by more than shown in table 1
Result - Remark
Verdict
P
(see appended table)
N
Shutters or similar devices in open position (IEC
60335-2-80)
10.2
Current at normal operating temperature, rated
voltage and normal operation not deviating from
rated current by more than shown in table 2
P
rated current is not marked
N
Shutters or similar devices in open position (IEC
60335-2-80)
N
11
HEATING
P
11.1
No excessive temperatures in normal use
P
11.2
Placing and mounting of appliance as described
11.3
Temperature rises, other than of windings,
determined by thermocouples
P
Temperature rises of windings determined by
resistance method, unless
P
the windings makes it difficult to make the necessary
connections
N
11.4
Heating appliances operated under normal operation
at 1.15 times rated power input .............................. :
N
11.5
Motor-operated appliances operated under normal
254,4V (1,06x240V) was the
operation at most unfavourable voltage between 0.94 most unfavourable at every
and 1.06 times rated voltage ................................... : model
P
11.6
Combined appliances operated under normal
operation at most unfavourable voltage between 0.94
and 1.06 times rated voltage ................................... :
N
11.7
Operation until steady conditions are established
(IEC 60335-2-80)
P
11.8
Temperature rises not exceeding values in table 3
on horizontal support with a
duct with a length of four times
of the duct diameter (400mm,
500mm and 600mm)
(see appended tables)
P
P
Protective devices do not operate
P
Sealing compound does not flow out
P
Fans for tropical climates: Temperature limits are
reduced by 15 K
N
TRF No. IEC60335_2_80B
TRF originator: KEMA