ProtoCom & ProtoCom Lon
TM
TM
This page intentionally left blank.
ProtoCom/ProtoCom-Lon Installation and Operation Manual Version 1.02
Published by:
Electro Industries/GaugeTechTM
1800 Shames Drive
Westbury, NY 11590
All rights reserved. No part of this publication may be reproduced or transmitted in
any form or by any means, electronic or mechanical, including photocopying, recording, or information storage or retrieval systems or any future forms of duplication, for
any purpose other than the purchaser's use, without the expressed written permission
of Electro Industries/GaugeTech.
© 2014 Electro Industries/GaugeTech
Shark® and Nexus® are registered trademarks of Electro Industries/GaugeTech. The
distinctive shapes, styles, and overall appearances of all Shark® and Nexus® devices
are trademarks of Electro Industries/GaugeTech. Communicator EXTTM and V-SwitchTM
are trademarks of Electro Industries/GaugeTech.
Microsoft® and Windows® are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or other countries.
Powered by FieldServer.
Metasys® is a registered trademark of Johnson Controls, Inc.
LonWorks® is a registered trademark of Echelon Corp.
BACnet® is a registered trademark of ASHRAE.
Modbus® is a registered trademark of Schneider Electric, licensed to the Modus
Organization, Inc.
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
i
This page intentionally left blank.
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
ii
Customer Service and Support
Customer support is available 9:00 am to 4:30 pm, Eastern Standard Time, Monday
through Friday. Please have the model, serial number and a detailed problem description available. If the problem concerns a particular reading, please have all meter
readings available. When returning any merchandise to EIG, a return materials
authorization number is required. For customer or technical assistance, repair or
calibration, phone 516-334-0870 or fax 516-338-4741.
Product Warranty
Electro Industries/GaugeTech warrants all products to be free from defects in material
and workmanship for a period of four years from the date of shipment. During the
warranty period, we will, at our option, either repair or replace any product that
proves to be defective.
To exercise this warranty, fax or call our customer-support department. You will
receive prompt assistance and return instructions. Send the instrument, transportation prepaid, to EIG at 1800 Shames Drive, Westbury, NY 11590. Repairs will be made
and the instrument will be returned.
This warranty does not apply to defects resulting from unauthorized modification,
misuse, or use for any reason other than electrical power monitoring. The ProtoCom/
ProtoCom-Lon unit is not a user-serviceable product.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED
OR IMPLIED, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. ELECTRO INDUSTRIES/
GAUGETECH SHALL NOT BE LIABLE FOR ANY INDIRECT, SPECIAL OR
CONSEQUENTIAL DAMAGES ARISING FROM ANY AUTHORIZED OR
UNAUTHORIZED USE OF ANY ELECTRO INDUSTRIES/GAUGETECH
PRODUCT. LIABILITY SHALL BE LIMITED TO THE ORIGINAL COST OF
THE PRODUCT SOLD.
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
iii
Use Of Product for Protection
Our products are not to be used for primary over-current protection. Any protection
feature in our products is to be used for alarm or secondary protection only.
Disclaimer
The information presented in this publication has been carefully checked for
reliability; however, no responsibility is assumed for inaccuracies. The information
contained in this document is subject to change without notice.
Safety Symbols
In this manual, this symbol indicates that the operator must refer to
an important WARNING or CAUTION in the operating instructions.
Please see Chapter 4 for important safety information regarding
installation and hookup of the ProtoCom/ProtoCom-Lon unit.
Dans ce manuel, ce symbole indique que l’opérateur doit se référer à un important
AVERTISSEMENT ou une MISE EN GARDE dans les instructions opérationnelles.
Veuillez consulter le chapitre 4 pour des informations importantes relatives à l’installation et branchement de ProtoCom/ProtoCom-Lon.
UL Compliance
For UL compliance, the following instructions must be met when operating the
ProtoCom/ProtoCom-Lon:
• The units shall be powered by listed LPS or Class 2 power supply suited to the
expected operating temperature range.
• The interconnecting power connector and power cable shall:
• Comply with local electrical code
• Be suited to the expected operating temperature range
• Meet the current and voltage rating for the ProtoCom/ProtoCom-Lon
• Furthermore, the interconnecting power cable shall:
• Be of length not exceeding 3.05m (118.3")
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
iv
• Be constructed of materials rated VW-1 or FT-1 or better
• If the unit is to be installed in an operating environment with a temperature above
65 °C, it should be installed in a Restricted Access Area requiring a key or a special
tool to gain access.
• This device must not be connected to a LAN segment with outdoor wiring.
About Electro Industries/GaugeTech (EIG)
Founded in 1975 by engineer and inventor Dr. Samuel Kagan, Electro Industries/
GaugeTech changed the face of power monitoring forever with its first breakthrough
innovation: an affordable, easy-to-use AC power meter.
More than thirty years since its founding, Electro Industries/GaugeTech, the leader in
power monitoring and control, continues to revolutionize the industry with the highest
quality, cutting edge power monitoring and control technology on the market today.
An ISO 9001:2008 certified company, EIG sets the industry standard for advanced
power quality and reporting, revenue metering and substation data acquisition and
control. EIG products can be found on site at mainly all of today's leading manufacturers, industrial giants and utilities.
EIG products are primarily designed, manufactured, tested and calibrated at our facility in Westbury, New York.
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
v
Revision History
The following table lists revision information for this manual, Doc #E204701, the
ProtoCom/ProtoCom-Lon Installation and Operation Manual.
Version Number
Revision Date
Summary of Changes
V.1.01
8/6/2014
First release
V.1.02
9/10/2014
Section 1.9 reorganized and
Section 1.9.1 added - DIN
Rail installation instructions
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
vi
Table of Contents
Table of Contents
Customer Service and Support
iii
Product Warranty
iii
Use Of Product for Protection
iv
Disclaimer
iv
Safety Symbols
iv
UL Compliance
iv
About Electro Industries/GaugeTech (EIG)
v
Revision History
vi
1: Introduction to the ProtoCom/ProtoCom-Lon
1-1
1.1: Overview of the ProtoCom/ProtoCom-Lon Gateway
1-1
1.2: EIG Devices and Available Point Count
1-2
1.3: Specifications
1-3
1.4: ProtoCom/ProtoCom-Lon Dimensions
1-4
1.5: Electrical Connections
1-5
1.6: Use of DIP Switches
1-7
1.7: Removing the Top Cover from the ProtoCom/ProtoCom-Lon
(ONLY if Necessary)
1-8
1.7.1: Replacing the Top Cover
1-11
1.8: Graphical User Interface (GUI) Configurator
1-11
1.9: ProtoCom/ProtoCom-Lon Installation
1-13
1.9.1: Mounting on a DIN Rail
1-13
1.9.2: Mounting on a Panel
1-14
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
TOC-1
Table of Contents
1.10: The Rest of This Manual
1-15
2: Using the ProtoCom/ProtoCom-Lon
2-1
2.1: Step One - Configure Modbus Communication Settings
2-1
2.2: Step Two - Select the Desired Field BAS Protocol (ProtoCom
only)
2-3
2.3: Step Three - Enable Auto-discovery
2-4
2.4: Step Four - Set MAC Address/Device Instance/Node-ID
(Proto-Com only)
2-5
2.4.1: Set MAC Address - for BACnet MS/TP Protocol Only
2-5
2.4.2: Set the Device Instance - for BACnet MS/TP and
BACnet/IP Protocols
2-6
2.4.2.1: Change Node_Offset Value
2-6
2.4.3: Device Node-ID for Metasys N2, Modbus/TCP, and DF1
Protocols
2-7
2.5: Step 5: Set the Baud Rate for BACnet MS/TP
and DF1 Protocols
2-8
2.6: Step 6 - Connect the ProtoCom/ProtoCom-Lon
to the Meter
2-9
2.6.1: Biasing the Modbus RS485 Network (only if necessary)
2-11
2.6.2: Set End of Line Termination Switch for the Modbus
RS485 Port (only if necessary)
2-12
2.7: Step 7 - Connect to the RS485/LonWorks Network
(BACnet MS/TP, Metasys N2, DF1, or LonWorks)
2.8: Step 8 - Connect Power to the ProtoCom/ProtoCom-Lon
2-13
2-14
2.9: Step 9 - Turn Off Auto-discovery After Completion to
Save Configuration
2-15
2.10: Step 10: Additional Configuration
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
2-16
Doc#
E204701
TOC-2
Table of Contents
2.10.1: Use the Web GUI to Configure IP Address for BACnet IP
and EtherNet/IP
2-16
2.10.2: Set Up a Password
2-20
2.10.3: Configure the ProtoCom-Lon
2-22
2.11: Step 11 - Use the CAS BACnet Explorer to Validate the
ProtoCom in the Field (BACnet MS/TP or BACnet/IP)
2-24
2.11.1: CAS BACnet Setup
2-26
3: Device Communication
3-1
3.1: LED Diagnostics for Modbus RTU Communications Between
ProtoCom/ProtoCom-Lon and Devices
3-1
3.2: Communication Problems
3-2
3.2.1: No Communication on Modbus RTU (Meter) Side
3-2
3.2.2: Field Communication Problems
3-2
A: Protocol Data Points for EIG Meters
A-1
A.1: Shark® 100 Meter
A-2
A.2: Shark® 200 Meter
A-4
A.3: Nexus® 1252/1262/1272 Meters
A-7
A.4: DMMS 425 Meter
A-9
A.5: Nexus® 1500 Meter
A-11
A.6: MP200-Y Metering System
A-13
A.7: MP200-S Metering System
A-20
B: MAC Address DIP Switch Settings
B-1
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
TOC-3
Table of Contents
This page intentionally left blank.
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
TOC-4
1: Introduction to the ProtoCom/ProtoCom-Lon
1: Introduction to the ProtoCom/
ProtoCom-Lon
1.1: Overview of the ProtoCom/ProtoCom-Lon Gateway
The ProtoCom/ProtoComLon is an external, high
performance Building Automation System (BAS)
multi-protocol gateway that
is pre-configured to automatically communicate
between Electro Industries/
Gaugetech (EIG) meters
and various building automation protocols.
The ProtoCom supports:
Figure 1.1: ProtoCom/ProtoCom-Lon
BACnet® MS/TP, BACnet®/IP, Johnson Controls’ Metasys® N2, EtherNet/IP and DF1,
and Modbus® TCP protocols; and the ProtoCom-Lon supports the LonWorks® protocol. With the ProtoCom, the meters’ Modbus communication is converted into BACnet
or other popular BAS protocols. With the ProtoCom-Lon, the meters’ Modbus communication is converted into LonWorks® protocol.
The ProtoCom/ProtoCom-Lon connects to the EIG meter’s RS485 port. Once
connected, the ProtoCom/ProtoCom-Lon unit auto-detects the EIG meter model it is
connected to, and loads the pre-configured protocol data points for that meter, e.g.,
the Shark® 200 meter’s BACnet® objects. You do not need to do manual mapping of
the meter’s Modbus points.
The ProtoCom/ProtoCom-Lon is shipped as a kit (ProtoCom-KT/ProtoCom-Lon-KT)
which consists of the unit, a power supply, a communication cable, a one page Quickstart guide, and this manual on a CD.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
1-1
1: Introduction to the ProtoCom/ProtoCom-Lon
1.2: EIG Devices and Available Point Count
The total number of devices attached to ProtoCom cannot exceed 1500 Modbus
registers for BACnet MS/TP, BACnet/IP, Modbus/TCP, Metasys N2, EtherNet/IP, or DF1.
The total number of devices attached to ProtoCom-Lon cannot exceed 1000 Modbus
registers for LonWorks.
Refer to the following table for the supported EIG meters and their associated data
points.
Point
Count
Devices
Shark® 100 Meter
56
Shark® 200 Meter
68
Nexus® 1252 1262 1272 Meters
48
DMMS 425 Meter
46
Nexus® 1500 Meter
56
MP200-Y Metering System
241
MP200-S Metering System
571
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
1-2
1: Introduction to the ProtoCom/ProtoCom-Lon
1.3: Specifications
Electrical
Connections
Approvals:
ProtoCom
One 6‐pin Phoenix connector, one RS485 +/‐
ground port, power +/‐ frame ground port
One 3‐pin RS485 Phoenix connector, one
RS485 +/‐ ground port
One Ethernet‐10/100 Ethernet port
ProtoCom‐Lon
One 6‐pin Phoenix connector, one RS485 +/‐
ground port, power +/‐ frame ground port
One Ethernet 10/100 BaseT port
One FTT‐10 LonWorks port
CE Certified; TUV approved to UL 916, EN 60950‐1, EN 50491‐3 and CSA C22‐2 standards;
FCC Class A Part 15; OPC Self‐tested for Compliance; RoHS Compliant; CSA 205 Approved
Power
Multi‐mode power adapter: 9‐30VDC or 12 ‐ 24VAC
Requirements
Physical
11.5 cm L x 8.3 cm W x 4.1 cm H (4.5 x 3.2 x 1.6 in.)
Dimensions
Weight:
0.2 kg (0.4 lbs)
Operating
‐40°C to 75°C (‐40°F to167°F) Temperature: Surge Suppression EN61000‐4‐2 ESD EN61000‐4‐3 EMC EN61000‐4‐4 EFT
Humidity:
5 ‐ 90% RH (non‐condensing)
(Specifications subject to change without notice)
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
1-3
1: Introduction to the ProtoCom/ProtoCom-Lon
1.4: ProtoCom/ProtoCom-Lon Dimensions
Figure 1.2: ProtoCom Dimensions in inches[cm]
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
1-4
1: Introduction to the ProtoCom/ProtoCom-Lon
1.5: Electrical Connections
RS485 Port to Field Protocol
LEDs: Field RS485 Rx/Tx
End of Line Termination Switch
LEDs: RUN, ERR, Offline, RUN2
Additional DIP Switches:
Only A1 and A2 are Enabled
A Bank - MAC Address
B Bank - Baud Rate
S Bank - Protocol/
Config
PWR
LEDs
RS485 Bias Jumpers
SPL
RUN
ERR
RX
TX
PWR
RS485 Termination
Jumper
6-pin Connector - Host RS485 and Power Connections
Figure 1.3: ProtoCom Electrical Connections
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
1-5
1: Introduction to the ProtoCom/ProtoCom-Lon
R
LonWorks Field Connection
LonWorks LED
LonWorks Service Pin
A Bank - Node-ID
RUN LED
Additional DIP Switches:
Only A1 and A2 are
Enabled
B Bank - Baud Rate
S Bank - Protocol/
Config
LonWorks Rx
LEDs
RS485 Bias Jumpers
SPL
RUN
ERR
RX
TX
PWR
RS485 Termination
Jumper
6-pin Connector - Host RS485 and Power Connections
Figure 1.4: ProtoCom-Lon Electrical Connections
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
1-6
1: Introduction to the ProtoCom/ProtoCom-Lon
1.6: Use of DIP Switches
The ProtoCom/ProtoCom-Lon makes use of DIP Switches for many of its settings.
There are 3 banks of DIP Switches on the ProtoCom/ProtoCom-Lon, but on the
ProtoCom-Lon the S bank of DIP Switches is disabled, as it is not used. See the figure
below.
WARNING! When setting DIP Switches, ensure that power to the
ProtoCom/ProtoCom-Lon is OFF. AVERTISSEMENT! Lors de la configuration des commutateurs DIP, veiller à ce que l’alimentation au ProtoCom/ProtoCom-Lon est DÉSACTIVÉE.
DIP Switch
OFF
ON
Figure 1.5: DIP Switches
• To set a DIP Switch ON, move it toward the center of the ProtoCom/ProtoCom-Lon.
• To set a DIP Switch OFF, move it toward the outside edge of the ProtoCom/ProtoCom-Lon.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
1-7
1: Introduction to the ProtoCom/ProtoCom-Lon
1.7: Removing the Top Cover from the ProtoCom/ProtoCom-Lon
(ONLY if Necessary)
There are two situations (biasing and end-of-line termination, described in Chapter 2)
in which you may need to adjust internal jumpers. To do so you need to separate the
top cover from the main part of the unit.
CAUTION! Be sure the ProtoCom/ProtoCom-Lon is
POWERED OFF. ATTENTION! Veiller à ce que l’alimentation au
ProtoCom/ProtoCom-Lon est DÉSACTIVÉE.
Recommended Procedure to remove the top cover:
Using a flat-sided screw driver or similar tool, gently insert it into the 4 slots in the
back of the ProtoCom/ProtoCom-Lon, alternating between slots until the cover is loosened enough to be removed. Refer to the diagram below.
Slots for
removing
cover (4)
Figure 1.6: Slots in ProtoCom/ProtoCom-Lon Back
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
1-8
1: Introduction to the ProtoCom/ProtoCom-Lon
Alternate Procedure to remove the top cover:
1. Hold the ProtoCom/ProtoCom-Lon firmly with both hands and turn it over, so that
the back is facing you.
2. Position your thumbs as shown in the figure below and press outward on both sides
to fractionally move the sides away from the back of the unit.
FIELD
Connector
2.Put right thumb here
1.Put left thumb here
3.Pull outward slightly
with thumbs on both
left and right edges
of top cover (in
direction of red
arrows)
4.Using either index
finger, pull forward
on the FIELD
connector to move
the main unit toward
you about .25”
Figure 1.7: Removing the Top Cover, Part 1
3. While keeping your thumbs in this position, use your index finger to pull the top
RS485 connector (labeled Field) toward you. The top back of the ProtoCom will be
freed from the top cover and move toward you about .25”.
4. Keeping the back of the ProtoCom facing you, turn the unit so that the 6 pin
connector (labeled HOST) is at the top. Once again, press outward with your
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
1-9
1: Introduction to the ProtoCom/ProtoCom-Lon
thumbs as shown in the diagram below and pull the HOST connector toward you.
The main part of the ProtoCom/ProtoCom-Lon will be freed from the top cover.
HOST
Connector
2.Put right thumb here
1.Put left thumb here
3.Pull outward slightly
with thumbs on both
left and right edges
of top cover (in
direction of red
arrows)
4.Using either index
finger, pull forward
on the HOST
connector to free the
main unit
Figure 1.8: Removing the Top Cover, Part 2
NOTE: The plastic LED lens will come loose when the top cover is removed. It
must be replaced as shown in 9he drawing below.
Plastic
LED
Lens
fits here
Figure 1.9: Position of the LED Lens
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
1-10
1: Introduction to the ProtoCom/ProtoCom-Lon
1.7.1: Replacing the Top Cover
To replace the cover:
1. Make sure the LED lens has been returned to its correct position (see Figure 1.8).
2. Carefully position the top cover over the main unit and press gently until it clicks
into place.
1.8: Graphical User Interface (GUI) Configurator
The ProtoCom/ProtoCom-Lon has an embedded GUI Configurator which can be used
to program the Node Offset or change the IP address (see Section 2.10.1), or to set
up a password for the ProtoCom/ProtoCom-Lon (see Section 2.10.2).
To open the GUI Configurator:
1. Connect a standard CAT5 Ethernet cable (straight or crossover) from your PC to the
RJ45 Ethernet port on the ProtoCom/ProtoCom-Lon.
Insert the Ethernet
cable into the unit’s
RJ45 port
Figure 1.10: ProtoCom/ProtoCom-Lon Ethernet Port
2. The Default IP Address of ProtoCom/ProtoCom-Lon is 192.168.1.24, and the
Subnet Mask is 255.255.255.0. If the PC and ProtoCom/ProtoCom-Lon are on
different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx
network:
a. Go to
>
>
b. Right-click on Local Area Connection > Properties.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
1-11
1: Introduction to the ProtoCom/ProtoCom-Lon
c. Highlight
>
d. Select: Use the following IP address and enter the information below.
e. Click
twice.
3. Open a browser application on your PC.
NOTE: You do not need to be connected to the Internet.
4. Type the ProtoCom/ProtoCom-Lon’s default IP address 192.168.1.24 in the browser
address bar and press Enter to open the GUI. You will see the screen shown below.
NOTES:
• The example screen above is for a ProtoCom running BACnet MSTP. The screen will
look a bit different if you are running another protocol.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
1-12
1: Introduction to the ProtoCom/ProtoCom-Lon
• If the IP address of the ProtoCom has been changed by previous configuration, you
will need to get the assigned IP address from the network administrator.
1.9: ProtoCom/ProtoCom-Lon Installation
You have two choices for installing the ProtoCom/ProtoCom-Lon:
•
Mounting on a DIN rail using the DIN Rail clip that came attached to the unit
•
Mounting on a panel using the unit’s mounting holes
1.9.1: Mounting on a DIN Rail
The ProtoCom/ProtoCom-Lon comes with an attached DIN Rail clip.
Top edge of clip
Butterfly spring
Two screws hold the
clip onto the unit
DIN Rail clip
Bottom edge of clip
Figure 1.11: DIN Rail Clip
To mount the unit on a DIN Rail:
1. Latch the top edge of the clip onto the DIN Rail and push down on the unit to
compress the butterfly spring.
2. Clip the bottom edge of the clip onto the DIN rail and stop pushing down on the
unit. The butterfly spring will hold the unit in place.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
1-13
1: Introduction to the ProtoCom/ProtoCom-Lon
To remove the unit from the DIN Rail:
1. Push down on the unit to compress the butterfly spring.
2. Pull the bottom of the unit away from the DIN Rail to release the bottom edge of
the clip.
3. Unhook the clip from the top of the DIN Rail.
1.9.2: Mounting on a Panel
The ProtoCom/ProtoCom-Lon has mounting holes in its tabs for installation in a panel.
Mounting Holes
Figure 1.12: Location of Mounting Holes
1. Using a #1 flat-blade screwdriver, unscrew the two screws holding the DIN Rail clip
to the back of the ProtoCom/ProtoCom-Lom (see Figure 1.11) and remove the clip.
2. Verify that the area where the unit is to be mounted allows proper clearance for all
connections and mount the unit using the holes provided, spaced 3.25" apart.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
1-14
1: Introduction to the ProtoCom/ProtoCom-Lon
1.10: Navigating This Manual
Chapter 2 explains how to use the ProtoCom/ProtoCom-Lon with EIG meters,
including configuration and wiring.
Chapter 3 contains information on device communication.
Appendix A contains the EIG meters points list for the supported protocols.
Appendix B contains the A Bank DIP Switch settings for MAC address.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
1-15
1: Introduction to the ProtoCom/ProtoCom-Lon
This page intentionally left blank.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
1-16
2: Using the ProtoCom/ProtoCom-Lon
2: Using the ProtoCom/ProtoCom-Lon
This chapter outlines the procedure for setting up communication between the ProtoCom/ProtoCom-Lon and an EIG meter.
2.1: Step One - Configure Modbus Communication Settings
The ProtoCom/ProtoCom-Lon is designed to connect to the RS485 Modbus port of an
EIG power meter and to convert the serial communication to the desired protocol.
Depending on the meter’s point count (see Section 1.2), the ProtoCom/ProtoCom-Lon
can communicate with more than one meter. Each meter must have an independent
RS485 Modbus address. See the example configuration below.
R
BACnet Building Management System
BACnet/IP
ProtoCom
RS485
R
Shark 200 Meter
R
Shark 200 Meter
R
Nexus 1500 Meter
Figure 2.1: Example of Meters, ProtoCom, and Protocol Communication
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-1
2: Using the ProtoCom/ProtoCom-Lon
All devices connected to the ProtoCom/ProtoCom-Lon MUST have the same Baud
Rate, Data Bits, Stop Bits, and Parity. Refer to the following table, which shows the
default communication settings.
Serial Port Setting
Device
Protocol
Modbus RTU
Baud Rate
9600
Parity
None
Data Bits
8
Stop Bits
1
1. Assign a Modbus Address to each of the devices attached to the ProtoCom/ProtoCom-Lon. The Modbus Address needs to be uniquely assigned between 1 and 255.
2. Record the Modbus Address assigned to each device.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-2
2: Using the ProtoCom/ProtoCom-Lon
2.2: Step Two - Select the Desired Field BAS Protocol (ProtoCom
only)
You will use the S Bank Dip Switches to choose from BACnet MS/TP, BACnet/IP,
Modbus/TCP, Metasys N2, EtherNet/IP, or DF1 (refer to Section 1.6 for an explanation
of the DIP switches). Note that the ProtoCom’s default setting enables BACnet, so you
don’t need to change this setting unless you want to use another protocol.
WARNING! When setting DIP Switches, please ensure that power to the
board is OFF. AVERTISSEMENT! Lors de la configuration des commutateurs
DIP, veiller à ce que l’alimentation au ProtoCom/ProtoCom-Lon est DÉSACTIVÉE.
S0 S1 S2 S3
Figure 2.2: S Bank of DIP Switches
• The S bank of DIP switches, S0 - S3 is used to select BACnet MS/TP, BACnet/IP,
Modbus/TCP, Metasys N2, EtherNet/IP, or DF1 protocols on ProtoCom.
• The following chart describes S0 - S3 DIP switch configuration settings for the
devices to support BACnet MS/TP, BACnet/IP, Modbus TCP, Metasys N2,
EtherNet/IP, or DF1 protocols on a ProtoCom.
ProtoCom
Protocol
BACnet IP
BACnet MSTP
Metasys N2
EtherNet/IP
DF1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
S0
Off
On
Off
On
Off
Doc#
S Bank DIP Switches
S1
S2
Off
Off
Off
Off
On
Off
On
Off
Off
On
E204701
2-3
2: Using the ProtoCom/ProtoCom-Lon
NOTES:
• When the S bank of switches are all off (this is the default setting) BACnet/IP is
enabled.
• The OFF position is when the DIP switches are set closest to the outside of the
box.
•
On the ProtoCom-Lon, the S bank DIP switches are disabled, since the Field
Protocol is always LonWorks.
2.3: Step Three - Enable Auto-discovery
The ProtoCom/ProtoCom-Lon has an Auto-discovery feature that lets it determine the
EIG meter model it is connected to, and automatically load the appropriate points list
for the protocol you choose. This makes configuration simple. The ProtoCom/ProtoCom-Lon allows a user to put different EIG meters on the RS485 bus, and have the
ProtoCom/ProtoCom-Lon automatically discover them and make them available via
the selected protocol.
Auto-discovery is set in the S Dip Switch bank’s S3 switch (see DIP Switch figure on
the previous page). The setting configuration is shown in the table below.
ProtoCom
Auto‐Discovery Settings
Auto‐Discovery ON ‐ Build New Configuration
Auto‐Discovery OFF ‐ Save Current Configuration
S Bank DIP Switches
S3
On
Off
When installing the ProtoCom for the first time, set S3 to the ON position to enable
Auto-discovery. The ON position is when the DIP switches are set closest to the inside
of the box.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-4
2: Using the ProtoCom/ProtoCom-Lon
2.4: Step Four - Set MAC Address/Device Instance/Node-ID (ProtoCom only)
The Building Management System (BMS) in use must be able to distinguish the ProtoCom, and the meters attached to it, from all of the other devices in the BMS system.
For this reason, the ProtoCom and connected devices must be given a unique ID. The
specific ID you need to set depends on the BMS protocol you’ll be using.
• MAC Address - used for BACnet MS/TP protocol only (Section 2.4.1): this is an
eight bit address used to identify devices on a single RS485 subnet (the devices
attached to the ProtoCom when using BACnet MS/TP). It identifies the ProtoCom to
the BACnet MS/TP protocol.
• Device Instance - used for both BACnet MS/TP and BACnet/IP (Section 2.4.2): the
Device Instance is used to set up a unique identifier for each of the meters
attached to the ProtoCom.
• Node-ID - used for Metasys N2, Modbus/TCP, and DF1 (Section 2.4.3): this is the
unique identifier for each of the meters attached to the ProtoCom.
2.4.1: Set MAC Address - for BACnet MS/TP Protocol Only
• Note that only 1 MAC address is set for the ProtoCom, regardless of how many
devices are connected to it.
• Set the BACnet MS/TP MAC address between 1 and 127 (Master MAC address):
this is so that the BMS system can find the ProtoCom via BACnet auto discovery.
• Use DIP switches A0 - A7 to assign the MAC Address for BACnet MS/TP.
Figure 2.2: A Bank of DIP Switches
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-5
2: Using the ProtoCom/ProtoCom-Lon
NOTES:
• Refer to Appendix C.1 for the MAC address DIP switch chart.
• When using Metasys N2, Modbus/TCP, and DF1 the A Bank of DIP
switches are disabled and not used. They should be set to the OFF
position.
2.4.2: Set the Device Instance - for BACnet MS/TP and BACnet/IP
Protocols
The BACnet protocol needs a value called Device Instance for each device in the
system. This Device Instance is used to uniquely identify the device in a BACnet
system. The BACnet Device Instance is set up by adding a value known as the
Node_Offset to the Modbus Address that you assigned to the device in step 1
(Section 2.1).
The BACnet Device Instance can range from 1 to 4,194,303. The default Node_Offset
is 50,000.
For example, using the Node_Offset default of 50,000:
a. If Device 1 has a Modbus Address of 1, Device 2 has a Modbus Address of 2,
Device 3 has a Modbus Address of 3;
b. The Device Instance for Device 1 is 50,001; for Device 2 it is 50,002; and for
Device 3 it is 50,003.
2.4.2.1: Change Node_Offset Value
If you need to, you can change the default Node_Offset from 50,000 to any number
between 1 and 4,194,302 using the GUI Configurator (see Section 1.9). Follow these
instructions:
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-6
2: Using the ProtoCom/ProtoCom-Lon
1. From the GUI Configurator screen, enter the Node_Offset you want to use. The
example screen below is for a ProtoCom configured for BACnet MS/TP protocol.
Enter a new
Node Offset
and click Submit
2. Enter the value you want to use in the Node_Offset field.
3. Click Submit. The BACnet device instances will be set by taking the new Node_Offset and adding it to the Modbus Address that you assigned to the device (Section
2.1).
For example, using a Node_Offset changed to 20,000:
• If Device 1 has a Modbus Address of 1, Device 2 has a Modbus Address of 2,
Device 3 has a Modbus Address of 3;
• The Device Instance for Device 1 is 20,001; for Device 2 it is 20,002; and for
Device 3 it is 20,003.
2.4.3: Device Node-ID for Metasys N2, Modbus/TCP, and DF1
Protocols
The Modbus Addresses that you assigned to the devices attached to the ProtoCom in
Section 2.1 will be the Metasy N2, Modbus TCP, and DF1 Node_ID's for the field
protocols. You don’t need to set up any other identification.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-7
2: Using the ProtoCom/ProtoCom-Lon
2.5: Step 5: Set the Baud Rate for BACnet MS/TP and DF1 Protocols
Use DIP Switches B0 - B3 to set the serial baud rate to match the baud rate provided
by the BMS for BACnet MS/TP and DF1.
B0 B1 B2 B3
Figure 2.3: B Bank of DIP Switches
NOTES:
• The baud rate for Metasys N2 protocol is set to 9600: the B bank of DIP Switches is
disabled for Metasys N2 on ProtoCom, since they are not needed.
• The B bank of DIP switches is disabled for the ProtoCom-Lon.
• The default setting of the ProtoCom is 38400.
The following table shows the Baud Rate DIP Switch selection.
Baud
9600
19200
38400
57600
76800
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
B0
On
Off
On
Off
On
B1
On
Off
On
Off
Off
Doc#
B2
On
Off
Off
On
On
B3
Off
On
On
On
On
E204701
2-8
2: Using the ProtoCom/ProtoCom-Lon
2.6: Step 6 - Connect the ProtoCom/ProtoCom-Lon to the Meter
The six pin connector at the bottom of the ProtoCom/ProtoCom-Lon (labeled HOST) is
used to connect the ProtoCom to the EIG meter and to the power supply. (See Section
1.5 for detailed information on the ProtoCom/ProtoCom-Lon’s connections).
• Pins 1 through 3 are for the meter’s RS485 connection, though the RS485 GND (Pin
3) is not typically connected.
• Pins 4 through 6 are for power.
CAUTION! DO NOT CONNECT POWER YET.
Device Pins
Pin RS‐485 +
Pin RS‐485 ‐
Pin GND
Power In (+)
Power In (‐)
Frame Ground
ProtoCom Pin #
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
Pin assignment
RS‐485 +
RS‐485 ‐
RS‐485 GND
V +
V ‐
FRAME GND
Figure 2.4: HOST RS485 Connections
The EIG meters have the following RS485 connections:
• The Shark® meters, the Nexus® meters, and the MP200 Metering System have a
two wire RS485 connection that can connect directly to the ProtoCom’s RS485
connections:
1. Connect the meter’s B+ to the ProtoCom/ProtoCom-Lon’s Tx +/- connection.
2. Connect the meter’s A- to the ProtoCom/ProtoCom-Lon’s Rx +/- connection.
• The DMMS 425 meter has a four wire RS485 connection.
1. Connect the meter’s R + and T+ wires together, and connect the combined
wire to the ProtoCom’s Tx+/-.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-9
2: Using the ProtoCom/ProtoCom-Lon
2. Connect the R- and T- wires together and connect the combined wire to the
ProtoCom/ProtoCom-Lon’s Rx +/-.
See the diagram below.
DMMS 425
Meter
RS485
Communications
Port
G
R+ T+
R-
T-
ProtoCom/ProtoCom-Lon
Tx+/Rx+/-Gnd
Figure 2.5: Connecting RS485 between DMMS 425 and ProtoCom/ProtoCom-Lon
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-10
2: Using the ProtoCom/ProtoCom-Lon
2.6.1: Biasing the Modbus RS485 Network (only if necessary)
An RS485 network with more than one device needs to have biasing to ensure proper
communication. The biasing only needs to be done on one device. If necessary, you
can set up biasing on the ProtoCom. Refer to Section 1.8 for instructions on removing
and replacing the unit’s top cover.
The ProtoCom has 530 Ohm resistors that can be used to set the biasing. The
default position of the Biasing jumpers is OFF. The OFF position is when the 2 RED
biasing jumpers straddle the 4 pins closest to the outside of the board of the ProtoCom. To turn biasing on, move the jumpers to the right so that they straddle the four
inside pins. See the figure below.
To turn biasing
ON, move the
red jumper to
the right so
that it covers
these 2 pins
Figure 2.6: Biasing Jumpers
IMPORTANT!
• Only turn biasing ON if the Building Management System (BMS) cannot see more
than one device connected to the ProtoCom and you have checked that all of the
settings (Modbus COM settings, wiring, and DIP switches) are correct.
• Do not touch any other parts of the main board.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-11
2: Using the ProtoCom/ProtoCom-Lon
2.6.2: Set End of Line Termination Switch for the Modbus RS485 Port
(only if necessary)
On long RS485 cabling runs, the RS485 trunk must be properly terminated at each
end. The ProtoCom has a blue End-of-Line (EOL) terminating switch (see the figure
below). On short cabling runs the EOL switch does not to need to be turned ON;
therefore the default setting for this ProtoCom’s EOL switch is OFF. Refer to Section
1.8 for instructions on removing and replacing the unit’s top cover.
If the ProtoCom is placed at one of the ends of the trunk on a long RS485 cabling run,
turn the Blue RS485 End-of- Line Terminating switch to the ON position.
To turn the EOL switch
ON, move the blue
jumper down so that it
covers these 2 pins
Figure 2.7: EOL Termination Jumpers
IMPORTANT! Do not touch any other parts of the main board.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-12
2: Using the ProtoCom/ProtoCom-Lon
2.7: Step 7 - Connect to the RS485/LonWorks Network (BACnet
MS/TP, Metasys N2, DF1, or LonWorks)
BACnet MS/TP, Metasys N2, or DF1: Wire the Field Port to the RS485
Network
Connect the BACnet MS/TP or Metasys N2 RS485 network wires to the 3-pin RS485
connector (labeled FIELD) on the top of the ProtoCom, as shown below.
BMS RS485 Wiring
RS485 +
RS485 ‐
‐
ProtoCom Pin #
Pin 1
Pin 2
Pin 3
Pin Assignment
RS‐485 +
RS‐485 ‐
RS‐485 GND
Figure 2.8: FIELD RS485 Wiring
NOTE: The RS485 GND (Pin 3) is not typically connected.
If the ProtoCom is the last device on the BACnet MS/TP, Metasys N2, or DF1 trunk,
the End-Of-Line Termination (EOL) Switch needs to be enabled. See Section 1.8 for
instructions on removing and replacing the unit’s top cover.
To enable the switch: using a thin, pointed tool, move it to the left, as shown in the
diagram below.
Push the white
rectangle to the
left
Figure 2.9: EOL Switch Setting
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-13
2: Using the ProtoCom/ProtoCom-Lon
ProtoCom-Lon: Wire the Field Port to the LonWorks Network
Connect the ProtoCom-Lon to the field network with the LonWorks terminal using a
twisted pair non-shielded cable. LonWorks has no polarity.
Figure 2.10: LonWorks FIELD Terminal
2.8: Step 8 - Connect Power to the ProtoCom/ProtoCom-Lon
Apply power to the ProtoCom/ProtoCom-Lon as show in the figure below. Ensure that
the power supply used complies with the specifications provided in Section 1.4.
The ProtoCom/ProtoCom-Lon accepts either 9-30VDC or 12-24 VAC on pins 4 and 5.
Power Requirement for ProtoCom/ProtoCom‐Lon at 9V through 30 VDC or 12‐24 VAC
Current Draw Type
ProtoCom Family
12VDC/VAC
24VDC/VAC
30VDC
ProtoCom (Typical)
170mA
100mA
80mA
ProtoCom (Maximum)
240mA
140mA
100mA
ProtoCom‐Lon (Typical)
210mA
100mA
90mA
ProtoCom‐Lon (Maximum)
250mA
130mA
100mA
Note: These values are ‘nominal’ and a safety margin should be added to the power supply of the host system. A
safety margin of 25% is recommended.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-14
2: Using the ProtoCom/ProtoCom-Lon
Power to ProtoCom/
ProtoCom‐Lon
Power In (+)
Power In (‐)
Frame Ground
ProtoCom/
ProtoCom‐Lon
Pin
Assignment
Pin #
Pin 4
Pin 5
Pin 6
V +
V ‐
FRAME GND
Figure 2.11: Connecting Power to the ProtoCom/ProtoCom-Lon
2.9: Step 9 - Turn Off Auto-discovery After Completion to Save
Configuration
The S3 DIP Switch for enabling Auto-discovery was set in step 3, Section 2.3. Once
power is applied to a ProtoCom/ProtoCom-Lon that is set to enable Auto-discovery,
the unit takes about 3 minutes to complete the discovery of all of the EIG meters
attached to the ProtoCom/ProtoCom-Lon and the loading of their data points.
Once the ProtoCom/ProtoCom-Lon has discovered all of the connected EIG meters,
set the S3 DIP switch to the OFF position to save the current configuration. The OFF
position is when the DIP switches are set closest to the outside of the box.
ProtoCom/ProtoCom‐Lon S3 DIP Switch Auto‐discovery Mode
Auto‐discovery ON – Build New Configuration
Auto‐discovery OFF – Save Current Configuration
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
S3
On
Off
2-15
2: Using the ProtoCom/ProtoCom-Lon
2.10: Step 10: Additional Configuration
Depending on the protocol being used and the specific needs of your application, you
may use the following configuration instructions.
2.10.1: Use the Web GUI to Configure IP Address for BACnet IP and
EtherNet/IP
Follow the instructions in Section 1.9 to connect to the ProtoCom via its Ethernet port
and to bring up the Web GUI.
NOTE: Below the Active Profiles heading you should see profiles listed for connected
devices. If no profiles are displayed, check the wiring, baud rate, and DIP switch settings, because there is a problem with device communication. All the active profiles
must show the correct Addresses before proceeding.
Connected devices
found through
Auto-Discovery
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-16
2: Using the ProtoCom/ProtoCom-Lon
Set the IP Address for Field Network (BACnet/IP, Modbus TCP, and
Ethernet/IP Only):
1. From the Web Configurator page, click the Diagnostics & Debugging button in the
bottom right side of the page.
Click this button
BACnet/IP Configurator Webpage
Click this button
Ethernet/IP Configurator Webpage
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-17
2: Using the ProtoCom/ProtoCom-Lon
2. Under Navigation, on the left side of the screen, click Setup>Network Settings.
3. The current network settings are shown in the screen.
Enter new
IP address
here
4. Modify the IP address (N1 IP address field) of the ProtoCom’s Ethernet port.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-18
2: Using the ProtoCom/ProtoCom-Lon
5. If necessary, change the Netmask (N1 Netmask field) by entering a new Subnet
Mask.
6. If necessary, change the IP Gateway (Default Gateway field) by entering a new IP
Gateway.
NOTE: If the ProtoCom is connected to a router, the IP Gateway of the ProtoCom
should be set to the IP address of the router.
7. Reset the ProtoCom by clicking the System Restart button at the bottom of the
page.
8. Unplug the Ethernet cable from the PC and connect it to the network hub or router.
9. Record the IP address you assigned to the ProtoCom and store it in a safe place.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-19
2: Using the ProtoCom/ProtoCom-Lon
2.10.2: Set Up a Password
The ProtoCom/ProtoCom-Lon comes with password disabled, but you can easily
configure a password for it.
There are 2 password access levels:
• Admin: the Admin account has unrestricted access to the unit.
• User: the User account can view any ProtoCom/ProtoCom-Lon information, but
cannot make any changes to settings or restart the unit.
1. Type the IP address of the ProtoCom/ProtoCom-Lon into your PC’s browser.
Click this button
2. From the Web Configurator landing page, click the Diagnostics & Debugging button
on the bottom right side of the page to access the FST Web GUI.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-20
2: Using the ProtoCom/ProtoCom-Lon
3. From the navigation tree on the left side of the page, click Setup>Passwords.
4. From the pull-down menu, select Admin or User to set the password for that
account.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-21
2: Using the ProtoCom/ProtoCom-Lon
5. Enter the current password (if there is one) and the new password in both the New
Password and Confirm New Password fields. The password must be a minimum of
eight characters; it is case sensitive. Be sure to write down the password and store
it in a safe place.
6. Click Update Password to save your changes.
7. Repeat the process for the other account, if desired.
8. You can close the browser window.
NOTE: You can disable an active password by leaving the New Password and Confirm
New Password fields blank and then clicking the Update Password button.
2.10.3: Configure the ProtoCom-Lon
Following are instructions specific to the ProtoCom-Lon configuration.
Commission the ProtoCom-Lon on a LonWorks Network
Commissioning can only be performed by the LonWorks administrator. The user will
be prompted by the LonWorks Administrator to activate the Service Pin on the ProtoCom-Lon at the correct step of the commissioning process, which varies for each
LonWorks Network Management Tool.
Figure 2.12: Location of ProtoCom-Lon Service Pin Instructions
Upload an XIF File from the ProtoCom-Lon Using the Using the Web GUI
You may need an XIF file. If so, first follow the instructions in Section 1.9 to connect
to the ProtoCom-Lon via its Ethernet port.
Open a web browser and go to the following address:
IP address of ProtoCessor/fserver.xif
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-22
2: Using the ProtoCom/ProtoCom-Lon
For example: 192.168.1.24/fserver.xif
If the web browser prompts you to save the file, save it to the PC. If the web browser
displays the xif file as a web page (see the example shown below), right-click in the
page and save the file to your PC as fserver.xif.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-23
2: Using the ProtoCom/ProtoCom-Lon
2.11: Step 11 - Use the CAS BACnet Explorer to Validate the
ProtoCom in the Field (BACnet MS/TP or BACnet/IP)
When you purchase a ProtoCom from EIG, you receive a complementary 2 week, fully
functional copy of CAS BACnet Explorer (through Chipkin Automation) that can be
used to validate BACnet MS/TP and/or BACnet/IP communications in the field without
having to have the BMS Integrator on site.
NOTE: To test BACnet MS/TP you will need a Serial to RS485 or a USB to RS485
converter.
Download the CAS Explorer and Request an Activation Key
To request the complementary BACnet CAS key:
1. Go to http://app.chipkin.com/activation/twoweek/.
2. Fill in all the information and enter "Electro2013" in the Vendor Code field.
3. The key will be sent to the email address you entered.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-24
2: Using the ProtoCom/ProtoCom-Lon
4. Once you receive the email with the activation key, go to http://www.chipkin.com/
technical-resources/cas-bacnet-explorer/.
5.. Scroll down until you see the Download icon.
6. Click Executable (dmb) and run the file. A Setup Wizard will step you through
downloading the CAS Bacnet Explorer application.
7. Follow the prompts. When you finish installation a window will prompt you to enter
a license.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-25
2: Using the ProtoCom/ProtoCom-Lon
8. When you click OK, you will see the screen below.
9. Enter your email address and paste the activation key that was sent to your email.
10. Click the Activate button to begin your two week free trial.
2.11.1: CAS BACnet Setup
Following is an example of how to configure the ProtoCom with a BACnet Explorer.
The one shown here was developed by Chipkin Automation Systems. It is subject to
all of their licenses and restrictions. Please read and follow their license requirements
before using.
These are the instructions to set up CAS BACnet Explorer for the first time on BACnet
MS/ST and BACnet/IP.
CAS BACnet MS/TP Setup
1. Using the Serial to RS485 or USB to RS485 converter, connect it to your PC and the
3 Pin BACnet MS/TP connector on the ProtoCom (the FIELD connector).
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-26
2: Using the ProtoCom/ProtoCom-Lon
2. Open the CAS BACnet Explorer application to display the main screen.
3. Click on Settings.
4. In the Networks section, check the BACnet MSTP box and uncheck the BACnet/IP
and BACnet Ethernet boxes.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-27
2: Using the ProtoCom/ProtoCom-Lon
5. Set the BACnet MSTP MAC address to 0.
6. Set the BACnet MSTP Baud Rate to 38400.
7. Click OK.
3. In the bottom right-hand corner of the main screen, make sure that the BACnet
MSTP box is green.
4. Click on Discover.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-28
2: Using the ProtoCom/ProtoCom-Lon
5. Check all 4 boxes.
6. Click Send. The screen will display BACnet network information.
CAS BACnet/IP Setup
1. See Section 1.9 to set the IP address and subnet of the PC that will be running the
CAS BACnet Explorer.
2. Connect a straight or crossover Ethernet cable from the PC to the ProtoCom.
3. Open the CAS BACnet Explorer application to display the main screen.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-29
2: Using the ProtoCom/ProtoCom-Lon
4. Click on Settings.
5. In the Networks section, check the BACnet/IP box and uncheck the BACnet MSTP
and BACnet Ethernet boxes.
6. In the Select a Network Device box, select the PC’s network card by clicking on it.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-30
2: Using the ProtoCom/ProtoCom-Lon
7. Click OK.
4. In the bottom right-hand corner of the screen, make sure that the BACnet/IP box is
green.
5. Click on Discover.
6. Check all 4 boxes.
7. Click Send. The screen will display BACnet network information.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-31
2: Using the ProtoCom/ProtoCom-Lon
This page intentionally left blank.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
2-32
3: Device Communication
3: Device Communication
The ProtoCom/ProtoCom-Lon has LEDs that indicate communication between the
device and both the EIG meters and other devices it is connected to. The LEDs can be
used to diagnose communication problems.
3.1: LED Diagnostics for Modbus RTU Communications Between
ProtoCom/ProtoCom-Lon and Devices
The diagram below shows the unit’s LED Locations.
Figure 3.1: ProtoCom/ProtoCom-Lon LEDs
The table below describes the action of the LEDs.
Tag
SPL
RUN
ERR
RX
TX
PWR
Description
The SPL LED is lit if the ProtoCom/ProtoCom‐Lon is offline.
The RUN LED starts flashing 20 seconds after power up, indicating normal operation. The SYS ERR LED will be solidly lit 15 seconds after power up, and will turn off after 5 seconds. A steady red light after that time indicates there is a system error on the ProtoCom/ProtoCom‐Lon. If this occurs, check the Web GUI Error screen and report the “system error” shown in the screen to EIG’s Technical Support for analysis.
The RX LED flashes when a message is received on the Host port.
The TX LED flashes when a message is sent on the Host port.
This is the power light that should show steady green at all times when the ProtoCom/ProtoCom‐Lon is
powered on.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
3-1
3: Device Communication
3.2: Communication Problems
Communication problems can be either from the side of the meter communication
with the ProtoCom/ProtoCom-Lon or the ProtoCom/ProtoCom-Lon’s communication
with the field device.
3.2.1: No Communication on Modbus RTU (Meter) Side
If the TX/RX LEDs are not flashing rapidly, there is a communication problem on the
Modbus (Meter) side. Check the following items:
• The action of the ProtoCom/ProtoCom-Lon LEDs - see the table on page 3-1
• That the baud rate, parity, data bits, and stop bits are set correctly
• That the Modbus device address is correct
• That the wiring is correct - see chapters 1 and 2
• That all of the Modbus RTU devices were discovered in the Web Configurator (see
Section 2.10.1)
3.2.2: Field Communication Problems
To diagnose field communication problems, check the following items:
• The action of the ProtoCom/ProtoCom-Lon LEDs - see the table on page 3-1
• That the DIP switch settings for baud rate and device instance are correct - see
sections 2.4 and 2.5
• That the IP address setting is correct
• That the wiring is correct - see chapters 1 and 2
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
3-2
A: Protocol Data Points for EIG Meters
A: Protocol Data Points for EIG Meters
Lists of the protocol data points for the supported EIG meters begins on the next page.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E204701
A-1
A: Protocol Data Points for EIG Meters
A.1: Shark® 100 Meter
PointName
VoltsAͲN
VoltsBͲN
VoltsCͲN
VoltsAͲB
VoltsBͲC
VoltsCͲA
AmpsA
AmpsB
AmpsC
Watts3ͲPhtotal
VARs3ͲPhtotal
VAs3ͲPhtotal
PowerFactor3ͲPhtotal
Frequency
NeutralCurrent
WͲhoursReceived
WͲhoursDelivered
WͲhoursNet
WͲhoursTotal
VARͲhoursPositive
VARͲhoursNegative
VARͲhoursNet
VARͲhoursTotal
VAͲhoursTotal
PositiveWatts3ͲPhAvg
PositiveVARs3ͲPhAvg
NegativeWatts3ͲPhAvg
NegativeVARs3ͲPhAvg
VAs3ͲPhAvg
PositivePF3ͲPhAvg
NegativePF3ͲPFAvg
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Doc# E204701
EIPTag
Name
Flt_XXX[0]
Flt_XXX[1]
Flt_XXX[2]
Flt_XXX[3]
Flt_XXX[4]
Flt_XXX[5]
Flt_XXX[6]
Flt_XXX[7]
Flt_XXX[8]
Flt_XXX[9]
Flt_XXX[10]
Flt_XXX[11]
Flt_XXX[12]
Flt_XXX[13]
Flt_XXX[14]
S32_XXX[0]
S32_XXX[1]
S32_XXX[2]
S32_XXX[3]
S32_XXX[4]
S32_XXX[5]
S32_XXX[6]
S32_XXX[7]
S32_XXX[8]
Flt_XXX[15]
Flt_XXX[16]
Flt_XXX[17]
Flt_XXX[18]
Flt_XXX[19]
Flt_XXX[20]
Flt_XXX[21]
DF1
Address
F10:0
F10:1
F10:2
F10:3
F10:4
F10:5
F10:6
F10:7
F10:8
F10:9
F10:10
F10:11
F10:12
F10:13
F10:14
F11:0
F11:1
F11:2
F11:3
F11:4
F11:5
F11:6
F11:7
F11:8
F10:15
F10:16
F10:17
F10:18
F10:19
F10:20
F10:21
LonName
nvoVoltsAN_XXX
nvoVoltsBN_XXX
nvoVoltsCN_XXX
nvoVoltsAB_XXX
nvoVoltsBC_XXX
nvoVoltsCA_XXX
nvoAmpsA_XXX
nvoAmpsB_XXX
nvoAmpsC_XXX
nvoWatt3PhTo_XXX
nvoVAR3PhTot_XXX
nvoVA3PhTot_XXX
nvoPF3PhTot_XXX
nvoFreq_XXX
nvoNeutCurr_XXX
nvoWh_Rec_XXX
nvoWh_Del_XXX
nvoWh_Net_XXX
nvoWh_Tot_XXX
nvoVARh_Pos_XXX
nvoVARh_Neg_XXX
nvoVARh_Net_XXX
nvoVARh_Tot_XXX
nvoVAh_Tot_XXX
nvoPsWt3PhAv_XXX
nvoPsVAR3PhA_XXX
nvoNgWt3PhAv_XXX
nvoNgVAR3PhA_XXX
nvoVA3Ph_Avg_XXX
nvoPsPF3PhAv_XXX
nvoNgPF3PhAv_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-2
A: Protocol Data Points for EIG Meters
PointName
PositiveWatts3ͲPhMaxAvgDemand
PositiveVARs3ͲPhMaxAvgDemand
NegativeWatts3ͲPhMaxAvgDemand
NegativeVARs3ͲPhMaxAvgDemand
VoltsAͲN%THD
VoltsBͲN%THD
VoltsCͲN%THD
AmpsA%THD
AmpsB%THD
AmpsC%THD
MeterStatus
CTmultiplier
CTdenominator
CTnumerator
PTnumerator
PTdenominator
PThookup
PTmultiplier
SerialNumberReg1
SerialNumberReg2
SerialNumberReg3
SerialNumberReg4
SerialNumberReg5
SerialNumberReg6
SerialNumberReg7
SerialNumberReg8
PasswordforResetinuse
PasswordforConfigurationinuse
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BI
BI
BACnet
Object
ID
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
DI
DI
N2
Point
Address
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
EIPTag
Name
Flt_XXX[22]
Flt_XXX[23]
Flt_XXX[24]
Flt_XXX[25]
Dev_XXX[0]
Dev_XXX[1]
Dev_XXX[2]
Dev_XXX[3]
Dev_XXX[4]
Dev_XXX[5]
Byt_XXX[0]
Byt_XXX[1]
Byt_XXX[2]
Dev_XXX[8]
Dev_XXX[9]
Dev_XXX[10]
Byt_XXX[3]
Byt_XXX[4]
Dev_XXX[12]
Dev_XXX[13]
Dev_XXX[14]
Dev_XXX[15]
Dev_XXX[16]
Dev_XXX[17]
Dev_XXX[18]
Dev_XXX[19]
Byt_XXX[5]
Byt_XXX[6]
DF1
Address
F10:22
F10:23
F10:24
F10:25
N12:0
N12:1
N12:2
N12:3
N12:4
N12:5
N13:0
N13:1
N13:2
N12:8
N12:9
N12:10
N13:3
N13:4
N12:12
N12:13
N12:14
N12:15
N12:16
N12:17
N12:18
N12:19
N13:5
N13:6
LonName
nvoPWt3PMADm_XXX
nvoPVAR3PMAD_XXX
nvoNWt3PMADm_XXX
nvoNVAR3PMAD_XXX
nvoVltAN_THD_XXX
nvoVltBN_THD_XXX
nvoVltCN_THD_XXX
nvoAmpA_THD_XXX
nvoAmpB_THD_XXX
nvoAmpC_THD_XXX
nvoMtrStat_XXX
nvoCT_mult_XXX
nvoCT_den_XXX
nvoCT_num_XXX
nvoPT_num_XXX
nvoPT_den_XXX
nvoPT_hookup_XXX
nvoPT_mult_XXX
nvoSerNum1_XXX
nvoSerNum2_XXX
nvoSerNum3_XXX
nvoSerNum4_XXX
nvoSerNum5_XXX
nvoSerNum6_XXX
nvoSerNum7_XXX
nvoSerNum8_XXX
nvoPswdReset_XXX
nvoPswdCnfg_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E204701
A-3
A: Protocol Data Points for EIG Meters
A.2: Shark® 200 Meter
PointName
VoltsAͲN
VoltsBͲN
VoltsCͲN
VoltsAͲB
VoltsBͲC
VoltsCͲA
AmpsA
AmpsB
AmpsC
Watts3ͲPhtotal
VARs3ͲPhtotal
VAs3ͲPhtotal
PowerFactor3ͲPhtotal
Frequency
NeutralCurrent
WattsPhaseA
WattsPhaseB
WattsPhaseC
VARsPhaseA
VARsPhaseB
VARsPhaseC
VAsPhaseA
VAsPhaseB
VAsPhaseC
PowerFactorPhaseA
PowerFactorPhaseB
PowerFactorPhaseC
WͲhoursReceived
WͲhoursDelivered
WͲhoursNet
WͲhoursTotal
VARͲhoursPositive
VARͲhoursNegative
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
Doc# E204701
EIPTag
Name
Flt_XXX[0]
Flt_XXX[1]
Flt_XXX[2]
Flt_XXX[3]
Flt_XXX[4]
Flt_XXX[5]
Flt_XXX[6]
Flt_XXX[7]
Flt_XXX[8]
Flt_XXX[9]
Flt_XXX[10]
Flt_XXX[11]
Flt_XXX[12]
Flt_XXX[13]
Flt_XXX[14]
Flt_XXX[15]
Flt_XXX[16]
Flt_XXX[17]
Flt_XXX[18]
Flt_XXX[19]
Flt_XXX[20]
Flt_XXX[21]
Flt_XXX[22]
Flt_XXX[23]
Flt_XXX[24]
Flt_XXX[25]
Flt_XXX[26]
S32_XXX[0]
S32_XXX[1]
S32_XXX[2]
S32_XXX[3]
S32_XXX[4]
S32_XXX[5]
DF1
Address
F10:0
F10:1
F10:2
F10:3
F10:4
F10:5
F10:6
F10:7
F10:8
F10:9
F10:10
F10:11
F10:12
F10:13
F10:14
F10:15
F10:16
F10:17
F10:18
F10:19
F10:20
F10:21
F10:22
F10:23
F10:24
F10:25
F10:26
F11:0
F11:1
F11:2
F11:3
F11:4
F11:5
LonName
nvoVolts_AN_XXX
nvoVolts_BN_XXX
nvoVolts_CN_XXX
nvoVolts_AB_XXX
nvoVolts_BC_XXX
nvoVolts_CA_XXX
nvoAmps_A_XXX
nvoAmps_B_XXX
nvoAmps_C_XXX
nvoWatt3PhTo_XXX
nvoVAR3PhTot_XXX
nvoVA_3PhTot_XXX
nvoPF_3PhTot_XXX
nvoFreq_XXX
nvoNeut_Crnt_XXX
nvoWatts_PhA_XXX
nvoWatts_PhB_XXX
nvoWatts_PhC_XXX
nvoVARs_PhA_XXX
nvoVARs_PhB_XXX
nvoVARs_PhC_XXX
nvoVAs_PhA_XXX
nvoVAs_PhB_XXX
nvoVAs_PhC_XXX
nvoPF_PhA_XXX
nvoPF_PhB_XXX
nvoPF_PhC_XXX
nvoWh_Rec_XXX
nvoWh_Del_XXX
nvoWh_Net_XXX
nvoWh_Tot_XXX
nvoVARh_Pos_XXX
nvoVARh_Neg_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-4
A: Protocol Data Points for EIG Meters
PointName
VARͲhoursNet
VARͲhoursTotal
AmpsAAvg
AmpsBAvg
AmpsCAvg
PositiveWatts3ͲPhAvg
PositiveVARs3ͲPhAvg
NegativeWatts3ͲPhAvg
NegativeVARs3ͲPhAvg
VAs3ͲPhAvg
PositivePF3ͲPhAvg
NegativePF3ͲPFAvg
VAͲhoursTotal
MeterStatus
CurrentDate&TimeReg1
CurrentDate&TimeReg2
CurrentDate&TimeReg3
PositiveWatts3ͲPhMaxAvgDemand
PositiveVARs3ͲPhMaxAvgDemand
NegativeWatts3ͲPhMaxAvgDemand
NegativeVARs3ͲPhMaxAvgDemand
CTmultiplier
CTdenominator
CTnumerator
PTnumerator
PTdenominator
PThookup
PTmultiplier
SerialNumberReg1
SerialNumberReg2
SerialNumberReg3
SerialNumberReg4
SerialNumberReg5
SerialNumberReg6
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
Doc# E204701
EIPTag
Name
S32_XXX[6]
S32_XXX[7]
Flt_XXX[27]
Flt_XXX[28]
Flt_XXX[29]
Flt_XXX[30]
Flt_XXX[31]
Flt_XXX[32]
Flt_XXX[33]
Flt_XXX[34]
Flt_XXX[35]
Flt_XXX[36]
S32_XXX[8]
Byt_XXX[0]
Dev1_XXX[0]
Dev1_XXX[1]
Dev1_XXX[2]
Flt_XXX[37]
Flt_XXX[38]
Flt_XXX[39]
Flt_XXX[40]
Byt_XXX[1]
Byt_XXX[2]
Dev2_XXX[0]
Dev2_XXX[1]
Dev2_XXX[2]
Byt_XXX[3]
Byt_XXX[4]
Dev2_XXX[4]
Dev2_XXX[5]
Dev2_XXX[6]
Dev2_XXX[7]
Dev2_XXX[8]
Dev2_XXX[9]
DF1
Address
F11:6
F11:7
F10:27
F10:28
F10:29
F10:30
F10:31
F10:32
F10:33
F10:34
F10:35
F10:36
F11:8
N14:0
N12:0
N12:1
N12:2
F10:37
F10:38
F10:39
F10:40
N14:1
N14:2
N13:0
N13:1
N13:2
N14:3
N14:4
N13:4
N13:5
N13:6
N13:7
N13:8
N13:9
LonName
nvoVARh_Net_XXX
nvoVARh_Tot_XXX
nvoAmpA_Avg_XXX
nvoAmpB_Avg_XXX
nvoAmpC_Avg_XXX
nvoPsWat3PAv_XXX
nvoPsVAR3PAv_XXX
nvoNgWat3PAv_XXX
nvoNgVAR3PAv_XXX
nvoVA_3PhAvg_XXX
nvoPsPF3PhAv_XXX
nvoNgPF3PhAv_XXX
nvoVAh_Tot_XXX
nvoMtr_Stat_XXX
nvoCurDatTm1_XXX
nvoCurDatTm2_XXX
nvoCurDatTm3_XXX
nvoPWt3PMADm_XXX
nvoPVr3PMADm_XXX
nvoNWt3PMADm_XXX
nvoNVr3PMADm_XXX
nvoCT_mult_XXX
nvoCT_den_XXX
nvoCT_num_XXX
nvoPT_num_XXX
nvoPT_den_XXX
nvoPT_hookup_XXX
nvoPT_mult_XXX
nvoSerNum1_XXX
nvoSerNum2_XXX
nvoSerNum3_XXX
nvoSerNum4_XXX
nvoSerNum5_XXX
nvoSerNum6_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
A-5
A: Protocol Data Points for EIG Meters
SerialNumberReg7
BACnet BACnet
N2
Object Object
Data
Type
ID
Type
AI
68
AI
SerialNumberReg8
AI
69
AI
PasswordforResetinuse
PasswordforConfigurationinuse
BI
BI
70
71
DI
DI
PointName
N2
EIPTag
Point
Name
Address
68
Dev2_XXX[1
0]
69
Dev2_XXX[1
1]
70
Byt_XXX[5]
71
Byt_XXX[6]
DF1
Address
LonName
LonSNVT
N13:10
nvoSerNum7_XXX
SNVT_count
N13:11
nvoSerNum8_XXX
SNVT_count
N14:5
N14:6
nvoPswdReset_XXX
nvoPswdCnfg_XXX
SNVT_count
SNVT_count
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E204701
A-6
A: Protocol Data Points for EIG Meters
A.3: Nexus® 1252/1262/1272 Meters
PointName
CurrentTimeReg1
CurrentTimeReg2
CurrentTimeReg3
CurrentTimeReg4
OnesecPhaseAͲNVoltage
OnesecPhaseBͲNVoltage
OnesecPhaseCͲNVoltage
OnesecPhaseACurrent
OnesecPhaseBCurrent
OnesecPhaseCCurrent
OnesecNeutralCurrentMeasured
OnesecNeutralCurrentCalculated
OnesecPhaseAͲBVoltage
OnesecPhaseBͲCVoltage
OnesecPhaseCͲAVoltage
OnesecThreePhaseVA
OnesecThreePhaseVAR
OnesecWatts
OnesecFrequency
OnesecThreePhasePF
PhaseAͲNVoltageTHD
PhaseBͲNVoltageTHD
PhaseCͲNVoltageTHD
PhaseACurrentTHD
PhaseBCurrentTHD
PhaseCCurrentTHD
BlockWindowAvgVA
BlockWindowAvgVAR
BlockWindowAvgWatt
MaxBlockWindowAvgPosVA
MaxBlockWindowAvgPosVAR
MaxBlockWindowAvgNegVAR
MaxBlockWindowAvgPosWatt
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
Doc# E204701
EIPTag
Name
Dev1_XXX[0]
Dev1_XXX[1]
Dev1_XXX[2]
Dev1_XXX[3]
S32_XXX[0]
S32_XXX[1]
S32_XXX[2]
S32_XXX[3]
S32_XXX[4]
S32_XXX[5]
S32_XXX[6]
S32_XXX[7]
S32_XXX[8]
S32_XXX[9]
S32_XXX[10]
S32_XXX[11]
S32_XXX[12]
S32_XXX[13]
S32_XXX[14]
Dev2_XXX[0]
Dev2_XXX[1]
Dev2_XXX[2]
Dev2_XXX[3]
Dev2_XXX[4]
Dev2_XXX[5]
Dev2_XXX[6]
S32_XXX[15]
S32_XXX[16]
S32_XXX[17]
S32_XXX[18]
S32_XXX[19]
S32_XXX[20]
S32_XXX[21]
DF1
Address
N12:0
N12:1
N12:2
N12:3
F10:0
F10:1
F10:2
F10:3
F10:4
F10:5
F10:6
F10:7
F10:8
F10:9
F10:10
F10:11
F10:12
F10:13
F10:14
N13:0
N13:1
N13:2
N13:3
N13:4
N13:5
N13:6
F10:15
F10:16
F10:17
F10:18
F10:19
F10:20
F10:21
LonName
nvoCurTime1_XXX
nvoCurTime2_XXX
nvoCurTime3_XXX
nvoCurTime4_XXX
nvoPhAN_Volt_XXX
nvoPhBN_Volt_XXX
nvoPhCN_Volt_XXX
nvoPhA_Curr_XXX
nvoPhB_Curr_XXX
nvoPhC_Curr_XXX
nvoNtCurMeas_XXX
nvoNtCurMalc_XXX
nvoPhAB_Volt_XXX
nvoPhBC_Volt_XXX
nvoPhCA_Volt_XXX
nvo3PhVA_XXX
nvo3PhVAR_XXX
nvoWatts_XXX
nvo1Freq_XXX
nvo3PhPF_XXX
nvoVoltANTHD_XXX
nvoVoltBNTHD_XXX
nvoVoltCNTHD_XXX
nvoCurrATHD_XXX
nvoCurrBTHD_XXX
nvoCurrCTHD_XXX
nvoBlWdAvVA_XXX
nvoBlWdAvVAR_XXX
nvoBlWdAvWat_XXX
nvoMBlWdAvVA_XXX
nvoMBWAvPVAR_XXX
nvoMBWAvNVAR_XXX
nvoMBWAvPWat_XXX
LonSNVT
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-7
A: Protocol Data Points for EIG Meters
PointName
MaxBlockWindowAvgNegWatt
TotalVAh(Quad1Ͳ4)ScaledPrimary
PosVARh(Quad1+2)ScaledPrimary
NegVARh(Quad3+4)ScaledPrimary
PosWh(Quad1+4)ScaledPrimary
NegWh(Quad2+3)ScaledPrimary
CTNumerator
CTDenominator
PTNumerator
PTDenominator
SystemHookup
PasswordState
CommDeviceStatus
DSPDeviceStatus
SerialNumber
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
Doc# E204701
EIPTag
Name
S32_XXX[22]
S32_XXX[23]
S32_XXX[24]
S32_XXX[25]
S32_XXX[26]
S32_XXX[27]
S32_XXX[27]
S32_XXX[28]
S32_XXX[29]
S32_XXX[30]
Dev3_XXX[0]
Dev3_XXX[1]
Dev3_XXX[2]
Dev3_XXX[3]
U32_XXX[0]
DF1
Address
F10:22
F10:23
F10:24
F10:25
F10:26
F10:27
F10:27
F10:28
F10:29
F10:30
N14:0
N14:1
N14:2
N14:3
F11:0
LonName
nvoMBWAvNWat_XXX
nvoTVAhQ14SP_XXX
nvoPVARQ12SP_XXX
nvoNVARQ34SP_XXX
nvoPWhQ14ScP_XXX
nvoNWhQ23ScP_XXX
nvoCT_num_XXX
nvoCT_den_XXX
nvoPT_num_XXX
nvoPT_den_XXX
nvoSysHookup_XXX
nvoPass_Stat_XXX
nvoComDevSt_XXX
nvoDSPDevSt_XXX
nvoSerNum_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count_inc_f
A-8
A: Protocol Data Points for EIG Meters
A.4: DMMS 425 Meter
PointName
InstVoltAN
InstVoltBN
InstVoltCN
InstVoltAB
InstVoltBC
InstVoltCA
InstAmpA
InstAmpB
InstAmpC
InstWatt
InstVar
InstVa
InstPf
InstFreq
MaxVoltAN
MaxVoltBN
MaxVoltCN
MaxVoltAB
MaxVoltBC
MaxVoltCA
MaxAmpA
MaxAmpB
MaxAmpC
MaxWatt
MaxVar
MaxVa
MaxPf
MaxFreq
WattHourBlock1
WattHourBlock2
WattHourBlock3
WattHourBlock4
WattHourBlock5
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
Doc# E204701
EIPTag
Name
S16_XXX[0]
S16_XXX[1]
S16_XXX[2]
S16_XXX[3]
S16_XXX[4]
S16_XXX[5]
S16_XXX[6]
S16_XXX[7]
S16_XXX[8]
S16_XXX[9]
S16_XXX[10]
S16_XXX[11]
S16_XXX[12]
S16_XXX[13]
S16_XXX[14]
S16_XXX[15]
S16_XXX[16]
S16_XXX[17]
S16_XXX[18]
S16_XXX[19]
S16_XXX[20]
S16_XXX[21]
S16_XXX[22]
S16_XXX[23]
S16_XXX[24]
S16_XXX[25]
S16_XXX[26]
S16_XXX[27]
Dev_XXX[0]
Dev_XXX[1]
Dev_XXX[2]
Dev_XXX[3]
Dev_XXX[4]
DF1
Address
N10:0
N10:1
N10:2
N10:3
N10:4
N10:5
N10:6
N10:7
N10:8
N10:9
N10:10
N10:11
N10:12
N10:13
N10:14
N10:15
N10:16
N10:17
N10:18
N10:19
N10:20
N10:21
N10:22
N10:23
N10:24
N10:25
N10:26
N10:27
N11:0
N11:1
N11:2
N11:3
N11:4
LonName
nvoVolt_AN_XXX
nvoVolt_BN_XXX
nvoVolt_CN_XXX
nvoVolt_AB_XXX
nvoVolt_BC_XXX
nvoVolt_CA_XXX
nvoAmp_A_XXX
nvoAmp_B_XXX
nvoAmp_C_XXX
nvoWatt_XXX
nvoVar_XXX
nvoVa_XXX
nvoPf_XXX
nvoFreq_XXX
nvoMaxVoltAN_XXX
nvoMaxVoltBN_XXX
nvoMaxVoltCN_XXX
nvoMaxVoltAB_XXX
nvoMaxVoltBC_XXX
nvoMaxVoltCA_XXX
nvoMaxAmp_A_XXX
nvoMaxAmp_B_XXX
nvoMaxAmp_C_XXX
nvoMaxWatt_XXX
nvoMaxVar_XXX
nvoMaxVa_XXX
nvoMaxPf_XXX
nvoMaxFreq_XXX
nvoWh_Blk1_XXX
nvoWh_Blk2_XXX
nvoWh_Blk3_XXX
nvoWh_Blk4_XXX
nvoWh_Blk5_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
A-9
A: Protocol Data Points for EIG Meters
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
PointName
WattHourBlock6
WattHourBlock7
WattHourBlock8
VarHourBlock1
VarHourBlock2
VarHourBlock3
VarHourBlock4
VarHourBlock5
VarHourBlock6
VarHourBlock7
VarHourBlock8
CTRatio
PTRatio
BACnet
Object
ID
34
35
36
37
38
39
40
41
42
43
44
45
46
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
34
35
36
37
38
39
40
41
42
43
44
45
46
EIPTag
Name
Dev_XXX[5]
Dev_XXX[6]
Dev_XXX[7]
Dev_XXX[8]
Dev_XXX[9]
Dev_XXX[10]
Dev_XXX[11]
Dev_XXX[12]
Dev_XXX[13]
Dev_XXX[14]
Dev_XXX[15]
Dev_XXX[16]
Dev_XXX[17]
DF1
Address
N11:5
N11:6
N11:7
N11:8
N11:9
N11:10
N11:11
N11:12
N11:13
N11:14
N11:15
N11:16
N11:17
LonName
nvoWh_Blk6_XXX
nvoWh_Blk7_XXX
nvoWh_Blk8_XXX
nvoVARh_Blk1_XXX
nvoVARh_Blk2_XXX
nvoVARh_Blk3_XXX
nvoVARh_Blk4_XXX
nvoVARh_Blk5_XXX
nvoVARh_Blk6_XXX
nvoVARh_Blk7_XXX
nvoVARh_Blk8_XXX
nvoCT_Ratio_XXX
nvoPT_Ratio_XXX
LonSNVT
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
A.5: Nexus® 1500 Meter
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E204701
A-10
A: Protocol Data Points for EIG Meters
A.5: Nexus® 1500 Meter
PointName
CurrentTimeReg1
CurrentTimeReg2
CurrentTimeReg3
CurrentTimeReg4
1secPhAͲNVoltage
1secPhBͲNVoltage
1secPhCͲNVoltage
1secVauxVoltage
1secPhACurrent
1secPhBCurrent
1secPhCCurrent
1secMeasuredNeutralCurrent
1secCalculatedNeutralCurrent
1secPhAͲBVoltage
1secPhBͲCVoltage
1secPhCͲAVoltage
1secVA
1secThreeVAR
1secWatts
1secFrequency
1secThreePhPowerFactor
PhAͲN/PhAͲBVoltageTHD
PhBͲN/PhBͲCVoltageTHD
PhCͲN/PhCͲAVoltageTHD
PhACurrentTHD
PhBCurrentTHD
PhCCurrentTHD
BlkWindowAvgVA
BlkWindowAvgVAR
BlkWindowAvgWatt
MaxBlkWindowAvgVA
MaxBlkWindowAvgPosVAR
MaxBlkWindowAvgNegVAR
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
Doc# E204701
EIPTag
Name
Dev1_XXX[0]
Dev1_XXX[1]
Dev1_XXX[2]
Dev1_XXX[3]
S32_XXX[0]
S32_XXX[1]
S32_XXX[2]
S32_XXX[3]
S32_XXX[4]
S32_XXX[5]
S32_XXX[6]
S32_XXX[7]
S32_XXX[8]
S32_XXX[9]
S32_XXX[10]
S32_XXX[11]
S32_XXX[12]
S32_XXX[13]
S32_XXX[14]
S32_XXX[15]
Dev2_XXX[0]
S16_XXX[0]
S16_XXX[1]
S16_XXX[2]
S16_XXX[3]
S16_XXX[4]
S16_XXX[5]
S32_XXX[16]
S32_XXX[17]
S32_XXX[18]
S32_XXX[19]
S32_XXX[20]
S32_XXX[21]
DF1
Address
N13:0
N13:1
N13:2
N13:3
F10:0
F10:1
F10:2
F10:3
F10:4
F10:5
F10:6
F10:7
F10:8
F10:9
F10:10
F10:11
F10:12
F10:13
F10:14
F10:15
N14:0
N11:0
N11:1
N11:2
N11:3
N11:4
N11:5
F10:16
F10:17
F10:18
F10:19
F10:20
F10:21
LonName
nvoCurTime1_XXX
nvoCurTime2_XXX
nvoCurTime3_XXX
nvoCurTime4_XXX
nvoAN_Volt_XXX
nvoBN_Volt_XXX
nvoCN_Volt_XXX
nvoVaux_Volt_XXX
nvoA_Crnt_XXX
nvoB_Crnt_XXX
nvoC_Crnt_XXX
nvoMeasNtCrn_XXX
nvoCalcNtCrn_XXX
nvoAB_Volt_XXX
nvoBC_Volt_XXX
nvoCA_Volt_XXX
nvoVA_XXX
nvo3_VAR_XXX
nvoWatts_XXX
nvoFreq_XXX
nvo3_PF_XXX
nvoANABVlTHD_XXX
nvoBNBCVlTHD_XXX
nvoCNCAVlTHD_XXX
nvoA_CurTHD_XXX
nvoB_CurTHD_XXX
nvoC_CurTHD_XXX
nvoBlWndAvVA_XXX
nvoBlWndAVAR_XXX
nvoBlWndAvWt_XXX
nvoMxBlWdAVA_XXX
nvoMBWdAPVAR_XXX
nvoMBWdANVAR_XXX
LonSNVT
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-11
A: Protocol Data Points for EIG Meters
PointName
MaxBlkWindowAvgPosWatt
MaxBlkWindowAvgNegWatt
TotalVAh(Quad1+2+3+4)ScaledPri
PosVARh(Quad1+2)ScaledPri
NegVARh(Quad3+4)ScaledPri
PosWh(Quad1+4)ScaledPri
NegWh(Quad2+3)ScaledPri
PhCurrentCTRatioNumerator
PhCurrentCTRatioDenominator
MeasuredNeutralCurrentCTRatioNum
MeasuredNeutralCurrentCTRatioDen
PhVoltagePTRatioNumerator
PhVoltagePTRatioDenominator
AuxVoltagePTRatioNumerator
AuxVoltagePTRationDenominator
SystemHookup
Level1/Level2PasswordState
SealingSwitchState
DeviceStatus
SerialNumberReg1
SerialNumberReg2
SerialNumberReg3
SerialNumberReg4
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
EIPTag
Name
S32_XXX[22]
S32_XXX[23]
Flt_XXX[0]
Flt_XXX[1]
Flt_XXX[2]
Flt_XXX[3]
Flt_XXX[4]
S32_XXX[29]
S32_XXX[30]
S32_XXX[31]
S32_XXX[32]
S32_XXX[33]
S32_XXX[34]
S32_XXX[35]
S32_XXX[36]
Dev3_XXX[0]
Dev3_XXX[2]
Dev3_XXX[3]
Dev3_XXX[4]
Dev3_XXX[5]
Dev3_XXX[6]
Dev3_XXX[7]
Dev3_XXX[8]
DF1
Address
F10:22
F10:23
F12:0
F12:1
F12:2
F12:3
F12:4
F10:29
F10:30
F10:31
F10:32
F10:33
F10:34
F10:35
F10:36
N15:0
N15:2
N15:3
N15:4
N15:5
N15:6
N15:7
N15:8
LonName
nvoMBWdAvPWT_XXX
nvoMBWdAvNWT_XXX
nvoTVAh1234P_XXX
nvoPVARhQ12P_XXX
nvoNVARhQ34P_XXX
nvoPWhQ14ScP_XXX
nvoNWhQd23SP_XXX
nvoCrtCTRtNm_XXX
nvoCrtCTRtDn_XXX
nvoMsNtCTRtN_XXX
nvoMsNtCTRtD_XXX
nvoVtPTRtNum_XXX
nvoVtPTRtDen_XXX
nvoAxVtPTRtN_XXX
nvoAxVtPTRtD_XXX
nvoSysHookup_XXX
nvoLv1_2PsSt_XXX
nvoSlSwState_XXX
nvoDevStat_XXX
nvoSerNum1_XXX
nvoSerNum2_XXX
nvoSerNum3_XXX
nvoSerNum4_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count
SNVT_count
SNVT_count
SNVT_count
SNVT_count
A.6: MP200-Y Metering System
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc# E204701
A-12
A: Protocol Data Points for EIG Meters
A.6: MP200-Y Metering System
PointName
VoltsAͲN
VoltsBͲN
VoltsCͲN
VoltsAͲB
VoltsBͲC
VoltsCͲA
Frequency
MTR01AmpsA
MTR01AmpsB
MTR01AmpsC
MTR01Watts3ͲPhtotal
MTR01VARs3ͲPhtotal
MTR01VAs3ͲPhtotal
MTR01PowerFactor3ͲPhtotal
MTR01NeutralCurrent
MTR02AmpsA
MTR02AmpsB
MTR02AmpsC
MTR02Watts3ͲPhtotal
MTR02VARs3ͲPhtotal
MTR02VAs3ͲPhtotal
MTR02PowerFactor3ͲPhtotal
MTR02NeutralCurrent
MTR03AmpsA
MTR03AmpsB
MTR03AmpsC
MTR03Watts3ͲPhtotal
MTR03VARs3ͲPhtotal
MTR03VAs3ͲPhtotal
MTR03PowerFactor3ͲPhtotal
MTR03NeutralCurrent
MTR04AmpsA
MTR04AmpsB
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Point
Address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
EIPTagName
Flt_XXX[000]
Flt_XXX[001]
Flt_XXX[002]
Flt_XXX[003]
Flt_XXX[004]
Flt_XXX[005]
Flt_XXX[006]
Flt_XXX[007]
Flt_XXX[008]
Flt_XXX[009]
Flt_XXX[010]
Flt_XXX[011]
Flt_XXX[012]
Flt_XXX[013]
Flt_XXX[014]
Flt_XXX[015]
Flt_XXX[016]
Flt_XXX[017]
Flt_XXX[018]
Flt_XXX[019]
Flt_XXX[020]
Flt_XXX[021]
Flt_XXX[022]
Flt_XXX[023]
Flt_XXX[024]
Flt_XXX[025]
Flt_XXX[026]
Flt_XXX[027]
Flt_XXX[028]
Flt_XXX[029]
Flt_XXX[030]
Flt_XXX[031]
Flt_XXX[032]
Doc# E204701
DF1
Address
F10:000
F10:001
F10:002
F10:003
F10:004
F10:005
F10:006
F10:007
F10:008
F10:009
F10:010
F10:011
F10:012
F10:013
F10:014
F10:015
F10:016
F10:017
F10:018
F10:019
F10:020
F10:021
F10:022
F10:023
F10:024
F10:025
F10:026
F10:027
F10:028
F10:029
F10:030
F10:031
F10:032
LonName
nvoVoltsAN_XXX
nvoVoltsBN_XXX
nvoVoltsCN_XXX
nvoVoltsAB_XXX
nvoVoltsBC_XXX
nvoVoltsCA_XXX
nvoFrequency_XXX
nvoM1AmpsA_XXX
nvoM1AmpsB_XXX
nvoM1AmpsC_XXX
nvoM1WattTot_XXX
nvoM1VARsTot_XXX
nvoM1VAsTot_XXX
nvoM1PFTot_XXX
nvoM1NeutCur_XXX
nvoM2AmpsA_XXX
nvoM2AmpsB_XXX
nvoM2AmpsC_XXX
nvoM2WattTot_XXX
nvoM2VARsTot_XXX
nvoM2VAsTot_XXX
nvoM2PFTot_XXX
nvoM2NeutCur_XXX
nvoM3AmpsA_XXX
nvoM3AmpsB_XXX
nvoM3AmpsC_XXX
nvoM3WattTot_XXX
nvoM3VARsTot_XXX
nvoM3VAsTot_XXX
nvoM3PFTot_XXX
nvoM3NeutCur_XXX
nvoM4AmpsA_XXX
nvoM4AmpsB_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-13
A: Protocol Data Points for EIG Meters
PointName
MTR04AmpsC
MTR04Watts3ͲPhtotal
MTR04VARs3ͲPhtotal
MTR04VAs3ͲPhtotal
MTR04PowerFactor3ͲPhtotal
MTR04NeutralCurrent
MTR05AmpsA
MTR05AmpsB
MTR05AmpsC
MTR05Watts3ͲPhtotal
MTR05VARs3ͲPhtotal
MTR05VAs3ͲPhtotal
MTR05PowerFactor3ͲPhtotal
MTR05NeutralCurrent
MTR06AmpsA
MTR06AmpsB
MTR06AmpsC
MTR06Watts3ͲPhtotal
MTR06VARs3ͲPhtotal
MTR06VAs3ͲPhtotal
MTR06PowerFactor3ͲPhtotal
MTR06NeutralCurrent
MTR07AmpsA
MTR07AmpsB
MTR07AmpsC
MTR07Watts3ͲPhtotal
MTR07VARs3ͲPhtotal
MTR07VAs3ͲPhtotal
MTR07PowerFactor3ͲPhtotal
MTR07NeutralCurrent
MTR08AmpsA
MTR08AmpsB
MTR08AmpsC
MTR08Watts3ͲPhtotal
MTR08VARs3ͲPhtotal
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
EIPTagName
Flt_XXX[033]
Flt_XXX[034]
Flt_XXX[035]
Flt_XXX[036]
Flt_XXX[037]
Flt_XXX[038]
Flt_XXX[039]
Flt_XXX[040]
Flt_XXX[041]
Flt_XXX[042]
Flt_XXX[043]
Flt_XXX[044]
Flt_XXX[045]
Flt_XXX[046]
Flt_XXX[047]
Flt_XXX[048]
Flt_XXX[049]
Flt_XXX[050]
Flt_XXX[051]
Flt_XXX[052]
Flt_XXX[053]
Flt_XXX[054]
Flt_XXX[055]
Flt_XXX[056]
Flt_XXX[057]
Flt_XXX[058]
Flt_XXX[059]
Flt_XXX[060]
Flt_XXX[061]
Flt_XXX[062]
Flt_XXX[063]
Flt_XXX[064]
Flt_XXX[065]
Flt_XXX[066]
Flt_XXX[067]
Doc# E204701
DF1
Address
F10:033
F10:034
F10:035
F10:036
F10:037
F10:038
F10:039
F10:040
F10:041
F10:042
F10:043
F10:044
F10:045
F10:046
F10:047
F10:048
F10:049
F10:050
F10:051
F10:052
F10:053
F10:054
F10:055
F10:056
F10:057
F10:058
F10:059
F10:060
F10:061
F10:062
F10:063
F10:064
F10:065
F10:066
F10:067
LonName
nvoM4AmpsC_XXX
nvoM4WattTot_XXX
nvoM4VARsTot_XXX
nvoM4VAsTot_XXX
nvoM4PFTot_XXX
nvoM4NeutCur_XXX
nvoM5AmpsA_XXX
nvoM5AmpsB_XXX
nvoM5AmpsC_XXX
nvoM5WattTot_XXX
nvoM5VARsTot_XXX
nvoM5VAsTot_XXX
nvoM5PFTot_XXX
nvoM5NeutCur_XXX
nvoM6AmpsA_XXX
nvoM6AmpsB_XXX
nvoM6AmpsC_XXX
nvoM6WattTot_XXX
nvoM6VARsTot_XXX
nvoM6VAsTot_XXX
nvoM6PFTot_XXX
nvoM6NeutCur_XXX
nvoM7AmpsA_XXX
nvoM7AmpsB_XXX
nvoM7AmpsC_XXX
nvoM7WattTot_XXX
nvoM7VARsTot_XXX
nvoM7VAsTot_XXX
nvoM7PFTot_XXX
nvoM7NeutCur_XXX
nvoM8AmpsA_XXX
nvoM8AmpsB_XXX
nvoM8AmpsC_XXX
nvoM8WattTot_XXX
nvoM8VARsTot_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-14
A: Protocol Data Points for EIG Meters
PointName
MTR08VAs3ͲPhtotal
MTR08PowerFactor3ͲPhtotal
MTR08NeutralCurrent
MTR01WͲhoursReceived
MTR01WͲhoursDelivered
MTR01WͲhoursNet
MTR01WͲhoursTotal
MTR01VARͲhoursPositive
MTR01VARͲhoursNegative
MTR01VARͲhoursNet
MTR01VARͲhoursTotal
MTR01VAͲhoursTotal
MTR02WͲhoursReceived
MTR02WͲhoursDelivered
MTR02WͲhoursNet
MTR02WͲhoursTotal
MTR02VARͲhoursPositive
MTR02VARͲhoursNegative
MTR02VARͲhoursNet
MTR02VARͲhoursTotal
MTR02VAͲhoursTotal
MTR03WͲhoursReceived
MTR03WͲhoursDelivered
MTR03WͲhoursNet
MTR03WͲhoursTotal
MTR03VARͲhoursPositive
MTR03VARͲhoursNegative
MTR03VARͲhoursNet
MTR03VARͲhoursTotal
MTR03VAͲhoursTotal
MTR04WͲhoursReceived
MTR04WͲhoursDelivered
MTR04WͲhoursNet
MTR04WͲhoursTotal
MTR04VARͲhoursPositive
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
EIPTagName
Flt_XXX[068]
Flt_XXX[069]
Flt_XXX[070]
S32_XXX[000]
S32_XXX[001]
S32_XXX[002]
S32_XXX[003]
S32_XXX[004]
S32_XXX[005]
S32_XXX[006]
S32_XXX[007]
S32_XXX[008]
S32_XXX[009]
S32_XXX[010]
S32_XXX[011]
S32_XXX[012]
S32_XXX[013]
S32_XXX[014]
S32_XXX[015]
S32_XXX[016]
S32_XXX[017]
S32_XXX[018]
S32_XXX[019]
S32_XXX[020]
S32_XXX[021]
S32_XXX[022]
S32_XXX[023]
S32_XXX[024]
S32_XXX[025]
S32_XXX[026]
S32_XXX[027]
S32_XXX[028]
S32_XXX[029]
S32_XXX[030]
S32_XXX[031]
Doc# E204701
DF1
Address
F10:068
F10:069
F10:070
F11:000
F11:001
F11:002
F11:003
F11:004
F11:005
F11:006
F11:007
F11:008
F11:009
F11:010
F11:011
F11:012
F11:013
F11:014
F11:015
F11:016
F11:017
F11:018
F11:019
F11:020
F11:021
F11:022
F11:023
F11:024
F11:025
F11:026
F11:027
F11:028
F11:029
F11:030
F11:031
LonName
nvoM8VAsTot_XXX
nvoM8PFTot_XXX
nvoM8NeutCur_XXX
nvoM1WHRec_XXX
nvoM1WHDel_XXX
nvoM1WHNet_XXX
nvoM1WHTot_XXX
nvoM1VARHPos_XXX
nvoM1VARHNeg_XXX
nvoM1VARHNet_XXX
nvoM1VARHTot_XXX
nvoM1VAHTot_XXX
nvoM2WHRec_XXX
nvoM2WHDel_XXX
nvoM2WHNet_XXX
nvoM2WHTot_XXX
nvoM2VARHPos_XXX
nvoM2VARHNeg_XXX
nvoM2VARHNet_XXX
nvoM2VARHTot_XXX
nvoM2VAHTot_XXX
nvoM3WHRec_XXX
nvoM3WHDel_XXX
nvoM3WHNet_XXX
nvoM3WHTot_XXX
nvoM3VARHPos_XXX
nvoM3VARHNeg_XXX
nvoM3VARHNet_XXX
nvoM3VARHTot_XXX
nvoM3VAHTot_XXX
nvoM4WHRec_XXX
nvoM4WHDel_XXX
nvoM4WHNet_XXX
nvoM4WHTot_XXX
nvoM4VARHPos_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-15
A: Protocol Data Points for EIG Meters
PointName
MTR04VARͲhoursNegative
A.7:
MP200-S Metering
MTR04VARͲhoursNet
MTR04VARͲhoursTotal
MTR04VAͲhoursTotal
MTR05WͲhoursReceived
MTR05WͲhoursDelivered
MTR05WͲhoursNet
MTR05WͲhoursTotal
MTR05VARͲhoursPositive
MTR05VARͲhoursNegative
MTR05VARͲhoursNet
MTR05VARͲhoursTotal
MTR05VAͲhoursTotal
MTR06WͲhoursReceived
MTR06WͲhoursDelivered
MTR06WͲhoursNet
MTR06WͲhoursTotal
MTR06VARͲhoursPositive
MTR06VARͲhoursNegative
MTR06VARͲhoursNet
MTR06VARͲhoursTotal
MTR06VAͲhoursTotal
MTR07WͲhoursReceived
MTR07WͲhoursDelivered
MTR07WͲhoursNet
MTR07WͲhoursTotal
MTR07VARͲhoursPositive
MTR07VARͲhoursNegative
MTR07VARͲhoursNet
MTR07VARͲhoursTotal
MTR07VAͲhoursTotal
MTR08WͲhoursReceived
MTR08WͲhoursDelivered
MTR08WͲhoursNet
MTR08WͲhoursTotal
BACnet
Object
Type
AI
System
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
EIPTagName
S32_XXX[032]
S32_XXX[033]
S32_XXX[034]
S32_XXX[035]
S32_XXX[036]
S32_XXX[037]
S32_XXX[038]
S32_XXX[039]
S32_XXX[040]
S32_XXX[041]
S32_XXX[042]
S32_XXX[043]
S32_XXX[044]
S32_XXX[045]
S32_XXX[046]
S32_XXX[047]
S32_XXX[048]
S32_XXX[049]
S32_XXX[050]
S32_XXX[051]
S32_XXX[052]
S32_XXX[053]
S32_XXX[054]
S32_XXX[055]
S32_XXX[056]
S32_XXX[057]
S32_XXX[058]
S32_XXX[059]
S32_XXX[060]
S32_XXX[061]
S32_XXX[062]
S32_XXX[063]
S32_XXX[064]
S32_XXX[065]
S32_XXX[066]
Doc# E204701
DF1
Address
F11:032
F11:033
F11:034
F11:035
F11:036
F11:037
F11:038
F11:039
F11:040
F11:041
F11:042
F11:043
F11:044
F11:045
F11:046
F11:047
F11:048
F11:049
F11:050
F11:051
F11:052
F11:053
F11:054
F11:055
F11:056
F11:057
F11:058
F11:059
F11:060
F11:061
F11:062
F11:063
F11:064
F11:065
F11:066
LonName
nvoM4VARHNeg_XXX
nvoM4VARHNet_XXX
nvoM4VARHTot_XXX
nvoM4VAHTot_XXX
nvoM5WHRec_XXX
nvoM5WHDel_XXX
nvoM5WHNet_XXX
nvoM5WHTot_XXX
nvoM5VARHPos_XXX
nvoM5VARHNeg_XXX
nvoM5VARHNet_XXX
nvoM5VARHTot_XXX
nvoM5VAHTot_XXX
nvoM6WHRec_XXX
nvoM6WHDel_XXX
nvoM6WHNet_XXX
nvoM6WHTot_XXX
nvoM6VARHPos_XXX
nvoM6VARHNeg_XXX
nvoM6VARHNet_XXX
nvoM6VARHTot_XXX
nvoM6VAHTot_XXX
nvoM7WHRec_XXX
nvoM7WHDel_XXX
nvoM7WHNet_XXX
nvoM7WHTot_XXX
nvoM7VARHPos_XXX
nvoM7VARHNeg_XXX
nvoM7VARHNet_XXX
nvoM7VARHTot_XXX
nvoM7VAHTot_XXX
nvoM8WHRec_XXX
nvoM8WHDel_XXX
nvoM8WHNet_XXX
nvoM8WHTot_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-16
A: Protocol Data Points for EIG Meters
PointName
MTR08VARͲhoursPositive
MTR08VARͲhoursNegative
MTR08VARͲhoursNet
MTR08VARͲhoursTotal
MTR08VAͲhoursTotal
MTR01PositiveWatts3ͲPhAvg
MTR01PositiveVARs3ͲPhAvg
MTR01NegativeWatts3ͲPhAvg
MTR01NegativeVARs3ͲPhAvg
MTR01VAs3ͲPhAvg
MTR02PositiveWatts3ͲPhAvg
MTR02PositiveVARs3ͲPhAvg
MTR02NegativeWatts3ͲPhAvg
MTR02NegativeVARs3ͲPhAvg
MTR02VAs3ͲPhAvg
MTR03PositiveWatts3ͲPhAvg
MTR03PositiveVARs3ͲPhAvg
MTR03NegativeWatts3ͲPhAvg
MTR03NegativeVARs3ͲPhAvg
MTR03VAs3ͲPhAvg
MTR04PositiveWatts3ͲPhAvg
MTR04PositiveVARs3ͲPhAvg
MTR04NegativeWatts3ͲPhAvg
MTR04NegativeVARs3ͲPhAvg
MTR04VAs3ͲPhAvg
MTR05PositiveWatts3ͲPhAvg
MTR05PositiveVARs3ͲPhAvg
MTR05NegativeWatts3ͲPhAvg
MTR05NegativeVARs3ͲPhAvg
MTR05VAs3ͲPhAvg
MTR06PositiveWatts3ͲPhAvg
MTR06PositiveVARs3ͲPhAvg
MTR06NegativeWatts3ͲPhAvg
MTR06NegativeVARs3ͲPhAvg
MTR06VAs3ͲPhAvg
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
EIPTagName
S32_XXX[067]
S32_XXX[068]
S32_XXX[069]
S32_XXX[070]
S32_XXX[071]
Flt_XXX[071]
Flt_XXX[072]
Flt_XXX[073]
Flt_XXX[074]
Flt_XXX[075]
Flt_XXX[076]
Flt_XXX[077]
Flt_XXX[078]
Flt_XXX[079]
Flt_XXX[080]
Flt_XXX[081]
Flt_XXX[082]
Flt_XXX[083]
Flt_XXX[084]
Flt_XXX[085]
Flt_XXX[086]
Flt_XXX[087]
Flt_XXX[088]
Flt_XXX[089]
Flt_XXX[090]
Flt_XXX[091]
Flt_XXX[092]
Flt_XXX[093]
Flt_XXX[094]
Flt_XXX[095]
Flt_XXX[096]
Flt_XXX[097]
Flt_XXX[098]
Flt_XXX[099]
Flt_XXX[100]
Doc# E204701
DF1
Address
F11:067
F11:068
F11:069
F11:070
F11:071
F10:071
F10:072
F10:073
F10:074
F10:075
F10:076
F10:077
F10:078
F10:079
F10:080
F10:081
F10:082
F10:083
F10:084
F10:085
F10:086
F10:087
F10:088
F10:089
F10:090
F10:091
F10:092
F10:093
F10:094
F10:095
F10:096
F10:097
F10:098
F10:099
F10:100
LonName
nvoM8VARHPos_XXX
nvoM8VARHNeg_XXX
nvoM8VARHNet_XXX
nvoM8VARHTot_XXX
nvoM8VAHTot_XXX
nvoM1PsWtAvg_XXX
nvoM1PsVARAv_XXX
nvoM1NgWtAvg_XXX
nvoM1NgVARAv_XXX
nvoM1VAsAvg_XXX
nvoM2PsWtAvg_XXX
nvoM2PsVARAv_XXX
nvoM2NgWtAvg_XXX
nvoM2NgVARAv_XXX
nvoM2VAsAvg_XXX
nvoM3PsWtAvg_XXX
nvoM3PsVARAv_XXX
nvoM3NgWtAvg_XXX
nvoM3NgVARAv_XXX
nvoM3VAsAvg_XXX
nvoM4PsWtAvg_XXX
nvoM4PsVARAv_XXX
nvoM4NgWtAvg_XXX
nvoM4NgVARAv_XXX
nvoM4VAsAvg_XXX
nvoM5PsWtAvg_XXX
nvoM5PsVARAv_XXX
nvoM5NgWtAvg_XXX
nvoM5NgVARAv_XXX
nvoM5VAsAvg_XXX
nvoM6PsWtAvg_XXX
nvoM6PsVARAv_XXX
nvoM6NgWtAvg_XXX
nvoM6NgVARAv_XXX
nvoM6VAsAvg_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-17
A: Protocol Data Points for EIG Meters
PointName
MTR07PositiveWatts3ͲPhAvg
MTR07PositiveVARs3ͲPhAvg
MTR07NegativeWatts3ͲPhAvg
MTR07NegativeVARs3ͲPhAvg
MTR07VAs3ͲPhAvg
MTR08PositiveWatts3ͲPhAvg
MTR08PositiveVARs3ͲPhAvg
MTR08NegativeWatts3ͲPhAvg
MTR08NegativeVARs3ͲPhAvg
MTR08VAs3ͲPhAvg
CPUStatus
CurrentTimeReg1
CurrentTimeReg2
CurrentTimeReg3
MTR01PositiveWatts3ͲPhMaxAvgDem
MTR01PositiveVARs3ͲPhMaxAvgDem
MTR01NegativeWatts3ͲPhMaxAvgDem
MTR01NegativeVARs3ͲPhMaxAvgDem
MTR02PositiveWatts3ͲPhMaxAvgDem
MTR02PositiveVARs3ͲPhMaxAvgDem
MTR02NegativeWatts3ͲPhMaxAvgDem
MTR02NegativeVARs3ͲPhMaxAvgDem
MTR03PositiveWatts3ͲPhMaxAvgDem
MTR03PositiveVARs3ͲPhMaxAvgDem
MTR03NegativeWatts3ͲPhMaxAvgDem
MTR03NegativeVARs3ͲPhMaxAvgDem
MTR04PositiveWatts3ͲPhMaxAvgDem
MTR04PositiveVARs3ͲPhMaxAvgDem
MTR04NegativeWatts3ͲPhMaxAvgDem
MTR04NegativeVARs3ͲPhMaxAvgDem
MTR05PositiveWatts3ͲPhMaxAvgDem
MTR05PositiveVARs3ͲPhMaxAvgDem
MTR05NegativeWatts3ͲPhMaxAvgDem
MTR05NegativeVARs3ͲPhMaxAvgDem
MTR06PositiveWatts3ͲPhMaxAvgDem
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
EIPTagName
Flt_XXX[101]
Flt_XXX[102]
Flt_XXX[103]
Flt_XXX[104]
Flt_XXX[105]
Flt_XXX[106]
Flt_XXX[107]
Flt_XXX[108]
Flt_XXX[109]
Flt_XXX[110]
Dev1_XXX[000]
Dev1_XXX[001]
Dev1_XXX[002]
Dev1_XXX[003]
Flt_XXX[111]
Flt_XXX[112]
Flt_XXX[113]
Flt_XXX[114]
Flt_XXX[115]
Flt_XXX[116]
Flt_XXX[117]
Flt_XXX[118]
Flt_XXX[119]
Flt_XXX[120]
Flt_XXX[121]
Flt_XXX[122]
Flt_XXX[123]
Flt_XXX[124]
Flt_XXX[125]
Flt_XXX[126]
Flt_XXX[127]
Flt_XXX[128]
Flt_XXX[129]
Flt_XXX[130]
Flt_XXX[131]
Doc# E204701
DF1
Address
F10:101
F10:102
F10:103
F10:104
F10:105
F10:106
F10:107
F10:108
F10:109
F10:110
N12:000
N12:001
N12:002
N12:003
F10:111
F10:112
F10:113
F10:114
F10:115
F10:116
F10:117
F10:118
F10:119
F10:120
F10:121
F10:122
F10:123
F10:124
F10:125
F10:126
F10:127
F10:128
F10:129
F10:130
F10:131
LonName
nvoM7PsWtAvg_XXX
nvoM7PsVARAv_XXX
nvoM7NgWtAvg_XXX
nvoM7NgVARAv_XXX
nvoM7VAsAvg_XXX
nvoM8PsWtAvg_XXX
nvoM8PsVARAv_XXX
nvoM8NgWtAvg_XXX
nvoM8NgVARAv_XXX
nvoM8VAsAvg_XXX
nvoCPUStatus_XXX
nvoCurTime1_XXX
nvoCurTime2_XXX
nvoCurTime3_XXX
nvo1PWtMxAvD_XXX
nvo1PVARMxAv_XXX
nvo1NWtMxAvD_XXX
nvo1NVARMxAv_XXX
nvo2PWtMxAvD_XXX
nvo2PVARMxAv_XXX
nvo2NWtMxAvD_XXX
nvo2NVARMxAv_XXX
nvo3PWtMxAvD_XXX
nvo3PVARMxAv_XXX
nvo3NWtMxAvD_XXX
nvo3NVARMxAv_XXX
nvo4PWtMxAvD_XXX
nvo4PVARMxAv_XXX
nvo4NWtMxAvD_XXX
nvo4NVARMxAv_XXX
nvo5PWtMxAvD_XXX
nvo5PVARMxAv_XXX
nvo5NWtMxAvD_XXX
nvo5NVARMxAv_XXX
nvo6PWtMxAvD_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-18
A: Protocol Data Points for EIG Meters
BACnet
Object
Type
MTR06PositiveVARs3ͲPhMaxAvgDem
AI
MTR06NegativeWatts3ͲPhMaxAvgDem AI
MTR06NegativeVARs3ͲPhMaxAvgDem AI
MTR07PositiveWatts3ͲPhMaxAvgDem AI
MTR07PositiveVARs3ͲPhMaxAvgDem
AI
MTR07NegativeWatts3ͲPhMaxAvgDem AI
MTR07NegativeVARs3ͲPhMaxAvgDem AI
MTR08PositiveWatts3ͲPhMaxAvgDem AI
MTR08PositiveVARs3ͲPhMaxAvgDem
AI
MTR08NegativeWatts3ͲPhMaxAvgDem AI
MTR08NegativeVARs3ͲPhMaxAvgDem AI
SerialNumberReg1
AI
SerialNumberReg2
AI
SerialNumberReg3
AI
SerialNumberReg4
AI
SerialNumberReg5
AI
SerialNumberReg6
AI
SerialNumberReg7
AI
SerialNumberReg8
AI
CTdenominator
AI
MTR01CTNumerator
AI
MTR02CTNumerator
AI
MTR03CTNumerator
AI
MTR04CTNumerator
AI
MTR05CTNumerator
AI
MTR06CTNumerator
AI
MTR07CTNumerator
AI
MTR08CTNumerator
AI
PTNumerator
AI
PTdenominator
AI
SystemHookup
AI
PasswordforResetinuse
BI
PasswordforConfigurationinuse
BI
PointName
BACnet
Object
ID
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
DI
DI
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Point
Address
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
EIPTagName
Flt_XXX[132]
Flt_XXX[133]
Flt_XXX[134]
Flt_XXX[135]
Flt_XXX[136]
Flt_XXX[137]
Flt_XXX[138]
Flt_XXX[139]
Flt_XXX[140]
Flt_XXX[141]
Flt_XXX[142]
Dev2_XXX[000]
Dev2_XXX[001]
Dev2_XXX[002]
Dev2_XXX[003]
Dev2_XXX[004]
Dev2_XXX[005]
Dev2_XXX[006]
Dev2_XXX[007]
Dev2_XXX[008]
Dev2_XXX[009]
Dev2_XXX[010]
Dev2_XXX[011]
Dev2_XXX[012]
Dev2_XXX[013]
Dev2_XXX[014]
Dev2_XXX[015]
Dev2_XXX[016]
Dev2_XXX[017]
Dev2_XXX[018]
Dev2_XXX[019]
Byt_XXX[0]
Byt_XXX[1]
Doc# E204701
DF1
Address
F10:132
F10:133
F10:134
F10:135
F10:136
F10:137
F10:138
F10:139
F10:140
F10:141
F10:142
N13:000
N13:001
N13:002
N13:003
N13:004
N13:005
N13:006
N13:007
N13:008
N13:009
N13:010
N13:011
N13:012
N13:013
N13:014
N13:015
N13:016
N13:017
N13:018
N13:019
N14:0
N14:1
LonName
nvo6PVARMxAv_XXX
nvo6NWtMxAvD_XXX
nvo6NVARMxAv_XXX
nvo7PWtMxAvD_XXX
nvo7PVARMxAv_XXX
nvo7NWtMxAvD_XXX
nvo7NVARMxAv_XXX
nvo8PWtMxAvD_XXX
nvo8PVARMxAv_XXX
nvo8NWtMxAvD_XXX
nvo8NVARMxAv_XXX
nvoSerNum1_XXX
nvoSerNum2_XXX
nvoSerNum3_XXX
nvoSerNum4_XXX
nvoSerNum5_XXX
nvoSerNum6_XXX
nvoSerNum7_XXX
nvoSerNum8_XXX
nvoCT_den_XXX
nvoM1CT_num_XXX
nvoM2CT_num_XXX
nvoM3CT_num_XXX
nvoM4CT_num_XXX
nvoM5CT_num_XXX
nvoM6CT_num_XXX
nvoM7CT_num_XXX
nvoM8CT_num_XXX
nvoPT_num_XXX
nvoPT_den_XXX
nvoSysHookup_XXX
nvoPswdReset_XXX
nvoPswdCnfg_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
A-19
A: Protocol Data Points for EIG Meters
A.7: MP200-S Metering System
PointName
Volts
Frequency
AmpsMeter01
AmpsMeter02
AmpsMeter03
WattsMeter01
WattsMeter02
WattsMeter03
VARsMeter01
VARsMeter02
VARsMeter03
VAsMeter01
VAsMeter02
VAsMeter03
PowerFactorMeter01
PowerFactorMeter02
PowerFactorMeter03
AmpsMeter04
AmpsMeter05
AmpsMeter06
WattsMeter04
WattsMeter05
WattsMeter06
VARsMeter04
VARsMeter05
VARsMeter06
VAsMeter04
VAsMeter05
VAsMeter06
PowerFactorMeter04
PowerFactorMeter05
PowerFactorMeter06
AmpsMeter07
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
EIPTagName
Flt_XXX[000]
Flt_XXX[001]
Flt_XXX[002]
Flt_XXX[003]
Flt_XXX[004]
Flt_XXX[005]
Flt_XXX[006]
Flt_XXX[007]
Flt_XXX[008]
Flt_XXX[009]
Flt_XXX[010]
Flt_XXX[011]
Flt_XXX[012]
Flt_XXX[013]
Flt_XXX[014]
Flt_XXX[015]
Flt_XXX[016]
Flt_XXX[017]
Flt_XXX[018]
Flt_XXX[019]
Flt_XXX[020]
Flt_XXX[021]
Flt_XXX[022]
Flt_XXX[023]
Flt_XXX[024]
Flt_XXX[025]
Flt_XXX[026]
Flt_XXX[027]
Flt_XXX[028]
Flt_XXX[029]
Flt_XXX[030]
Flt_XXX[031]
Flt_XXX[032]
Doc# E204701
DF1
Address
F10:000
F10:001
F10:002
F10:003
F10:004
F10:005
F10:006
F10:007
F10:008
F10:009
F10:010
F10:011
F10:012
F10:013
F10:014
F10:015
F10:016
F10:017
F10:018
F10:019
F10:020
F10:021
F10:022
F10:023
F10:024
F10:025
F10:026
F10:027
F10:028
F10:029
F10:030
F10:031
F10:032
LonName
nvoVolts_XXX
nvoFrequency_XXX
nvoAmpsM1_XXX
nvoAmpsM2_XXX
nvoAmpsM3_XXX
nvoWattsM1_XXX
nvoWattsM2_XXX
nvoWattsM3_XXX
nvoVARsM1_XXX
nvoVARsM2_XXX
nvoVARsM3_XXX
nvoVAsM1_XXX
nvoVAsM2_XXX
nvoVAsM3_XXX
nvoPFM1_XXX
nvoPFM2_XXX
nvoPFM3_XXX
nvoAmpsM4_XXX
nvoAmpsM5_XXX
nvoAmpsM6_XXX
nvoWattsM4_XXX
nvoWattsM5_XXX
nvoWattsM6_XXX
nvoVARsM4_XXX
nvoVARsM5_XXX
nvoVARsM6_XXX
nvoVAsM4_XXX
nvoVAsM5_XXX
nvoVAsM6_XXX
nvoPFM4_XXX
nvoPFM5_XXX
nvoPFM6_XXX
nvoAmpsM7_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-20
A: Protocol Data Points for EIG Meters
PointName
AmpsMeter08
AmpsMeter09
WattsMeter07
WattsMeter08
WattsMeter09
VARsMeter07
VARsMeter08
VARsMeter09
VAsMeter07
VAsMeter08
VAsMeter09
PowerFactorMeter07
PowerFactorMeter08
PowerFactorMeter09
AmpsMeter10
AmpsMeter11
AmpsMeter12
WattsMeter10
WattsMeter11
WattsMeter12
VARsMeter10
VARsMeter11
VARsMeter12
VAsMeter10
VAsMeter11
VAsMeter12
PowerFactorMeter10
PowerFactorMeter11
PowerFactorMeter12
AmpsMeter13
AmpsMeter14
AmpsMeter15
WattsMeter13
WattsMeter14
WattsMeter15
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
EIPTagName
Flt_XXX[033]
Flt_XXX[034]
Flt_XXX[035]
Flt_XXX[036]
Flt_XXX[037]
Flt_XXX[038]
Flt_XXX[039]
Flt_XXX[040]
Flt_XXX[041]
Flt_XXX[042]
Flt_XXX[043]
Flt_XXX[044]
Flt_XXX[045]
Flt_XXX[046]
Flt_XXX[047]
Flt_XXX[048]
Flt_XXX[049]
Flt_XXX[050]
Flt_XXX[051]
Flt_XXX[052]
Flt_XXX[053]
Flt_XXX[054]
Flt_XXX[055]
Flt_XXX[056]
Flt_XXX[057]
Flt_XXX[058]
Flt_XXX[059]
Flt_XXX[060]
Flt_XXX[061]
Flt_XXX[062]
Flt_XXX[063]
Flt_XXX[064]
Flt_XXX[065]
Flt_XXX[066]
Flt_XXX[067]
Doc# E204701
DF1
Address
F10:033
F10:034
F10:035
F10:036
F10:037
F10:038
F10:039
F10:040
F10:041
F10:042
F10:043
F10:044
F10:045
F10:046
F10:047
F10:048
F10:049
F10:050
F10:051
F10:052
F10:053
F10:054
F10:055
F10:056
F10:057
F10:058
F10:059
F10:060
F10:061
F10:062
F10:063
F10:064
F10:065
F10:066
F10:067
LonName
nvoAmpsM8_XXX
nvoAmpsM9_XXX
nvoWattsM7_XXX
nvoWattsM8_XXX
nvoWattsM9_XXX
nvoVARsM7_XXX
nvoVARsM8_XXX
nvoVARsM9_XXX
nvoVAsM7_XXX
nvoVAsM8_XXX
nvoVAsM9_XXX
nvoPFM7_XXX
nvoPFM8_XXX
nvoPFM9_XXX
nvoAmpsM10_XXX
nvoAmpsM11_XXX
nvoAmpsM12_XXX
nvoWattsM10_XXX
nvoWattsM11_XXX
nvoWattsM12_XXX
nvoVARsM10_XXX
nvoVARsM11_XXX
nvoVARsM12_XXX
nvoVAsM10_XXX
nvoVAsM11_XXX
nvoVAsM12_XXX
nvoPFM10_XXX
nvoPFM11_XXX
nvoPFM12_XXX
nvoAmpsM13_XXX
nvoAmpsM14_XXX
nvoAmpsM15_XXX
nvoWattsM13_XXX
nvoWattsM14_XXX
nvoWattsM15_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-21
A: Protocol Data Points for EIG Meters
PointName
VARsMeter13
VARsMeter14
VARsMeter15
VAsMeter13
VAsMeter14
VAsMeter15
PowerFactorMeter13
PowerFactorMeter14
PowerFactorMeter15
AmpsMeter16
AmpsMeter17
AmpsMeter18
WattsMeter16
WattsMeter17
WattsMeter18
VARsMeter16
VARsMeter17
VARsMeter18
VAsMeter16
VAsMeter17
VAsMeter18
PowerFactorMeter16
PowerFactorMeter17
PowerFactorMeter18
AmpsMeter19
AmpsMeter20
AmpsMeter21
WattsMeter19
WattsMeter20
WattsMeter21
VARsMeter19
VARsMeter20
VARsMeter21
VAsMeter19
VAsMeter20
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
EIPTagName
Flt_XXX[068]
Flt_XXX[069]
Flt_XXX[070]
Flt_XXX[071]
Flt_XXX[072]
Flt_XXX[073]
Flt_XXX[074]
Flt_XXX[075]
Flt_XXX[076]
Flt_XXX[077]
Flt_XXX[078]
Flt_XXX[079]
Flt_XXX[080]
Flt_XXX[081]
Flt_XXX[082]
Flt_XXX[083]
Flt_XXX[084]
Flt_XXX[085]
Flt_XXX[086]
Flt_XXX[087]
Flt_XXX[088]
Flt_XXX[089]
Flt_XXX[090]
Flt_XXX[091]
Flt_XXX[092]
Flt_XXX[093]
Flt_XXX[094]
Flt_XXX[095]
Flt_XXX[096]
Flt_XXX[097]
Flt_XXX[098]
Flt_XXX[099]
Flt_XXX[100]
Flt_XXX[101]
Flt_XXX[102]
Doc# E204701
DF1
Address
F10:068
F10:069
F10:070
F10:071
F10:072
F10:073
F10:074
F10:075
F10:076
F10:077
F10:078
F10:079
F10:080
F10:081
F10:082
F10:083
F10:084
F10:085
F10:086
F10:087
F10:088
F10:089
F10:090
F10:091
F10:092
F10:093
F10:094
F10:095
F10:096
F10:097
F10:098
F10:099
F10:100
F10:101
F10:102
LonName
nvoVARsM13_XXX
nvoVARsM14_XXX
nvoVARsM15_XXX
nvoVAsM13_XXX
nvoVAsM14_XXX
nvoVAsM15_XXX
nvoPFM13_XXX
nvoPFM14_XXX
nvoPFM15_XXX
nvoAmpsM16_XXX
nvoAmpsM17_XXX
nvoAmpsM18_XXX
nvoWattsM16_XXX
nvoWattsM17_XXX
nvoWattsM18_XXX
nvoVARsM16_XXX
nvoVARsM17_XXX
nvoVARsM18_XXX
nvoVAsM16_XXX
nvoVAsM17_XXX
nvoVAsM18_XXX
nvoPFM16_XXX
nvoPFM17_XXX
nvoPFM18_XXX
nvoAmpsM19_XXX
nvoAmpsM20_XXX
nvoAmpsM21_XXX
nvoWattsM19_XXX
nvoWattsM20_XXX
nvoWattsM21_XXX
nvoVARsM19_XXX
nvoVARsM20_XXX
nvoVARsM21_XXX
nvoVAsM19_XXX
nvoVAsM20_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-22
A: Protocol Data Points for EIG Meters
PointName
VAsMeter21
PowerFactorMeter19
PowerFactorMeter20
PowerFactorMeter21
AmpsMeter22
AmpsMeter23
AmpsMeter24
WattsMeter22
WattsMeter23
WattsMeter24
VARsMeter22
VARsMeter23
VARsMeter24
VAsMeter22
VAsMeter23
VAsMeter24
PowerFactorMeter22
PowerFactorMeter23
PowerFactorMeter24
WͲhoursReceivedMeter01
WͲhoursReceivedMeter02
WͲhoursReceivedMeter03
WͲhoursDeliveredMeter01
WͲhoursDeliveredMeter02
WͲhoursDeliveredMeter03
WͲhoursNetMeter01
WͲhoursNetMeter02
WͲhoursNetMeter03
WͲhoursTotalMeter01
WͲhoursTotalMeter02
WͲhoursTotalMeter03
VARͲhoursPositiveMeter01
VARͲhoursPositiveMeter02
VARͲhoursPositiveMeter03
VARͲhoursNegativeMeter01
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
EIPTagName
Flt_XXX[103]
Flt_XXX[104]
Flt_XXX[105]
Flt_XXX[106]
Flt_XXX[107]
Flt_XXX[108]
Flt_XXX[109]
Flt_XXX[110]
Flt_XXX[111]
Flt_XXX[112]
Flt_XXX[113]
Flt_XXX[114]
Flt_XXX[115]
Flt_XXX[116]
Flt_XXX[117]
Flt_XXX[118]
Flt_XXX[119]
Flt_XXX[120]
Flt_XXX[121]
S32_XXX[000]
S32_XXX[001]
S32_XXX[002]
S32_XXX[003]
S32_XXX[004]
S32_XXX[005]
S32_XXX[006]
S32_XXX[007]
S32_XXX[008]
S32_XXX[009]
S32_XXX[010]
S32_XXX[011]
S32_XXX[012]
S32_XXX[013]
S32_XXX[014]
S32_XXX[015]
Doc# E204701
DF1
Address
F10:103
F10:104
F10:105
F10:106
F10:107
F10:108
F10:109
F10:110
F10:111
F10:112
F10:113
F10:114
F10:115
F10:116
F10:117
F10:118
F10:119
F10:120
F10:121
F12:000
F12:001
F12:002
F12:003
F12:004
F12:005
F12:006
F12:007
F12:008
F12:009
F12:010
F12:011
F12:012
F12:013
F12:014
F12:015
LonName
nvoVAsM21_XXX
nvoPFM19_XXX
nvoPFM20_XXX
nvoPFM21_XXX
nvoAmpsM22_XXX
nvoAmpsM23_XXX
nvoAmpsM24_XXX
nvoWattsM22_XXX
nvoWattsM23_XXX
nvoWattsM24_XXX
nvoVARsM22_XXX
nvoVARsM23_XXX
nvoVARsM24_XXX
nvoVAsM22_XXX
nvoVAsM23_XXX
nvoVAsM24_XXX
nvoPFM22_XXX
nvoPFM23_XXX
nvoPFM24_XXX
nvoWHRecM1_XXX
nvoWHRecM2_XXX
nvoWHRecM3_XXX
nvoWHDelM1_XXX
nvoWHDelM2_XXX
nvoWHDelM3_XXX
nvoWHNetM1_XXX
nvoWHNetM2_XXX
nvoWHNetM3_XXX
nvoWHTotM1_XXX
nvoWHTotM2_XXX
nvoWHTotM3_XXX
nvoVARhPosM1_XXX
nvoVARhPosM2_XXX
nvoVARhPosM3_XXX
nvoVARhNegM1_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-23
A: Protocol Data Points for EIG Meters
PointName
VARͲhoursNegativeMeter02
VARͲhoursNegativeMeter03
VARͲhoursNetMeter01
VARͲhoursNetMeter02
VARͲhoursNetMeter03
VARͲhoursTotalMeter01
VARͲhoursTotalMeter02
VARͲhoursTotalMeter03
VAͲhoursTotalMeter01
VAͲhoursTotalMeter02
VAͲhoursTotalMeter03
WͲhoursReceivedMeter04
WͲhoursReceivedMeter05
WͲhoursReceivedMeter06
WͲhoursDeliveredMeter04
WͲhoursDeliveredMeter05
WͲhoursDeliveredMeter06
WͲhoursNetMeter04
WͲhoursNetMeter05
WͲhoursNetMeter06
WͲhoursTotalMeter04
WͲhoursTotalMeter05
WͲhoursTotalMeter06
VARͲhoursPositiveMeter04
VARͲhoursPositiveMeter05
VARͲhoursPositiveMeter06
VARͲhoursNegativeMeter04
VARͲhoursNegativeMeter05
VARͲhoursNegativeMeter06
VARͲhoursNetMeter04
VARͲhoursNetMeter05
VARͲhoursNetMeter06
VARͲhoursTotalMeter04
VARͲhoursTotalMeter05
VARͲhoursTotalMeter06
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
EIPTagName
S32_XXX[016]
S32_XXX[017]
S32_XXX[018]
S32_XXX[019]
S32_XXX[020]
S32_XXX[021]
S32_XXX[022]
S32_XXX[023]
S32_XXX[024]
S32_XXX[025]
S32_XXX[026]
S32_XXX[027]
S32_XXX[028]
S32_XXX[029]
S32_XXX[030]
S32_XXX[031]
S32_XXX[032]
S32_XXX[033]
S32_XXX[034]
S32_XXX[035]
S32_XXX[036]
S32_XXX[037]
S32_XXX[038]
S32_XXX[039]
S32_XXX[040]
S32_XXX[041]
S32_XXX[042]
S32_XXX[043]
S32_XXX[044]
S32_XXX[045]
S32_XXX[046]
S32_XXX[047]
S32_XXX[048]
S32_XXX[049]
S32_XXX[050]
Doc# E204701
DF1
Address
F12:016
F12:017
F12:018
F12:019
F12:020
F12:021
F12:022
F12:023
F12:024
F12:025
F12:026
F12:027
F12:028
F12:029
F12:030
F12:031
F12:032
F12:033
F12:034
F12:035
F12:036
F12:037
F12:038
F12:039
F12:040
F12:041
F12:042
F12:043
F12:044
F12:045
F12:046
F12:047
F12:048
F12:049
F12:050
LonName
nvoVARhNegM2_XXX
nvoVARhNegM3_XXX
nvoVARhNetM1_XXX
nvoVARhNetM2_XXX
nvoVARhNetM3_XXX
nvoVARhTotM1_XXX
nvoVARhTotM2_XXX
nvoVARhTotM3_XXX
nvoVAhTotM1_XXX
nvoVAhTotM2_XXX
nvoVAhTotM3_XXX
nvoWHRecM4_XXX
nvoWHRecM5_XXX
nvoWHRecM6_XXX
nvoWHDelM4_XXX
nvoWHDelM5_XXX
nvoWHDelM6_XXX
nvoWHNetM4_XXX
nvoWHNetM5_XXX
nvoWHNetM6_XXX
nvoWHTotM4_XXX
nvoWHTotM5_XXX
nvoWHTotM6_XXX
nvoVARhPosM4_XXX
nvoVARhPosM5_XXX
nvoVARhPosM6_XXX
nvoVARhNegM4_XXX
nvoVARhNegM5_XXX
nvoVARhNegM6_XXX
nvoVARhNetM4_XXX
nvoVARhNetM5_XXX
nvoVARhNetM6_XXX
nvoVARhTotM4_XXX
nvoVARhTotM5_XXX
nvoVARhTotM6_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-24
A: Protocol Data Points for EIG Meters
PointName
VAͲhoursTotalMeter04
VAͲhoursTotalMeter05
VAͲhoursTotalMeter06
WͲhoursReceivedMeter07
WͲhoursReceivedMeter08
WͲhoursReceivedMeter09
WͲhoursDeliveredMeter07
WͲhoursDeliveredMeter08
WͲhoursDeliveredMeter09
WͲhoursNetMeter07
WͲhoursNetMeter08
WͲhoursNetMeter09
WͲhoursTotalMeter07
WͲhoursTotalMeter08
WͲhoursTotalMeter09
VARͲhoursPositiveMeter07
VARͲhoursPositiveMeter08
VARͲhoursPositiveMeter09
VARͲhoursNegativeMeter07
VARͲhoursNegativeMeter08
VARͲhoursNegativeMeter09
VARͲhoursNetMeter07
VARͲhoursNetMeter08
VARͲhoursNetMeter09
VARͲhoursTotalMeter07
VARͲhoursTotalMeter08
VARͲhoursTotalMeter09
VAͲhoursTotalMeter07
VAͲhoursTotalMeter08
VAͲhoursTotalMeter09
WͲhoursReceivedMeter10
WͲhoursReceivedMeter11
WͲhoursReceivedMeter12
WͲhoursDeliveredMeter10
WͲhoursDeliveredMeter11
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
EIPTagName
S32_XXX[051]
S32_XXX[052]
S32_XXX[053]
S32_XXX[054]
S32_XXX[055]
S32_XXX[056]
S32_XXX[057]
S32_XXX[058]
S32_XXX[059]
S32_XXX[060]
S32_XXX[061]
S32_XXX[062]
S32_XXX[063]
S32_XXX[064]
S32_XXX[065]
S32_XXX[066]
S32_XXX[067]
S32_XXX[068]
S32_XXX[069]
S32_XXX[070]
S32_XXX[071]
S32_XXX[072]
S32_XXX[073]
S32_XXX[074]
S32_XXX[075]
S32_XXX[076]
S32_XXX[077]
S32_XXX[078]
S32_XXX[079]
S32_XXX[080]
S32_XXX[081]
S32_XXX[082]
S32_XXX[083]
S32_XXX[084]
S32_XXX[085]
Doc# E204701
DF1
Address
F12:051
F12:052
F12:053
F12:054
F12:055
F12:056
F12:057
F12:058
F12:059
F12:060
F12:061
F12:062
F12:063
F12:064
F12:065
F12:066
F12:067
F12:068
F12:069
F12:070
F12:071
F12:072
F12:073
F12:074
F12:075
F12:076
F12:077
F12:078
F12:079
F12:080
F12:081
F12:082
F12:083
F12:084
F12:085
LonName
nvoVAhTotM4_XXX
nvoVAhTotM5_XXX
nvoVAhTotM6_XXX
nvoWHRecM7_XXX
nvoWHRecM8_XXX
nvoWHRecM9_XXX
nvoWHDelM7_XXX
nvoWHDelM8_XXX
nvoWHDelM9_XXX
nvoWHNetM7_XXX
nvoWHNetM8_XXX
nvoWHNetM9_XXX
nvoWHTotM7_XXX
nvoWHTotM8_XXX
nvoWHTotM9_XXX
nvoVARhPosM7_XXX
nvoVARhPosM8_XXX
nvoVARhPosM9_XXX
nvoVARhNegM7_XXX
nvoVARhNegM8_XXX
nvoVARhNegM9_XXX
nvoVARhNetM7_XXX
nvoVARhNetM8_XXX
nvoVARhNetM9_XXX
nvoVARhTotM7_XXX
nvoVARhTotM8_XXX
nvoVARhTotM9_XXX
nvoVAhTotM7_XXX
nvoVAhTotM8_XXX
nvoVAhTotM9_XXX
nvoWHRecM10_XXX
nvoWHRecM11_XXX
nvoWHRecM12_XXX
nvoWHDelM10_XXX
nvoWHDelM11_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-25
A: Protocol Data Points for EIG Meters
PointName
WͲhoursDeliveredMeter12
WͲhoursNetMeter10
WͲhoursNetMeter11
WͲhoursNetMeter12
WͲhoursTotalMeter10
WͲhoursTotalMeter11
WͲhoursTotalMeter12
VARͲhoursPositiveMeter10
VARͲhoursPositiveMeter11
VARͲhoursPositiveMeter12
VARͲhoursNegativeMeter10
VARͲhoursNegativeMeter11
VARͲhoursNegativeMeter12
VARͲhoursNetMeter10
VARͲhoursNetMeter11
VARͲhoursNetMeter12
VARͲhoursTotalMeter10
VARͲhoursTotalMeter11
VARͲhoursTotalMeter12
VAͲhoursTotalMeter10
VAͲhoursTotalMeter11
VAͲhoursTotalMeter12
WͲhoursReceivedMeter13
WͲhoursReceivedMeter14
WͲhoursReceivedMeter15
WͲhoursDeliveredMeter13
WͲhoursDeliveredMeter14
WͲhoursDeliveredMeter15
WͲhoursNetMeter13
WͲhoursNetMeter14
WͲhoursNetMeter15
WͲhoursTotalMeter13
WͲhoursTotalMeter14
WͲhoursTotalMeter15
VARͲhoursPositiveMeter13
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
N2
Point
Address
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
Doc# E204701
EIPTagName
S32_XXX[086]
S32_XXX[087]
S32_XXX[088]
S32_XXX[089]
S32_XXX[090]
S32_XXX[091]
S32_XXX[092]
S32_XXX[093]
S32_XXX[094]
S32_XXX[095]
S32_XXX[096]
S32_XXX[097]
S32_XXX[098]
S32_XXX[099]
S32_XXX[100]
S32_XXX[101]
S32_XXX[102]
S32_XXX[103]
S32_XXX[104]
S32_XXX[105]
S32_XXX[106]
S32_XXX[107]
S32_XXX[108]
S32_XXX[109]
S32_XXX[110]
S32_XXX[111]
S32_XXX[112]
S32_XXX[113]
S32_XXX[114]
S32_XXX[115]
S32_XXX[116]
S32_XXX[117]
S32_XXX[118]
S32_XXX[119]
S32_XXX[120]
DF1
Address
F12:086
F12:087
F12:088
F12:089
F12:090
F12:091
F12:092
F12:093
F12:094
F12:095
F12:096
F12:097
F12:098
F12:099
F12:100
F12:101
F12:102
F12:103
F12:104
F12:105
F12:106
F12:107
F12:108
F12:109
F12:110
F12:111
F12:112
F12:113
F12:114
F12:115
F12:116
F12:117
F12:118
F12:119
F12:120
LonName
nvoWHDelM12_XXX
nvoWHNetM10_XXX
nvoWHNetM11_XXX
nvoWHNetM12_XXX
nvoWHTotM10_XXX
nvoWHTotM11_XXX
nvoWHTotM12_XXX
nvoVARhPsM10_XXX
nvoVARhPsM11_XXX
nvoVARhPsM12_XXX
nvoVARhNgM10_XXX
nvoVARhNgM11_XXX
nvoVARhNgM12_XXX
nvoVARhNtM10_XXX
nvoVARhNtM11_XXX
nvoVARhNtM12_XXX
nvoVARhToM10_XXX
nvoVARhToM11_XXX
nvoVARhToM12_XXX
nvoVAhTotM10_XXX
nvoVAhTotM11_XXX
nvoVAhTotM12_XXX
nvoWHRecM13_XXX
nvoWHRecM14_XXX
nvoWHRecM15_XXX
nvoWHDelM13_XXX
nvoWHDelM14_XXX
nvoWHDelM15_XXX
nvoWHNetM13_XXX
nvoWHNetM14_XXX
nvoWHNetM15_XXX
nvoWHTotM13_XXX
nvoWHTotM14_XXX
nvoWHTotM15_XXX
nvoVARhPsM13_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-26
A: Protocol Data Points for EIG Meters
PointName
VARͲhoursPositiveMeter14
VARͲhoursPositiveMeter15
VARͲhoursNegativeMeter13
VARͲhoursNegativeMeter14
VARͲhoursNegativeMeter15
VARͲhoursNetMeter13
VARͲhoursNetMeter14
VARͲhoursNetMeter15
VARͲhoursTotalMeter13
VARͲhoursTotalMeter14
VARͲhoursTotalMeter15
VAͲhoursTotalMeter13
VAͲhoursTotalMeter14
VAͲhoursTotalMeter15
WͲhoursReceivedMeter16
WͲhoursReceivedMeter17
WͲhoursReceivedMeter18
WͲhoursDeliveredMeter16
WͲhoursDeliveredMeter17
WͲhoursDeliveredMeter18
WͲhoursNetMeter16
WͲhoursNetMeter17
WͲhoursNetMeter18
WͲhoursTotalMeter16
WͲhoursTotalMeter17
WͲhoursTotalMeter18
VARͲhoursPositiveMeter16
VARͲhoursPositiveMeter17
VARͲhoursPositiveMeter18
VARͲhoursNegativeMeter16
VARͲhoursNegativeMeter17
VARͲhoursNegativeMeter18
VARͲhoursNetMeter16
VARͲhoursNetMeter17
VARͲhoursNetMeter18
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
N2
Point
Address
244
245
246
247
248
249
250
251
252
253
254
255
256
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
EIPTagName
S32_XXX[121]
S32_XXX[122]
S32_XXX[123]
S32_XXX[124]
S32_XXX[125]
S32_XXX[126]
S32_XXX[127]
S32_XXX[128]
S32_XXX[129]
S32_XXX[130]
S32_XXX[131]
S32_XXX[132]
S32_XXX[133]
S32_XXX[134]
S32_XXX[135]
S32_XXX[136]
S32_XXX[137]
S32_XXX[138]
S32_XXX[139]
S32_XXX[140]
S32_XXX[141]
S32_XXX[142]
S32_XXX[143]
S32_XXX[144]
S32_XXX[145]
S32_XXX[146]
S32_XXX[147]
S32_XXX[148]
S32_XXX[149]
S32_XXX[150]
S32_XXX[151]
S32_XXX[152]
S32_XXX[153]
S32_XXX[154]
S32_XXX[155]
Doc# E204701
DF1
Address
F12:121
F12:122
F12:123
F12:124
F12:125
F12:126
F12:127
F12:128
F12:129
F12:130
F12:131
F12:132
F12:133
F12:134
F12:135
F12:136
F12:137
F12:138
F12:139
F12:140
F12:141
F12:142
F12:143
F12:144
F12:145
F12:146
F12:147
F12:148
F12:149
F12:150
F12:151
F12:152
F12:153
F12:154
F12:155
LonName
nvoVARhPsM14_XXX
nvoVARhPsM15_XXX
nvoVARhNgM13_XXX
nvoVARhNgM14_XXX
nvoVARhNgM15_XXX
nvoVARhNtM13_XXX
nvoVARhNtM14_XXX
nvoVARhNtM15_XXX
nvoVARhToM13_XXX
nvoVARhToM14_XXX
nvoVARhToM15_XXX
nvoVAhTotM13_XXX
nvoVAhTotM14_XXX
nvoVAhTotM15_XXX
nvoWHRecM16_XXX
nvoWHRecM17_XXX
nvoWHRecM18_XXX
nvoWHDelM16_XXX
nvoWHDelM17_XXX
nvoWHDelM18_XXX
nvoWHNetM16_XXX
nvoWHNetM17_XXX
nvoWHNetM18_XXX
nvoWHTotM16_XXX
nvoWHTotM17_XXX
nvoWHTotM18_XXX
nvoVARhPsM16_XXX
nvoVARhPsM17_XXX
nvoVARhPsM18_XXX
nvoVARhNgM16_XXX
nvoVARhNgM17_XXX
nvoVARhNgM18_XXX
nvoVARhNtM16_XXX
nvoVARhNtM17_XXX
nvoVARhNtM18_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-27
A: Protocol Data Points for EIG Meters
PointName
VARͲhoursTotalMeter16
VARͲhoursTotalMeter17
VARͲhoursTotalMeter18
VAͲhoursTotalMeter16
VAͲhoursTotalMeter17
VAͲhoursTotalMeter18
WͲhoursReceivedMeter19
WͲhoursReceivedMeter20
WͲhoursReceivedMeter21
WͲhoursDeliveredMeter19
WͲhoursDeliveredMeter20
WͲhoursDeliveredMeter21
WͲhoursNetMeter19
WͲhoursNetMeter20
WͲhoursNetMeter21
WͲhoursTotalMeter19
WͲhoursTotalMeter20
WͲhoursTotalMeter21
VARͲhoursPositiveMeter19
VARͲhoursPositiveMeter20
VARͲhoursPositiveMeter21
VARͲhoursNegativeMeter19
VARͲhoursNegativeMeter20
VARͲhoursNegativeMeter21
VARͲhoursNetMeter19
VARͲhoursNetMeter20
VARͲhoursNetMeter21
VARͲhoursTotalMeter19
VARͲhoursTotalMeter20
VARͲhoursTotalMeter21
VAͲhoursTotalMeter19
VAͲhoursTotalMeter20
VAͲhoursTotalMeter21
WͲhoursReceivedMeter22
WͲhoursReceivedMeter23
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
N2
Point
Address
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
EIPTagName
S32_XXX[156]
S32_XXX[157]
S32_XXX[158]
S32_XXX[159]
S32_XXX[160]
S32_XXX[161]
S32_XXX[162]
S32_XXX[163]
S32_XXX[164]
S32_XXX[165]
S32_XXX[166]
S32_XXX[167]
S32_XXX[168]
S32_XXX[169]
S32_XXX[170]
S32_XXX[171]
S32_XXX[172]
S32_XXX[173]
S32_XXX[174]
S32_XXX[175]
S32_XXX[176]
S32_XXX[177]
S32_XXX[178]
S32_XXX[179]
S32_XXX[180]
S32_XXX[181]
S32_XXX[182]
S32_XXX[183]
S32_XXX[184]
S32_XXX[185]
S32_XXX[186]
S32_XXX[187]
S32_XXX[188]
S32_XXX[189]
S32_XXX[190]
Doc# E204701
DF1
Address
F12:156
F12:157
F12:158
F12:159
F12:160
F12:161
F12:162
F12:163
F12:164
F12:165
F12:166
F12:167
F12:168
F12:169
F12:170
F12:171
F12:172
F12:173
F12:174
F12:175
F12:176
F12:177
F12:178
F12:179
F12:180
F12:181
F12:182
F12:183
F12:184
F12:185
F12:186
F12:187
F12:188
F12:189
F12:190
LonName
nvoVARhToM16_XXX
nvoVARhToM17_XXX
nvoVARhToM18_XXX
nvoVAhTotM16_XXX
nvoVAhTotM17_XXX
nvoVAhTotM18_XXX
nvoWHRecM19_XXX
nvoWHRecM20_XXX
nvoWHRecM21_XXX
nvoWHDelM19_XXX
nvoWHDelM20_XXX
nvoWHDelM21_XXX
nvoWHNetM19_XXX
nvoWHNetM20_XXX
nvoWHNetM21_XXX
nvoWHTotM19_XXX
nvoWHTotM20_XXX
nvoWHTotM21_XXX
nvoVARhPsM19_XXX
nvoVARhPsM20_XXX
nvoVARhPsM21_XXX
nvoVARhNgM19_XXX
nvoVARhNgM20_XXX
nvoVARhNgM21_XXX
nvoVARhNtM19_XXX
nvoVARhNtM20_XXX
nvoVARhNtM21_XXX
nvoVARhToM19_XXX
nvoVARhToM20_XXX
nvoVARhToM21_XXX
nvoVAhTotM19_XXX
nvoVAhTotM20_XXX
nvoVAhTotM21_XXX
nvoWHRecM22_XXX
nvoWHRecM23_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-28
A: Protocol Data Points for EIG Meters
PointName
WͲhoursReceivedMeter24
WͲhoursDeliveredMeter22
WͲhoursDeliveredMeter23
WͲhoursDeliveredMeter24
WͲhoursNetMeter22
WͲhoursNetMeter23
WͲhoursNetMeter24
WͲhoursTotalMeter22
WͲhoursTotalMeter23
WͲhoursTotalMeter24
VARͲhoursPositiveMeter22
VARͲhoursPositiveMeter23
VARͲhoursPositiveMeter24
VARͲhoursNegativeMeter22
VARͲhoursNegativeMeter23
VARͲhoursNegativeMeter24
VARͲhoursNetMeter22
VARͲhoursNetMeter23
VARͲhoursNetMeter24
VARͲhoursTotalMeter22
VARͲhoursTotalMeter23
VARͲhoursTotalMeter24
VAͲhoursTotalMeter22
VAͲhoursTotalMeter23
VAͲhoursTotalMeter24
PositiveWattsMeter01Avg
PositiveWattsMeter02Avg
PositiveWattsMeter03Avg
PositiveVARsMeter01Avg
PositiveVARsMeter02Avg
PositiveVARsMeter03Avg
NegativeWattsMeter01Avg
NegativeWattsMeter02Avg
NegativeWattsMeter03Avg
NegativeVARsMeter01Avg
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
N2
Point
Address
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
EIPTagName
S32_XXX[191]
S32_XXX[192]
S32_XXX[193]
S32_XXX[194]
S32_XXX[195]
S32_XXX[196]
S32_XXX[197]
S32_XXX[198]
S32_XXX[199]
S32_XXX[200]
S32_XXX[201]
S32_XXX[202]
S32_XXX[203]
S32_XXX[204]
S32_XXX[205]
S32_XXX[206]
S32_XXX[207]
S32_XXX[208]
S32_XXX[209]
S32_XXX[210]
S32_XXX[211]
S32_XXX[212]
S32_XXX[213]
S32_XXX[214]
S32_XXX[215]
Flt_XXX[122]
Flt_XXX[123]
Flt_XXX[124]
Flt_XXX[125]
Flt_XXX[126]
Flt_XXX[127]
Flt_XXX[128]
Flt_XXX[129]
Flt_XXX[130]
Flt_XXX[131]
Doc# E204701
DF1
Address
F12:191
F12:192
F12:193
F12:194
F12:195
F12:196
F12:197
F12:198
F12:199
F12:200
F12:201
F12:202
F12:203
F12:204
F12:205
F12:206
F12:207
F12:208
F12:209
F12:210
F12:211
F12:212
F12:213
F12:214
F12:215
F10:122
F10:123
F10:124
F10:125
F10:126
F10:127
F10:128
F10:129
F10:130
F10:131
LonName
nvoWHRecM24_XXX
nvoWHDelM22_XXX
nvoWHDelM23_XXX
nvoWHDelM24_XXX
nvoWHNetM22_XXX
nvoWHNetM23_XXX
nvoWHNetM24_XXX
nvoWHTotM22_XXX
nvoWHTotM23_XXX
nvoWHTotM24_XXX
nvoVARhPsM22_XXX
nvoVARhPsM23_XXX
nvoVARhPsM24_XXX
nvoVARhNgM22_XXX
nvoVARhNgM23_XXX
nvoVARhNgM24_XXX
nvoVARhNtM22_XXX
nvoVARhNtM23_XXX
nvoVARhNtM24_XXX
nvoVARhToM22_XXX
nvoVARhToM23_XXX
nvoVARhToM24_XXX
nvoVAhTotM22_XXX
nvoVAhTotM23_XXX
nvoVAhTotM24_XXX
nvoPsWtM1Avg_XXX
nvoPsWtM2Avg_XXX
nvoPsWtM3Avg_XXX
nvoPsVARM1Av_XXX
nvoPsVARM2Av_XXX
nvoPsVARM3Av_XXX
nvoNgWtM1Avg_XXX
nvoNgWtM2Avg_XXX
nvoNgWtM3Avg_XXX
nvoNgVARM1Av_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-29
A: Protocol Data Points for EIG Meters
PointName
NegativeVARsMeter02Avg
NegativeVARsMeter03Avg
PositiveWattsMeter04Avg
PositiveWattsMeter05Avg
PositiveWattsMeter06Avg
PositiveVARsMeter04Avg
PositiveVARsMeter05Avg
PositiveVARsMeter06Avg
NegativeWattsMeter04Avg
NegativeWattsMeter05Avg
NegativeWattsMeter06Avg
NegativeVARsMeter04Avg
NegativeVARsMeter05Avg
NegativeVARsMeter06Avg
PositiveWattsMeter07Avg
PositiveWattsMeter08Avg
PositiveWattsMeter09Avg
PositiveVARsMeter07Avg
PositiveVARsMeter08Avg
PositiveVARsMeter09Avg
NegativeWattsMeter07Avg
NegativeWattsMeter08Avg
NegativeWattsMeter09Avg
NegativeVARsMeter07Avg
NegativeVARsMeter08Avg
NegativeVARsMeter09Avg
PositiveWattsMeter10Avg
PositiveWattsMeter11Avg
PositiveWattsMeter12Avg
PositiveVARsMeter10Avg
PositiveVARsMeter11Avg
PositiveVARsMeter12Avg
NegativeWattsMeter10Avg
NegativeWattsMeter11Avg
NegativeWattsMeter12Avg
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378
379
380
381
382
383
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
N2
Point
Address
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
EIPTagName
Flt_XXX[132]
Flt_XXX[133]
Flt_XXX[134]
Flt_XXX[135]
Flt_XXX[136]
Flt_XXX[137]
Flt_XXX[138]
Flt_XXX[139]
Flt_XXX[140]
Flt_XXX[141]
Flt_XXX[142]
Flt_XXX[143]
Flt_XXX[144]
Flt_XXX[145]
Flt_XXX[146]
Flt_XXX[147]
Flt_XXX[148]
Flt_XXX[149]
Flt_XXX[150]
Flt_XXX[151]
Flt_XXX[152]
Flt_XXX[153]
Flt_XXX[154]
Flt_XXX[155]
Flt_XXX[156]
Flt_XXX[157]
Flt_XXX[158]
Flt_XXX[159]
Flt_XXX[160]
Flt_XXX[161]
Flt_XXX[162]
Flt_XXX[163]
Flt_XXX[164]
Flt_XXX[165]
Flt_XXX[166]
Doc# E204701
DF1
Address
F10:132
F10:133
F10:134
F10:135
F10:136
F10:137
F10:138
F10:139
F10:140
F10:141
F10:142
F10:143
F10:144
F10:145
F10:146
F10:147
F10:148
F10:149
F10:150
F10:151
F10:152
F10:153
F10:154
F10:155
F10:156
F10:157
F10:158
F10:159
F10:160
F10:161
F10:162
F10:163
F10:164
F10:165
F10:166
LonName
nvoNgVARM2Av_XXX
nvoNgVARM3Av_XXX
nvoPsWtM4Avg_XXX
nvoPsWtM5Avg_XXX
nvoPsWtM6Avg_XXX
nvoPsVARM4Av_XXX
nvoPsVARM5Av_XXX
nvoPsVARM6Av_XXX
nvoNgWtM4Avg_XXX
nvoNgWtM5Avg_XXX
nvoNgWtM6Avg_XXX
nvoNgVARM4Av_XXX
nvoNgVARM5Av_XXX
nvoNgVARM6Av_XXX
nvoPsWtM7Avg_XXX
nvoPsWtM8Avg_XXX
nvoPsWtM9Avg_XXX
nvoPsVARM7Av_XXX
nvoPsVARM8Av_XXX
nvoPsVARM9Av_XXX
nvoNgWtM7Avg_XXX
nvoNgWtM8Avg_XXX
nvoNgWtM9Avg_XXX
nvoNgVARM7Av_XXX
nvoNgVARM8Av_XXX
nvoNgVARM9Av_XXX
nvoPsWtM10Av_XXX
nvoPsWtM11Av_XXX
nvoPsWtM12Av_XXX
nvoPsVAR10Av_XXX
nvoPsVAR11Av_XXX
nvoPsVAR12Av_XXX
nvoNgWtM10Av_XXX
nvoNgWtM11Av_XXX
nvoNgWtM12Av_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-30
A: Protocol Data Points for EIG Meters
PointName
NegativeVARsMeter10Avg
NegativeVARsMeter11Avg
NegativeVARsMeter12Avg
PositiveWattsMeter13Avg
PositiveWattsMeter14Avg
PositiveWattsMeter15Avg
PositiveVARsMeter13Avg
PositiveVARsMeter14Avg
PositiveVARsMeter15Avg
NegativeWattsMeter13Avg
NegativeWattsMeter14Avg
NegativeWattsMeter15Avg
NegativeVARsMeter13Avg
NegativeVARsMeter14Avg
NegativeVARsMeter15Avg
PositiveWattsMeter16Avg
PositiveWattsMeter17Avg
PositiveWattsMeter18Avg
PositiveVARsMeter16Avg
PositiveVARsMeter17Avg
PositiveVARsMeter18Avg
NegativeWattsMeter16Avg
NegativeWattsMeter17Avg
NegativeWattsMeter18Avg
NegativeVARsMeter16Avg
NegativeVARsMeter17Avg
NegativeVARsMeter18Avg
PositiveWattsMeter19Avg
PositiveWattsMeter20Avg
PositiveWattsMeter21Avg
PositiveVARsMeter19Avg
PositiveVARsMeter20Avg
PositiveVARsMeter21Avg
NegativeWattsMeter19Avg
NegativeWattsMeter20Avg
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
384
385
386
387
388
389
390
391
392
393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
N2
Point
Address
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
EIPTagName
Flt_XXX[167]
Flt_XXX[168]
Flt_XXX[169]
Flt_XXX[170]
Flt_XXX[171]
Flt_XXX[172]
Flt_XXX[173]
Flt_XXX[174]
Flt_XXX[175]
Flt_XXX[176]
Flt_XXX[177]
Flt_XXX[178]
Flt_XXX[179]
Flt_XXX[180]
Flt_XXX[181]
Flt_XXX[182]
Flt_XXX[183]
Flt_XXX[184]
Flt_XXX[185]
Flt_XXX[186]
Flt_XXX[187]
Flt_XXX[188]
Flt_XXX[189]
Flt_XXX[190]
Flt_XXX[191]
Flt_XXX[192]
Flt_XXX[193]
Flt_XXX[194]
Flt_XXX[195]
Flt_XXX[196]
Flt_XXX[197]
Flt_XXX[198]
Flt_XXX[199]
Flt_XXX[200]
Flt_XXX[201]
Doc# E204701
DF1
Address
F10:167
F10:168
F10:169
F10:170
F10:171
F10:172
F10:173
F10:174
F10:175
F10:176
F10:177
F10:178
F10:179
F10:180
F10:181
F10:182
F10:183
F10:184
F10:185
F10:186
F10:187
F10:188
F10:189
F10:190
F10:191
F10:192
F10:193
F10:194
F10:195
F10:196
F10:197
F10:198
F10:199
F10:200
F10:201
LonName
nvoNgVAR10Av_XXX
nvoNgVAR11Av_XXX
nvoNgVAR12Av_XXX
nvoPsWtM13Av_XXX
nvoPsWtM14Av_XXX
nvoPsWtM15Av_XXX
nvoPsVAR13Av_XXX
nvoPsVAR14Av_XXX
nvoPsVAR15Av_XXX
nvoNgWtM13Av_XXX
nvoNgWtM14Av_XXX
nvoNgWtM15Av_XXX
nvoNgVAR13Av_XXX
nvoNgVAR14Av_XXX
nvoNgVAR15Av_XXX
nvoPsWtM16Av_XXX
nvoPsWtM17Av_XXX
nvoPsWtM18Av_XXX
nvoPsVAR16Av_XXX
nvoPsVAR17Av_XXX
nvoPsVAR18Av_XXX
nvoNgWtM16Av_XXX
nvoNgWtM17Av_XXX
nvoNgWtM18Av_XXX
nvoNgVAR16Av_XXX
nvoNgVAR17Av_XXX
nvoNgVAR18Av_XXX
nvoPsWtM19Av_XXX
nvoPsWtM20Av_XXX
nvoPsWtM21Av_XXX
nvoPsVAR19Av_XXX
nvoPsVAR20Av_XXX
nvoPsVAR21Av_XXX
nvoNgWtM19Av_XXX
nvoNgWtM20Av_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-31
A: Protocol Data Points for EIG Meters
PointName
NegativeWattsMeter21Avg
NegativeVARsMeter19Avg
NegativeVARsMeter20Avg
NegativeVARsMeter21Avg
PositiveWattsMeter22Avg
PositiveWattsMeter23Avg
PositiveWattsMeter24Avg
PositiveVARsMeter22Avg
PositiveVARsMeter23Avg
PositiveVARsMeter24Avg
NegativeWattsMeter22Avg
NegativeWattsMeter23Avg
NegativeWattsMeter24Avg
NegativeVARsMeter22Avg
NegativeVARsMeter23Avg
NegativeVARsMeter24Avg
CurrentDateandTime1
CurrentDateandTime2
CurrentDateandTime3
PosWattsMeter01MaxAvgDem
PosWattsMeter02MaxAvgDem
PosWattsMeter03MaxAvgDem
PosVARsMeter01MaxAvgDem
PosVARsMeter02MaxAvgDem
PosVARsMeter03MaxAvgDem
NegWattsMeter01MaxAvgDem
NegWattsMeter02MaxAvgDem
NegWattsMeter03MaxAvgDem
NegVARsMeter01MaxAvgDem
NegVARsMeter02MaxAvgDem
NegVARsMeter03MaxAvgDem
PosWattsMeter04MaxAvgDem
PosWattsMeter05MaxAvgDem
PosWattsMeter06MaxAvgDem
PosVARsMeter04MaxAvgDem
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
441
442
443
444
445
446
447
448
449
450
451
452
453
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
N2
Point
Address
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
EIPTagName
Flt_XXX[202]
Flt_XXX[203]
Flt_XXX[204]
Flt_XXX[205]
Flt_XXX[206]
Flt_XXX[207]
Flt_XXX[208]
Flt_XXX[209]
Flt_XXX[210]
Flt_XXX[211]
Flt_XXX[212]
Flt_XXX[213]
Flt_XXX[214]
Flt_XXX[215]
Flt_XXX[216]
Flt_XXX[217]
Dev1_XXX[000]
Dev1_XXX[001]
Dev1_XXX[002]
Flt_XXX[218]
Flt_XXX[219]
Flt_XXX[220]
Flt_XXX[221]
Flt_XXX[222]
Flt_XXX[223]
Flt_XXX[224]
Flt_XXX[225]
Flt_XXX[226]
Flt_XXX[227]
Flt_XXX[228]
Flt_XXX[229]
Flt_XXX[230]
Flt_XXX[231]
Flt_XXX[232]
Flt_XXX[233]
Doc# E204701
DF1
Address
F10:202
F10:203
F10:204
F10:205
F10:206
F10:207
F10:208
F10:209
F10:210
F10:211
F10:212
F10:213
F10:214
F10:215
F10:216
F10:217
N13:000
N13:001
N13:002
F10:218
F10:219
F10:220
F10:221
F10:222
F10:223
F10:224
F10:225
F10:226
F10:227
F10:228
F10:229
F10:230
F10:231
F10:232
F10:233
LonName
nvoNgWtM21Av_XXX
nvoNgVAR19Av_XXX
nvoNgVAR20Av_XXX
nvoNgVAR21Av_XXX
nvoPsWtM22Av_XXX
nvoPsWtM23Av_XXX
nvoPsWtM24Av_XXX
nvoPsVAR22Av_XXX
nvoPsVAR23Av_XXX
nvoPsVAR24Av_XXX
nvoNgWtM22Av_XXX
nvoNgWtM23Av_XXX
nvoNgWtM24Av_XXX
nvoNgVAR22Av_XXX
nvoNgVAR23Av_XXX
nvoNgVAR24Av_XXX
nvoCurDatTm1_XXX
nvoCurDatTm2_XXX
nvoCurDatTm3_XXX
nvoPWt1MxAvD_XXX
nvoPWt2MxAvD_XXX
nvoPWt3MxAvD_XXX
nvoPVAR1MxAv_XXX
nvoPVAR2MxAv_XXX
nvoPVAR3MxAv_XXX
nvoNWt1MxAvD_XXX
nvoNWt2MxAvD_XXX
nvoNWt3MxAvD_XXX
nvoNVAR1MxAv_XXX
nvoNVAR2MxAv_XXX
nvoNVAR3MxAv_XXX
nvoPWt4MxAvD_XXX
nvoPWt5MxAvD_XXX
nvoPWt6MxAvD_XXX
nvoPVAR4MxAv_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-32
A: Protocol Data Points for EIG Meters
PointName
PosVARsMeter05MaxAvgDem
PosVARsMeter06MaxAvgDem
NegWattsMeter04MaxAvgDem
NegWattsMeter05MaxAvgDem
NegWattsMeter06MaxAvgDem
NegVARsMeter04MaxAvgDem
NegVARsMeter05MaxAvgDem
NegVARsMeter06MaxAvgDem
PosWattsMeter07MaxAvgDem
PosWattsMeter08MaxAvgDem
PosWattsMeter09MaxAvgDem
PosVARsMeter07MaxAvgDem
PosVARsMeter08MaxAvgDem
PosVARsMeter09MaxAvgDem
NegWattsMeter07MaxAvgDem
NegWattsMeter08MaxAvgDem
NegWattsMeter09MaxAvgDem
NegVARsMeter07MaxAvgDem
NegVARsMeter08MaxAvgDem
NegVARsMeter09MaxAvgDem
PosWattsMeter10MaxAvgDem
PosWattsMeter11MaxAvgDem
PosWattsMeter12MaxAvgDem
PosVARsMeter10MaxAvgDem
PosVARsMeter11MaxAvgDem
PosVARsMeter12MaxAvgDem
NegWattsMeter10MaxAvgDem
NegWattsMeter11MaxAvgDem
NegWattsMeter12MaxAvgDem
NegVARsMeter10MaxAvgDem
NegVARsMeter11MaxAvgDem
NegVARsMeter12MaxAvgDem
PosWattsMeter13MaxAvgDem
PosWattsMeter14MaxAvgDem
PosWattsMeter15MaxAvgDem
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470
471
472
473
474
475
476
477
478
479
480
481
482
483
484
485
486
487
488
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
N2
Point
Address
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
EIPTagName
Flt_XXX[234]
Flt_XXX[235]
Flt_XXX[236]
Flt_XXX[237]
Flt_XXX[238]
Flt_XXX[239]
Flt_XXX[240]
Flt_XXX[241]
Flt_XXX[242]
Flt_XXX[243]
Flt_XXX[244]
Flt_XXX[245]
Flt_XXX[246]
Flt_XXX[247]
Flt_XXX[248]
Flt_XXX[249]
Flt_XXX[250]
Flt_XXX[251]
Flt_XXX[252]
Flt_XXX[253]
Flt_XXX[254]
Flt_XXX[255]
Flt_XXX[256]
Flt_XXX[257]
Flt_XXX[258]
Flt_XXX[259]
Flt_XXX[260]
Flt_XXX[261]
Flt_XXX[262]
Flt_XXX[263]
Flt_XXX[264]
Flt_XXX[265]
Flt_XXX[266]
Flt_XXX[267]
Flt_XXX[268]
Doc# E204701
DF1
Address
F10:234
F10:235
F10:236
F10:237
F10:238
F10:239
F10:240
F10:241
F10:242
F10:243
F10:244
F10:245
F10:246
F10:247
F10:248
F10:249
F10:250
F10:251
F10:252
F10:253
F10:254
F11:000
F11:001
F11:002
F11:003
F11:004
F11:005
F11:006
F11:007
F11:008
F11:009
F11:010
F11:011
F11:012
F11:013
LonName
nvoPVAR5MxAv_XXX
nvoPVAR6MxAv_XXX
nvoNWt4MxAvD_XXX
nvoNWt5MxAvD_XXX
nvoNWt6MxAvD_XXX
nvoNVAR4MxAv_XXX
nvoNVAR5MxAv_XXX
nvoNVAR6MxAv_XXX
nvoPWt7MxAvD_XXX
nvoPWt8MxAvD_XXX
nvoPWt9MxAvD_XXX
nvoPVAR7MxAv_XXX
nvoPVAR8MxAv_XXX
nvoPVAR9MxAv_XXX
nvoNWt7MxAvD_XXX
nvoNWt8MxAvD_XXX
nvoNWt9MxAvD_XXX
nvoNVAR7MxAv_XXX
nvoNVAR8MxAv_XXX
nvoNVAR9MxAv_XXX
nvoPWt10MxAv_XXX
nvoPWt11MxAv_XXX
nvoPWt12MxAv_XXX
nvoPVAR10MxA_XXX
nvoPVAR11MxA_XXX
nvoPVAR12MxA_XXX
nvoNWt10MxAv_XXX
nvoNWt11MxAv_XXX
nvoNWt12MxAv_XXX
nvoNVAR10MxA_XXX
nvoNVAR11MxA_XXX
nvoNVAR12MxA_XXX
nvoPWt13MxAv_XXX
nvoPWt14MxAv_XXX
nvoPWt15MxAv_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-33
A: Protocol Data Points for EIG Meters
PointName
PosVARsMeter13MaxAvgDem
PosVARsMeter14MaxAvgDem
PosVARsMeter15MaxAvgDem
NegWattsMeter13MaxAvgDem
NegWattsMeter14MaxAvgDem
NegWattsMeter15MaxAvgDem
NegVARsMeter13MaxAvgDem
NegVARsMeter14MaxAvgDem
NegVARsMeter15MaxAvgDem
PosWattsMeter16MaxAvgDem
PosWattsMeter17MaxAvgDem
PosWattsMeter18MaxAvgDem
PosVARsMeter16MaxAvgDem
PosVARsMeter17MaxAvgDem
PosVARsMeter18MaxAvgDem
NegWattsMeter16MaxAvgDem
NegWattsMeter17MaxAvgDem
NegWattsMeter18MaxAvgDem
NegVARsMeter16MaxAvgDem
NegVARsMeter17MaxAvgDem
NegVARsMeter18MaxAvgDem
PosWattsMeter19MaxAvgDem
PosWattsMeter20MaxAvgDem
PosWattsMeter21MaxAvgDem
PosVARsMeter19MaxAvgDem
PosVARsMeter20MaxAvgDem
PosVARsMeter21MaxAvgDem
NegWattsMeter19MaxAvgDem
NegWattsMeter20MaxAvgDem
NegWattsMeter21MaxAvgDem
NegVARsMeter19MaxAvgDem
NegVARsMeter20MaxAvgDem
NegVARsMeter21MaxAvgDem
PosWattsMeter22MaxAvgDem
PosWattsMeter23MaxAvgDem
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
489
490
491
492
493
494
495
496
497
498
499
500
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
517
518
519
520
521
522
523
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
N2
Point
Address
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
1
2
3
4
5
6
7
8
9
10
11
EIPTagName
Flt_XXX[269]
Flt_XXX[270]
Flt_XXX[271]
Flt_XXX[272]
Flt_XXX[273]
Flt_XXX[274]
Flt_XXX[275]
Flt_XXX[276]
Flt_XXX[277]
Flt_XXX[278]
Flt_XXX[279]
Flt_XXX[280]
Flt_XXX[281]
Flt_XXX[282]
Flt_XXX[283]
Flt_XXX[284]
Flt_XXX[285]
Flt_XXX[286]
Flt_XXX[287]
Flt_XXX[288]
Flt_XXX[289]
Flt_XXX[290]
Flt_XXX[291]
Flt_XXX[292]
Flt_XXX[293]
Flt_XXX[294]
Flt_XXX[295]
Flt_XXX[296]
Flt_XXX[297]
Flt_XXX[298]
Flt_XXX[299]
Flt_XXX[300]
Flt_XXX[301]
Flt_XXX[302]
Flt_XXX[303]
Doc# E204701
DF1
Address
F11:014
F11:015
F11:016
F11:017
F11:018
F11:019
F11:020
F11:021
F11:022
F11:023
F11:024
F11:025
F11:026
F11:027
F11:028
F11:029
F11:030
F11:031
F11:032
F11:033
F11:034
F11:035
F11:036
F11:037
F11:038
F11:039
F11:040
F11:041
F11:042
F11:043
F11:044
F11:045
F11:046
F11:047
F11:048
LonName
nvoPVAR13MxA_XXX
nvoPVAR14MxA_XXX
nvoPVAR15MxA_XXX
nvoNWt13MxAv_XXX
nvoNWt14MxAv_XXX
nvoNWt15MxAv_XXX
nvoNVAR13MxA_XXX
nvoNVAR14MxA_XXX
nvoNVAR15MxA_XXX
nvoPWt16MxAv_XXX
nvoPWt17MxAv_XXX
nvoPWt18MxAv_XXX
nvoPVAR16MxA_XXX
nvoPVAR17MxA_XXX
nvoPVAR18MxA_XXX
nvoNWt16MxAv_XXX
nvoNWt17MxAv_XXX
nvoNWt18MxAv_XXX
nvoNVAR16MxA_XXX
nvoNVAR17MxA_XXX
nvoNVAR18MxA_XXX
nvoPWt19MxAv_XXX
nvoPWt20MxAv_XXX
nvoPWt21MxAv_XXX
nvoPVAR19MxA_XXX
nvoPVAR20MxA_XXX
nvoPVAR21MxA_XXX
nvoNWt19MxAv_XXX
nvoNWt20MxAv_XXX
nvoNWt21MxAv_XXX
nvoNVAR19MxA_XXX
nvoNVAR20MxA_XXX
nvoNVAR21MxA_XXX
nvoPWt22MxAv_XXX
nvoPWt23MxAv_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
A-34
A: Protocol Data Points for EIG Meters
PointName
PosWattsMeter24MaxAvgDem
PosVARsMeter22MaxAvgDem
PosVARsMeter23MaxAvgDem
PosVARsMeter24MaxAvgDem
NegWattsMeter22MaxAvgDem
NegWattsMeter23MaxAvgDem
NegWattsMeter24MaxAvgDem
NegVARsMeter22MaxAvgDem
NegVARsMeter23MaxAvgDem
NegVARsMeter24MaxAvgDem
CTDenominator
CTNumeratorMeter1
CTNumeratorMeter2
CTNumeratorMeter3
CTNumeratorMeter4
CTNumeratorMeter5
CTNumeratorMeter6
CTNumeratorMeter7
CTNumeratorMeter8
CTNumeratorMeter9
CTNumeratorMeter10
CTNumeratorMeter11
CTNumeratorMeter12
CTNumeratorMeter13
CTNumeratorMeter14
CTNumeratorMeter15
CTNumeratorMeter16
CTNumeratorMeter17
CTNumeratorMeter18
CTNumeratorMeter19
CTNumeratorMeter20
CTNumeratorMeter21
CTNumeratorMeter22
CTNumeratorMeter23
CTNumeratorMeter24
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BACnet
Object
ID
524
525
526
527
528
529
530
531
532
533
534
535
536
537
538
539
540
541
542
543
544
545
546
547
548
549
550
551
552
553
554
555
556
557
558
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
N2
Point
Address
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
EIPTagName
Flt_XXX[304]
Flt_XXX[305]
Flt_XXX[306]
Flt_XXX[307]
Flt_XXX[308]
Flt_XXX[309]
Flt_XXX[310]
Flt_XXX[311]
Flt_XXX[312]
Flt_XXX[313]
Dev2_XXX[000]
Dev2_XXX[001]
Dev2_XXX[002]
Dev2_XXX[003]
Dev2_XXX[004]
Dev2_XXX[005]
Dev2_XXX[006]
Dev2_XXX[007]
Dev2_XXX[008]
Dev2_XXX[009]
Dev2_XXX[010]
Dev2_XXX[011]
Dev2_XXX[012]
Dev2_XXX[013]
Dev2_XXX[014]
Dev2_XXX[015]
Dev2_XXX[016]
Dev2_XXX[017]
Dev2_XXX[018]
Dev2_XXX[019]
Dev2_XXX[020]
Dev2_XXX[021]
Dev2_XXX[022]
Dev2_XXX[023]
Dev2_XXX[024]
Doc# E204701
DF1
Address
F11:049
F11:050
F11:051
F11:052
F11:053
F11:054
F11:055
F11:056
F11:057
F11:058
N14:000
N14:001
N14:002
N14:003
N14:004
N14:005
N14:006
N14:007
N14:008
N14:009
N14:010
N14:011
N14:012
N14:013
N14:014
N14:015
N14:016
N14:017
N14:018
N14:019
N14:020
N14:021
N14:022
N14:023
N14:024
LonName
nvoPWt24MxAv_XXX
nvoPVAR22MxA_XXX
nvoPVAR23MxA_XXX
nvoPVAR24MxA_XXX
nvoNWt22MxAv_XXX
nvoNWt23MxAv_XXX
nvoNWt24MxAv_XXX
nvoNVAR22MxA_XXX
nvoNVAR23MxA_XXX
nvoNVAR24MxA_XXX
nvoCTDen_XXX
nvoCTNum1_XXX
nvoCTNum2_XXX
nvoCTNum3_XXX
nvoCTNum4_XXX
nvoCTNum5_XXX
nvoCTNum6_XXX
nvoCTNum7_XXX
nvoCTNum8_XXX
nvoCTNum9_XXX
nvoCTNum10_XXX
nvoCTNum11_XXX
nvoCTNum12_XXX
nvoCTNum13_XXX
nvoCTNum14_XXX
nvoCTNum15_XXX
nvoCTNum16_XXX
nvoCTNum17_XXX
nvoCTNum18_XXX
nvoCTNum19_XXX
nvoCTNum20_XXX
nvoCTNum21_XXX
nvoCTNum22_XXX
nvoCTNum23_XXX
nvoCTNum24_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc_f
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
A-35
A: Protocol Data Points for EIG Meters
PointName
PTnumerator
PTdenominator
Hookup
SerialNumberReg1
SerialNumberReg2
SerialNumberReg3
SerialNumberReg4
SerialNumberReg5
SerialNumberReg6
SerialNumberReg7
SerialNumberReg8
PasswordforResetinuse
PasswordforConfigurationinuse
BACnet
Object
Type
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
BI
BI
BACnet
Object
ID
559
560
561
562
563
564
565
566
567
568
569
570
571
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
N2
Data
Type
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
N2
Point
Address
47
48
49
50
51
52
53
54
55
56
57
58
59
EIPTagName
Dev2_XXX[025]
Dev3_XXX[000]
Dev3_XXX[001]
Dev3_XXX[002]
Dev3_XXX[003]
Dev3_XXX[004]
Dev3_XXX[005]
Dev3_XXX[006]
Dev3_XXX[007]
Dev3_XXX[008]
Dev3_XXX[009]
Byt_XXX[0]
Byt_XXX[1]
Doc# E204701
DF1
Address
N14:025
N15:000
N15:001
N15:002
N15:003
N15:004
N15:005
N15:006
N15:007
N15:008
N15:009
N16:0
N16:1
LonName
nvoPTnum_XXX
nvoPTden_XXX
nvoHookup_XXX
nvoSerNum1_XXX
nvoSerNum2_XXX
nvoSerNum3_XXX
nvoSerNum4_XXX
nvoSerNum5_XXX
nvoSerNum6_XXX
nvoSerNum7_XXX
nvoSerNum8_XXX
nvoPswdReset_XXX
nvoPswdCnfg_XXX
LonSNVT
SNVT_count_inc_f
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
SNVT_count_inc
A-36
B: MAC Address DIP Switch Settings
B: MAC Address DIP Switch Settings
This following table lists the settings for the A Bank of DIP switches, used to set a
MAC address.
Address
A0
A1
A2
A3
A4
A5
A6
A7
0
Off
Off
Off
Off
Off
Off
Off
Off
1
On
Off
Off
Off
Off
Off
Off
Off
2
Off
On
Off
Off
Off
Off
Off
Off
3
On
On
Off
Off
Off
Off
Off
Off
4
Off
Off
On
Off
Off
Off
Off
Off
5
On
Off
On
Off
Off
Off
Off
Off
6
Off
On
On
Off
Off
Off
Off
Off
7
On
On
On
Off
Off
Off
Off
Off
8
Off
Off
Off
On
Off
Off
Off
Off
9
On
Off
Off
On
Off
Off
Off
Off
10
Off
On
Off
On
Off
Off
Off
Off
11
On
On
Off
On
Off
Off
Off
Off
12
Off
Off
On
On
Off
Off
Off
Off
13
On
Off
On
On
Off
Off
Off
Off
14
Off
On
On
On
Off
Off
Off
Off
15
On
On
On
On
Off
Off
Off
Off
16
Off
Off
Off
Off
On
Off
Off
Off
17
On
Off
Off
Off
On
Off
Off
Off
18
Off
On
Off
Off
On
Off
Off
Off
19
On
On
Off
Off
On
Off
Off
Off
20
Off
Off
On
Off
On
Off
Off
Off
21
On
Off
On
Off
On
Off
Off
Off
22
Off
On
On
Off
On
Off
Off
Off
23
On
On
On
Off
On
Off
Off
Off
24
Off
Off
Off
On
On
Off
Off
Off
25
On
Off
Off
On
On
Off
Off
Off
26
Off
On
Off
On
On
Off
Off
Off
Off
27
On
On
Off
On
On
Off
Off
28
Off
Off
On
On
On
Off
Off
Off
29
On
Off
On
On
On
Off
Off
Off
30
Off
On
On
On
On
Off
Off
Off
31
On
On
On
On
On
Off
Off
Off
32
Off
Off
Off
Off
Off
On
Off
Off
33
On
Off
Off
Off
Off
On
Off
Off
34
Off
On
Off
Off
Off
On
Off
Off
35
On
On
Off
Off
Off
On
Off
Off
36
Off
Off
On
Off
Off
On
Off
Off
37
On
Off
On
Off
Off
On
Off
Off
38
Off
On
On
Off
Off
On
Off
Off
39
On
On
On
Off
Off
On
Off
Off
40
Off
Off
Off
On
Off
On
Off
Off
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
B-1
B: MAC Address DIP Switch Settings
Address
A0
A1
A2
A3
A4
A5
A6
A7
41
On
Off
Off
On
Off
On
Off
Off
42
Off
On
Off
On
Off
On
Off
Off
43
On
On
Off
On
Off
On
Off
Off
44
Off
Off
On
On
Off
On
Off
Off
45
On
Off
On
On
Off
On
Off
Off
46
Off
On
On
On
Off
On
Off
Off
47
On
On
On
On
Off
On
Off
Off
48
Off
Off
Off
Off
On
On
Off
Off
49
On
Off
Off
Off
On
On
Off
Off
50
Off
On
Off
Off
On
On
Off
Off
51
On
On
Off
Off
On
On
Off
Off
52
Off
Off
On
Off
On
On
Off
Off
53
On
Off
On
Off
On
On
Off
Off
54
Off
On
On
Off
On
On
Off
Off
Off
55
On
On
On
Off
On
On
Off
56
Off
Off
Off
On
On
On
Off
Off
57
On
Off
Off
On
On
On
Off
Off
58
Off
On
Off
On
On
On
Off
Off
59
On
On
Off
On
On
On
Off
Off
60
Off
Off
On
On
On
On
Off
Off
61
On
Off
On
On
On
On
Off
Off
62
Off
On
On
On
On
On
Off
Off
63
On
On
On
On
On
On
Off
Off
64
Off
Off
Off
Off
Off
Off
On
Off
65
On
Off
Off
Off
Off
Off
On
Off
66
Off
On
Off
Off
Off
Off
On
Off
67
On
On
Off
Off
Off
Off
On
Off
68
Off
Off
On
Off
Off
Off
On
Off
69
On
Off
On
Off
Off
Off
On
Off
70
Off
On
On
Off
Off
Off
On
Off
71
On
On
On
Off
Off
Off
On
Off
72
Off
Off
Off
On
Off
Off
On
Off
73
On
Off
Off
On
Off
Off
On
Off
74
Off
On
Off
On
Off
Off
On
Off
Off
75
On
On
Off
On
Off
Off
On
76
Off
Off
On
On
Off
Off
On
Off
77
On
Off
On
On
Off
Off
On
Off
78
Off
On
On
On
Off
Off
On
Off
79
On
On
On
On
Off
Off
On
Off
80
Off
Off
Off
Off
On
Off
On
Off
81
On
Off
Off
Off
On
Off
On
Off
82
Off
On
Off
Off
On
Off
On
Off
83
On
On
Off
Off
On
Off
On
Off
84
Off
Off
On
Off
On
Off
On
Off
85
On
Off
On
Off
On
Off
On
Off
86
Off
On
On
Off
On
Off
On
Off
87
On
On
On
Off
On
Off
On
Off
88
Off
Off
Off
On
On
Off
On
Off
89
On
Off
Off
On
On
Off
On
Off
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
B-2
B: MAC Address DIP Switch Settings
Address
A0
A1
A2
A3
A4
A5
A6
A7
90
Off
On
Off
On
On
Off
On
Off
91
On
On
Off
On
On
Off
On
Off
92
Off
Off
On
On
On
Off
On
Off
93
On
Off
On
On
On
Off
On
Off
94
Off
On
On
On
On
Off
On
Off
95
On
On
On
On
On
Off
On
Off
96
Off
Off
Off
Off
Off
On
On
Off
97
On
Off
Off
Off
Off
On
On
Off
98
Off
On
Off
Off
Off
On
On
Off
99
On
On
Off
Off
Off
On
On
Off
100
Off
Off
On
Off
Off
On
On
Off
101
On
Off
On
Off
Off
On
On
Off
102
Off
On
On
Off
Off
On
On
Off
103
On
On
On
Off
Off
On
On
Off
104
Off
Off
Off
On
Off
On
On
Off
105
On
Off
Off
On
Off
On
On
Off
106
Off
On
Off
On
Off
On
On
Off
107
On
On
Off
On
Off
On
On
Off
108
Off
Off
On
On
Off
On
On
Off
109
On
Off
On
On
Off
On
On
Off
110
Off
On
On
On
Off
On
On
Off
111
On
On
On
On
Off
On
On
Off
112
Off
Off
Off
Off
On
On
On
Off
113
On
Off
Off
Off
On
On
On
Off
114
Off
On
Off
Off
On
On
On
Off
115
On
On
Off
Off
On
On
On
Off
116
Off
Off
On
Off
On
On
On
Off
117
On
Off
On
Off
On
On
On
Off
118
Off
On
On
Off
On
On
On
Off
119
On
On
On
Off
On
On
On
Off
120
Off
Off
Off
On
On
On
On
Off
121
On
Off
Off
On
On
On
On
Off
122
Off
On
Off
On
On
On
On
Off
123
On
On
Off
On
On
On
On
Off
124
Off
Off
On
On
On
On
On
Off
125
On
Off
On
On
On
On
On
Off
126
Off
On
On
On
On
On
On
Off
Off
127
On
On
On
On
On
On
On
128
Off
Off
Off
Off
Off
Off
Off
On
129
On
Off
Off
Off
Off
Off
Off
On
130
Off
On
Off
Off
Off
Off
Off
On
131
On
On
Off
Off
Off
Off
Off
On
132
Off
Off
On
Off
Off
Off
Off
On
133
On
Off
On
Off
Off
Off
Off
On
134
Off
On
On
Off
Off
Off
Off
On
135
On
On
On
Off
Off
Off
Off
On
136
Off
Off
Off
On
Off
Off
Off
On
137
On
Off
Off
On
Off
Off
Off
On
138
Off
On
Off
On
Off
Off
Off
On
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
B-3
B: MAC Address DIP Switch Settings
Address
A0
A1
A2
A3
A4
A5
A6
A7
139
On
On
Off
On
Off
Off
Off
On
140
Off
Off
On
On
Off
Off
Off
On
141
On
Off
On
On
Off
Off
Off
On
142
Off
On
On
On
Off
Off
Off
On
143
On
On
On
On
Off
Off
Off
On
144
Off
Off
Off
Off
On
Off
Off
On
145
On
Off
Off
Off
On
Off
Off
On
146
Off
On
Off
Off
On
Off
Off
On
On
147
On
On
Off
Off
On
Off
Off
148
Off
Off
On
Off
On
Off
Off
On
149
On
Off
On
Off
On
Off
Off
On
150
Off
On
On
Off
On
Off
Off
On
151
On
On
On
Off
On
Off
Off
On
152
Off
Off
Off
On
On
Off
Off
On
153
On
Off
Off
On
On
Off
Off
On
154
Off
On
Off
On
On
Off
Off
On
155
On
On
Off
On
On
Off
Off
On
156
Off
Off
On
On
On
Off
Off
On
157
On
Off
On
On
On
Off
Off
On
158
Off
On
On
On
On
Off
Off
On
On
159
On
On
On
On
On
Off
Off
160
Off
Off
Off
Off
Off
On
Off
On
161
On
Off
Off
Off
Off
On
Off
On
162
Off
On
Off
Off
Off
On
Off
On
163
On
On
Off
Off
Off
On
Off
On
164
Off
Off
On
Off
Off
On
Off
On
165
On
Off
On
Off
Off
On
Off
On
166
Off
On
On
Off
Off
On
Off
On
167
On
On
On
Off
Off
On
Off
On
168
Off
Off
Off
On
Off
On
Off
On
169
On
Off
Off
On
Off
On
Off
On
170
Off
On
Off
On
Off
On
Off
On
171
On
On
Off
On
Off
On
Off
On
172
Off
Off
On
On
Off
On
Off
On
173
On
Off
On
On
Off
On
Off
On
174
Off
On
On
On
Off
On
Off
On
175
On
On
On
On
Off
On
Off
On
176
Off
Off
Off
Off
On
On
Off
On
177
On
Off
Off
Off
On
On
Off
On
178
Off
On
Off
Off
On
On
Off
On
179
On
On
Off
Off
On
On
Off
On
180
Off
Off
On
Off
On
On
Off
On
181
On
Off
On
Off
On
On
Off
On
182
Off
On
On
Off
On
On
Off
On
183
On
On
On
Off
On
On
Off
On
184
Off
Off
Off
On
On
On
Off
On
185
On
Off
Off
On
On
On
Off
On
186
Off
On
Off
On
On
On
Off
On
187
On
On
Off
On
On
On
Off
On
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
B-4
B: MAC Address DIP Switch Settings
Address
A0
A1
A2
A3
A4
A5
A6
A7
188
Off
Off
On
On
On
On
Off
On
189
On
Off
On
On
On
On
Off
On
190
Off
On
On
On
On
On
Off
On
191
On
On
On
On
On
On
Off
On
192
Off
Off
Off
Off
Off
Off
On
On
193
On
Off
Off
Off
Off
Off
On
On
194
Off
On
Off
Off
Off
Off
On
On
195
On
On
Off
Off
Off
Off
On
On
196
Off
Off
On
Off
Off
Off
On
On
197
On
Off
On
Off
Off
Off
On
On
198
Off
On
On
Off
Off
Off
On
On
199
On
On
On
Off
Off
Off
On
On
200
Off
Off
Off
On
Off
Off
On
On
201
On
Off
Off
On
Off
Off
On
On
202
Off
On
Off
On
Off
Off
On
On
203
On
On
Off
On
Off
Off
On
On
204
Off
Off
On
On
Off
Off
On
On
205
On
Off
On
On
Off
Off
On
On
206
Off
On
On
On
Off
Off
On
On
207
On
On
On
On
Off
Off
On
On
208
Off
Off
Off
Off
On
Off
On
On
209
On
Off
Off
Off
On
Off
On
On
210
Off
On
Off
Off
On
Off
On
On
211
On
On
Off
Off
On
Off
On
On
212
Off
Off
On
Off
On
Off
On
On
213
On
Off
On
Off
On
Off
On
On
214
Off
On
On
Off
On
Off
On
On
215
On
On
On
Off
On
Off
On
On
216
Off
Off
Off
On
On
Off
On
On
217
On
Off
Off
On
On
Off
On
On
218
Off
On
Off
On
On
Off
On
On
On
219
On
On
Off
On
On
Off
On
220
Off
Off
On
On
On
Off
On
On
221
On
Off
On
On
On
Off
On
On
222
Off
On
On
On
On
Off
On
On
223
On
On
On
On
On
Off
On
On
224
Off
Off
Off
Off
Off
On
On
On
225
On
Off
Off
Off
Off
On
On
On
226
Off
On
Off
Off
Off
On
On
On
227
On
On
Off
Off
Off
On
On
On
228
Off
Off
On
Off
Off
On
On
On
229
On
Off
On
Off
Off
On
On
On
230
Off
On
On
Off
Off
On
On
On
231
On
On
On
Off
Off
On
On
On
232
Off
Off
Off
On
Off
On
On
On
233
On
Off
Off
On
Off
On
On
On
234
Off
On
Off
On
Off
On
On
On
235
On
On
Off
On
Off
On
On
On
236
Off
Off
On
On
Off
On
On
On
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Doc#
E204701
B-5
B: MAC Address DIP Switch Settings
Address
A0
A1
A2
A3
A4
A5
A6
A7
237
On
Off
On
On
Off
On
On
On
238
Off
On
On
On
Off
On
On
On
239
On
On
On
On
Off
On
On
On
240
Off
Off
Off
Off
On
On
On
On
241
On
Off
Off
Off
On
On
On
On
242
Off
On
Off
Off
On
On
On
On
243
On
On
Off
Off
On
On
On
On
244
Off
Off
On
Off
On
On
On
On
245
On
Off
On
Off
On
On
On
On
246
Off
On
On
Off
On
On
On
On
247
On
On
On
Off
On
On
On
On
248
Off
Off
Off
On
On
On
On
On
249
On
Off
Off
On
On
On
On
On
250
Off
On
Off
On
On
On
On
On
251
On
On
Off
On
On
On
On
On
252
Off
Off
On
On
On
On
On
On
253
On
Off
On
On
On
On
On
On
254
Off
On
On
On
On
On
On
On
255
On
On
On
On
On
On
On
On