F02
Running/Stopping and Rotational Direction
Selects a source issuing a run command--keypad or external control signal input.
- If F02 = 0, 2, or 3, the inverter can run the motor by the
and
keys on the
built-in keypad. The motor rotational direction can be specified in two ways,
either by control signal input (F02 = 0) or by use of prefixed forward or reverse
rotation (F02 = 2 or 3).
When F02 = 0, to specify the motor rotational direction by control signal input,
assign the commands (FWD) and (REV) to terminals [FWD] and [REV],
respectively. Turn on the (FWD) or (REV) for the forward or reverse direction,
respectively, and then press the
key to run the motor.
- If F02 = 1, the inverter can run the motor by control signal inputs. To specify the
motor rotational direction, assign the commands (FWD) and (REV) to terminals
[FWD] and [REV], respectively. Turn on the (FWD) or (REV) for the forward or
reverse direction, respectively. If both of (FWD) and (REV) are turned on
simultaneously, the inverter immediately decelerates to stop the motor.
The table below lists the operational relationship between function code F02
and
key operation, and
(Running/Stopping and Rotational Direction), the
control signal inputs to terminals [FWD] and [REV], which determines the rotational
direction.
Function
Key on the
code F02:
keypad
key
0
key
1
Ignored.
2 (forward/
fixed)
key
3
(reverse/
fixed)
key
Control signal inputs to
terminals [FWD] and [REV]
Motor
rotational
direction
Function code E98
(FWD) command
Function code E99
(REV) command
OFF
OFF
Stop
ON
OFF
Forward
OFF
ON
Reverse
ON
ON
Stop
OFF
OFF
ON
OFF
OFF
ON
Stop
ON
ON
OFF
OFF
Stop
ON
OFF
Forward
OFF
ON
Reverse
ON
ON
Ignored.
key
Stop
Forward
Stop
Reverse
Ignored.
key
5-14
Stop