SY210NT Serial Controller
Operation Manual
Version 2.3
© 2005 by SYRIS Technology Corp.
1
User Manual
Item Content
1.
2.
3.
4.
5.
Introduction
1.1
SYNT Serial Product
1.2
System Configuration
Wiring Connection
2.1
Controller to PC
2.2
Controller to Card Reader
2.3
Controller to Other Module
System Setup
3.1
Power Up Procedures
3.2
System Setting
3.3
PCB Layout of Typical SY210NT Controller
Programming
4.1
Set Controller Date / Time
4.2
Card Process
4.3
Set DI Parameter
4.4
DO Parameter Setting
4.5
Anti-PassBack Setting
4.6
Set Door Lock-Release Time
4.7
Set Timer, TimeZone, Holiday TimeZone
4.8
Set Application Set [APPSET]
4.9
Set Flow Process
4.10 Flow Chart
4.11 Typical Wiring Connection
Technical Information
5.1
SY210NT Controller Specification
5.2
SYWIN95A Access Control Software
5.3
SYRIS Proximity Reader
5.4
Proximity Card
5.5
Power Consumption
2
1. Introduction
1.1
SY210NT Series Product
1.
SY210NT2/NT4 Card Access Controller
2.
SYRDS1/L5… Card Reader
3.
MDDIDO Input/Output Module
4.
Printer Interface Module
5.
Proximity Card
6.
Other Application Module
1.2
System Configuration
Figure 1.1 System Configuration
3
2. Wiring Connection
Type Of Connection
a. Controller to Personal Computer
b. Controller to Card Reader
c. Controller to Extension Module
d. Input/Output Contact Build in Controller
Detail Connection as follow :
2.1
Controller To PC
Controller link to PC by RS485 Communication module, Maximum distance from PC to Controller is 1
KM. A single
Controller M4 Connector
SYLINK Connector
PIN 1 4A -, Blue Color
PIN 3 Green Color
PIN 2 4A+, Purple Color PIN 2 Yellow Color
PIN 5 GND, Black Color PIN 1 Black Color
SY210NT
Main PCB
Board
Computer
PIN 3 4APIN 2 4A+
PIN 1 GND
PIN1
PIN 2
PIN 5
Figure 2.1 Connection from SY210NT to PC
Caution : RS485 Communication Wire must be Twisted Screen Cable, grade AWG18~24 depend on
distance.
4
2.3
Controller to Other Module
2.3.1
MDDIDO Module
DIDO Module consist of :
a. Power Supply …… DC : 5 ~ 12 V
b. RS485 Line ….. Link to Controller 4R+, 4Rc. DO Ouput ….. 4DO, 8DO, 16DO
d. DI Input ….. 4DI, 8DI,16DI
DO … Dry Contact Output
DI … Dry Contact Input
Stalus indicate LED : LED 1 ~ 4 --- DO Output
LED 5 ~ 8 --- DI Input
LED 9 ---RS485 (Blinking)
Figure 2.3.1 DI4Do4 Module Connection
Please contact factory for other DIDO Module wiring connection.
6
2.3.2
Printer Module
SY200NT Controller can connect to the following printers directly or reports printing via printer module.
1. Do-Metrics Printers
2. Inkjet Printers
3. Laser Printers
Figure 2.3.2 Connection of Printer Module
2.3.3
AI Module
Please contact factory for AI Module Connection.
7
3. System Setup
3.1 Power up procedures
3.1.1
3.1.2
3.1.3
Before power up, ensure all wiring connection is correct.
When the power is turned on, the controller will automatically initialize and the LED change from
Green to Red with a short Beep sound.
If the controller is ready, LCD will show Date/Time.
3.2 System Setting
3.2.1
Go to program mode
Follow Figure 3.2.1 to go to program mode.
Figure 3.2.1 How to Go to Program Mode
98/01/06
TUE13:10
System
Press MENU Key
Password
________
Login
Press EN Key
Press EN Key
Login OK
press CLR key
2 times to return
System main
screen
Keyin 1234
Then Press EN
Master
Ok
You are in program mode now.
8
3.2.4
Get Card Reader Link to Controller
The linking of card reader to controller is not completed until the following step is done.
Figure 3.2.4 Module Plug & Play
System
Module
Process
Press EN Key, Press
to Select [Module Process]
3.2.5
Module
PlugPlay
Press EN Key, Press
to Select [Module PlugPlay]
Module
Watting.
Auto-detect
Module
Ok
Store Cards I Controller
Upon completion of System Setting, it is important to store all user cards in the controller. The produces
is shown as below:
Figure 3.2.5 Store Cards in Controller
Card
Add Card
Process
Press EN Key, Press
to Select [Add Card Process]
Add Card
BySerial
Ins Card
Flash a card
Press EN Key, Press
to Select [Add Card
By Serial]
Ins Card
[0001]
continus flashing cards
to automatically add
3.2.6
Confirmation for Systems Set Up
a. The systems set up is completed after going through above steps 3.2.1 to 3.2.5.
b. Press [CLR] repeatly until the LCD of controller show Date & Time.
c. To confirm that the systems is properly set up, flash any of the cards previously stored in the
controller to mak sure the "OK" LED lighted and the LCD show card serial number.
10
3.3 PCB Layout of typical SY210NT Controller
3.3.1
The PCB layout of SY210NT controller
Door 2 Output
Relay 2
Door 1 Output
Relay 1
Power
Supply
Door 4 Output
Relay 4
Door 3 Output
Relay 3
DC0V
DC+12V
Relay Output
NV Input
Network Connect
5V Output
4R+ WHT or Yellow
Pin3: 4A-
4R- GRN
RS485
Pin2: 4A+
Connector
Pin1: GND
To other Reader or Module
To other Controller
Figure 3.3.1 The PCB Layout of SY210NT Controller
11
3.3.2
The following setting is fixed by the systems
Card Reader ID
Reader ID = 1 (Door 1 Entry) or 5 (Door 1
Exit)
Reader ID = 2 (Door 2 Entry) or 6 (Door 2
Exit)
Reader ID = 3 (Door 3 Entry) or 7 (Door 3
Exit)
Reader ID = 4 (Door 4 Entry) or 8 (Door 4
Exit)
Controller Output
Relay 1
Relay 2
Relay 3
Relay 4
Reader ID "1" is for Door 1 Entry Reader, likewise ID "2" is for Door 2 Entry Reader, and similar to ID
"3" and ID "4"
Reader ID "5", "6", "7" and "8" are for Door "1", "2", "3" and "4" Exit Reader.
12
4
Programming
4.1
Set Controller Date / Time
4.1.1
Set Time
System
Press EN Key Then Press
to Select [Change Time]
Change
Time
Press EN Key Then Keyin Time
HH:MM:SS
Figure 4.1.1 Set Time
4.1.2
Set Date
Figure 4.1.2 Set Data
13
4.2
Card Process
4.2.1
Store Card to Controller
a.
b.
Logon in Controller Program Mode
Store Card Procedures
Card
EN
Add Card
Process
Add Card
EN
Operation Proceducer
EN
Press EN to
enter
Page Up/Down
EN
Press En to
Enter
Add Card
BySerial
Add Card in sequence
EN
Add Card
ByNo.
EN
Ins Card
EN
EN
Add Card by
Serial No.
Flash Card in
sequence
CLR
Flash Card
Add Card
No:_ _ _
Ins Card
EN
Key in serial
No.
CLR
Flash a card
Function Key
Page Down
MENU
Function Menu
EN
Enter Key
CLR
Escape to Previous Menu
0 ~ 9
FUN
Number Key
Shift Key
Page Up
Figure 4.2.1 Store Card
14
4.2.2
Delete card from Controller
a.
b.
Logon in Controller Program Mode
Delete Card Procedures
Card
EN
Del Card
ByNo.
Del Card
Process
Del card
DEl by Serial No.
EN
Delete
All Card
Del All cards
EN
Operation Proceducer
EN
Press EN to
enter
Page Up/Down
EN
Press En to
Enter
Del Card
No:_ _ _
_
EN
key in serial No.
Delete
[No/Yes]
EN
select Yes
Delete One Card
EN
CLR
Delete All Card
EN
CLR
EN
Function Key
Page Down
MENU
Function Menu
EN
Enter Key
CLR
0 ~ 9
Escape to Previous Menu
FUN
Number Key
Shift Key
Page Up
Figure 4.2.2 Delete Card
15
4.2.3
Modify Card Data
a.
b.
Logon in Controller Program Mode
Modify Card Procedure
Card
Status
Setting
EN
EN
Card status
APP
Setting
EN
Modify
One Card
Edit Card data
EN
Card No.
No:_ _ _
EN
App set
Key in No.
EN
EN
PIN
Setting
EN
Pin setting
APB
Setting
EN
Press EN to
enter
Page Up/Down
EN
Press En to
Enter
EN CLR
Enable/Disable
Setting
Set:[ _ _ ]
EN
CLR
App 01~16
PIN Set
[No/Yes]
EN
card APB setting
Operation Proceducer
Card
[Enable/
Disable]
Card+Pin
Enable/Disable
Check
APB
[No/Yes]
EN
PIN Set
PIN:_ _ _
EN CLR
Define Pin
EN CLR
APB check
Function Key
Page Down
MENU
Function Menu
EN
Enter Key
CLR
0 ~ 9
Escape to Previous Menu
FUN
Number Key
Shift Key
Page Up
Figure 4.2.3 Modify Card Data
16
4.2.4
Show Card Number
Card Code Numbers --- Fix Internal Number
Card Serial Numbers --- Depend on programming Sequence
a.
Logon in Controller Mode
b.
Show Card Number Procedures
Show Card
Card No.
Card
Show Card
Process
Figure 4.2.4 Show Card Number
17
4.3
Set DI Parameter
4.3.1
DI Holiday Time Zone Setting
a.
b.
c.
Set
DISet
Logon in Controller Program Mode
Go to [Time Zone] Menu, Select [Set DI Set]
Programming Produces
EN
DiSet:
___
EN
Key in DI
No.
(1~8)
DiSet
HodayTZ
Set DI
Holiday TZ
Holday:
___
EN
EN
Key in Holiday No.
EN
Operation Proceducer
EN
Press EN to
enter
Page Up/Down
EN
Press En to
Enter
Holday:
_<_ _>_
Key in TZ No.
Before Holiday
Holiday
After Holiday
Function Key
Page Down
MENU
Function Menu
EN
Enter Key
CLR
Escape to Previous Menu
0 ~ 9
FUN
Number Key
Shift Key
Page Up
Figure 4.3.1 Set DI Holiday Time Zone
18
4.3.2
Set DI Week Time Zone
a. Logon in Controller Program Mode
b. Go to [Time Zone] Menu, Select [Set DI Set]
c. Programming Produces
Set
DISet
EN
DiSet:
___
EN
Key in DI
No.
(1~8)
DiSet
WeekTZ
Set DI
Week TZ
EN
WeekTZ:
___
Key Week No.
(1~7)
EN
WeekTZ:_
TZ:[ _ _ ]
Key in TZ
EN
Operation Proceducer
EN
Press EN to
enter
Page Up/Down
EN
Press En to
Enter
Function Key
MENU
EN
CLR
Page Down
Function Menu
0 ~ 9
Enter Key
Escape to Previous Menu
FUN
Number Key
Shift Key
Page Up
Figure 4.3.2 Set DI Week Time Zone
19
4.3.3
Set DI Action Status
a. Logon in Controller Program Mode
b. Go to [Time Zone] Menu, Select [Set DI Set]
c. Programming Produces
Set
DISet
EN
DiSet:
___
Key in DI
No.
(1~8)
EN
DiSet
Module
Set DI Input
EN
Operation Proceducer
EN
Press EN to
enter
Page Up/Down
EN
Press En to
Enter
EN
Module:
___
EN
Module:_
[Disable][Enable]
Enable/Disable
Value:
1:DI ON, Action
2:DI OFF, Action
3:DI Float, Action
4:DI Change, Action
Function Key
Page Down
MENU
Function Menu
EN
Enter Key
CLR
0 ~ 9
Escape to Previous Menu
FUN
Number Key
Shift Key
Page Up
Figure 4.3.3 Set DI Action Status
20
4.4.2
Set DO Week Time Zone
a. Logon in Controller Program Mode
b. Go to [Time Zone] Menu, Select [Set DO Set]
c. Programming Produces
Set
DOSet
EN
DoSet:
___
EN
Key in DO
No.
(01~16)
DoSet
WeekTZ
Set DO
Week TZ
EN
WeekTZ:
___
Key in Week No.
(1~7)
EN
WeekTZ:_
TZ:[ _ _ ]
Key in TZ No.
EN
Operation Proceducer
EN
Press EN to
enter
Page Up/Down
EN
Press En to
Enter
Function Key
Page Down
MENU
Function Menu
EN
Enter Key
CLR
0 ~ 9
Escape to Previous Menu
FUN
Number Key
Shift Key
Page Up
Figure 4.4.2 Set DO Week Time Zone
22
4.4.3 Set DO Action Status
a. Logon in Controller Program Mode
b. Go to [Time Zone] Menu, Select [Set DO Set]
c. Programming Produces
Set
DOSet
EN
DoSet:
___
Key in DO
No.
(01~16)
EN
DoSet
SetType
Set Action Type
EN
EN
Operation Proceducer
EN
Press EN to
enter
Page Up/Down
EN
Press En to
Enter
SetType
Type:[ _ ]
Action Typr:
0: Not use
1: Always
2: by Min
Function Key
Page Down
MENU
Function Menu
EN
Enter Key
CLR
0 ~ 9
Escape to Previous Menu
FUN
Number Key
Shift Key
Page Up
Figure 4.4.3 Set DO Action Status
23
Anti-Passback Setting
4.4.2
Set APB for Individual Door
a.
b.
System Provide 3-Class APB Level
Programming Procedures
System
EN
System
Process
EN
EN
APBLevel
Setting
APB CLASS
APBLevel
>_-_-_-_
EN
AREA:1_ 2 _3 _ 4_
KEY IN 0 1 2 3
SET APB CHECK
LEVEL
0:IGNORE
EN
1:LEVEL 1
2:LEVEL 2
3:LEVEL 3
EN
Figure 4.5.1 Anti-Passback Setting
4.4.3
Set APB for Individual Card
a.
b.
c.
Program only for those cards required APB
Logon in Controller Program Mode
Program Procedures
Card
EN
Modify
One Card
Edit Card
EN
EN
Card No.
No:_ _ _
EN
Key In Card
No
APB
Setting
EN
Check APB
[No/Yes]
EN
Yes/No
Set APB
EN
Figure 4.5.2 Set Card APB
24
4.5
Set Door Lock-Release Time
a.
b.
c.
SY200NT controller will send a signal output to release the lock (Relay 1 to 4) if a valid
card is read. The setting is to determine how long you want the lock to remain open.
Logon in Controller Program Mode.
Program Procedures
Figure 4.6 Set Door Lock-Release Time
4.6
Set Timer, TimeZone, Holiday TimeZone
4.6.1
Set Timer
a.
A Total of 30 Timers may be programmed. The
25
4.6.2
Set TimeZone
a.
b.
c.
d.
A Total of 60 TimeZone may be programmed. Each with 3 sets of timers
TimeZone is important and used in access control and DIDO programming etc
Logon in Controller Program Mode
Programming Procedures
Figure 4.7.2 Set TimeZone
TimeZone
EN
Timer
Table
Timer setting
Timer: _ _
EN
Timer No.
EN
Timer: _ _
Start_ _:_ _
Start Time
EN
Timer: _ _
End_ _:_ _
End Time
EN
01~30
EN
4.6.3
Set Holiday TimeZone
a. Holiday access control include : Holiday Eve, Holiday and day after Holiday
b. To define Holiday Access Control, must go to TimeZone] Menu, select [APPSET] to set
[Holiday TimeZone] first
c. A total of 8 Holiday TimeZone may be set
d. Programming procedures
Figure 4.7.3 Set Holiday TimeZone
TimeZone
EN
Timer
Table
Timer setting
Timer: _ _
EN
Timer No.
EN
Timer: _ _
Start_ _:_ _
Start Time
EN
Timer: _ _
End_ _:_ _
End Time
01~30
EN
26
EN
4.7
Set Application Set [APPSET]
APPSET Setting List
a.
b.
c.
d.
e.
f.
Edit Holiday TimeZone
Edit Weekly TimeZone
Set Out Flag (Exit control)
Set Door Flag (Door Access Control)
Set Security PIN Code (Common PIN)
Set Personal PIN Code (APP Group PIN)
APP Set Flow Chart
EN
TimeZone
Set
APPset
EN
EN
Set APPSet
Data
EN
Set:[ _ _ ]
Set AppSet No. ( 01~16 )
EN
APPSet
Hoday TZ
APPSet
WeekTZ
APPSet
OutFlag
APPSet
DoorFlag
APPSet
Security
Personal
Set Holiday TZ
Se Week TZ
Set OutFlag
Set DoorFlag
Set Security
PIN Code
Set Personal
PIN
APPSet
Figure 4.8 APP set Flow Chart
27
4.7.1
Set Holiday TimeZone
a.
The Controller Provides 8 Group of Holiday TimeZone, Date include Holiday Eve,
Holiday and day after Holiday
Logon in Controller Program Mode
Programming Procedures
Figure 4.8.1 Set Holiday TimeZone
b.
c.
Set
APPSet
EN
Set:[ _ _ ]
EN
APPSet
HoldayTZ
Holday:_
EN
Set Holiday TZ
Set APPSet No.
(1~16 )
EN
Set Holiday No.
(1~8 )
EN
4.7.2
Holday:_
_ _<_ _>_ _
Holday:_
O[ _<_>_ ]
EN
EN
Set Holiday Exit
Control
0:No, 1:Yes
Key in TZ for:
Holiday Eve
Holiday
day After Holiday
Set Weekly TimeZone
a.
b.
c.
To set Daily TimeZone and within a week
Logon in Controller Program Mode
Programming Produces
Figure 4.8.2 Set Weekly TimeZone
Set
APPSet
EN
Set:[ _ _ ]
EN
APPSet
HoldayTZ
Set Holiday TZ
Set APPSet No.
(1~16 )
EN
Holday:_
EN
EN
Set Holiday No.
(1~8 )
Holday:_
_ _<_ _>_ _
Key in TZ for:
Holiday Eve
Holiday
day After Holiday
EN
Holday:_
O[ _<_>_ ]
Set Holiday Exit
Control
0:Yes, 1:Nol
28
EN
4.7.5
Set Security PIN Code
a.
b.
c.
The function may be used to set Card + PIN (Common PIN)
Logon in Controller Program Mode
Programming Procedures
Figure 4.8.5 Set Security PIN Code
Set
APPSet
EN
Set:[ _ _ ]
EN
APPSet
HoldayTZ
Holday:_
EN
Set Holiday TZ
Set APPSet No.
(1~16 )
EN
Set Holiday No.
(1~8 )
EN
Holday:_
O[ _<_>_ ]
EN
Set Holiday Exit
Control
0:No, 1:Yes
Key in TZ for:
Holiday Eve
Holiday
day After Holiday
EN
4.7.6
Holday:_
_ _<_ _>_ _
Set Personal PIN Code
a.
b.
c.
The function may be used to set Card + PIN (Personal PIN)
Logon in Controller Program Mode
Programming Procedures
Figure 4.8.6 Set Personal PIN Code
Set
APPSet
EN
Set:[ _ _ ]
EN
APPSet
HoldayTZ
Set Holiday TZ
Set APPSet No.
(1~16 )
EN
Holday:_
EN
EN
Set Holiday No.
(1~8 )
Holday:_
_ _<_ _>_ _
Key in TZ for:
Holiday Eve
Holiday
day After Holiday
EN
Holday:_
O[ _<_>_ ]
Set Holiday Exit
Control
0:No, 1:Yes
30
EN
Set Flow Process
SY200NT Controller Provide:
A Total of 26 Events for detection
A Total of 11 Actions for Execute
SY200NT will work depending on following sequence:
Source (Detecting Events)
Target (Action)
Mode (Action Mode)
Event Table
Ite
m
Event Function
Description
ID (0-9)
Channel (0 -60)
31
15
DI Float
16
DI Change Status
17
DI Set On
9 :
SY200NT
1-8 :
MDDIDO
9 :
SY200NT
1-8 :
MDDIDO
9 :
SY200NT
1-4 DI Point
18
DI Set Off
1-4 DI Point
19
DI Set Float
1-4 DI Point
20
DI Set Change
1-4 DI Point
21
DO Set On
None
22
DO Set Off
None
23
Time Out
None
24
Forced
None
25
Duress
None
26
HardWare Error
None
1-16 DI Point
0-99
Seconds
1-16 DI Point
None
1-4 TimeZone
Number
1-4 TimeZone
Number
1-4 TimeZone
Number
1-4 TimeZone
Number
1-60 TimeZone
Number
1-60 TimeZone
Number
1-60 TimeZone
Number
1-60 TimeZone
Number
1-60 TimeZone
Number
Module No =
1-20
59
SY200NT
60 ALL
None
None
None
None
None
None
0-99
Seconds
0-99
Seconds
None
None
Action Table
Item
Event
Function
1
SY200NT
2
Set Sound
3
Set Alarm
Sound
4
Set
Description
ID(0-9)
LED Code
1 : Ok LED
2 : Error Led
3 : Set up LED
4 : Active LED
5 : BlackLight LED
Sound Code
1 : Beep sound
2 : Do Sound
Alarm Code
1 : Steal
2 : Emergency
3 : Fire Alarm
4 : Gas
5 : Error
6 : Duress
DO Action
Channel(0-60)
Method(04)
1 : always
2 : 100ms
3 : sec
4 : min
LED Color
1 : Dark (Blacklight Off)
2 : Red ((Blacklight On)
3 : Green
4 : Orange
DO Point 1-4 :
32
Time
(1-999)
1 : always
2 : 100ms
3 : sec
4 : min
1 : always
2 : 100ms
3 : sec
4 : min
Time
(1-999)
1 : always
Time
Time
(1-999)
5
System
Internal
DO
Set DIDO
Module
DO Point
On
1 : Open
2 : Close
3 : Change
DIDO Module ID
1-8
Door 1-4
2 : 100ms
3 : sec
4 : min
1 : always
2 : 100ms
3 : sec
4 : min
DO Point 1-16
33
(1-999)
Time
(1-999)
Default Flow Control Setting
No
Event
IDEvent
1
2
3
4
Card Sense
In Check Ok
In Check Ok
In Check Ok
All Module
All Module
All Module
All Module
Check Card
LED
Sound
Show Data
Ok LED
Beep
SY200
5
6
7
8
In Check Ok
Out Check Ok
Out Check Ok
Out Check Ok
All Module
All Module
All Module
All Module
Add InOut
LED
Sound
Show Data
Ok LED
Beep
SY200
9
10
Out Check Ok All Module
Invalid Card All Module
Add InOut
LED
Chanel
Event
Action
IDAction Chanel Method Time
Action
Error
LED
Bell
SY200
11
12
Invalid Card
Invalid Card
All Module
All Module
Sound
Show Data
13
14
Invalid Card
Disable Card
All Module
All Module
Add InOut
LED
15
16
Disable Card
Disable Card
All Module
All Module
Sound
Show Data
17
18
Disable Card
Invalid
TimeZone
Invalid
TimeZone
Invalid
TimeZone
All Module
All Module
Add InOut
LED
All Module
Sound
Error
LED
Bell
All Module
Show Data
All Module
Add InOut
22
Invalid
TimeZone
Invalid Door
All Module
LED
23
24
Invalid Door
Invalid Door
All Module
All Module
Sound
Show Data
25
26
Invalid Door
Invalid
ReEntry
Invalid
ReEntry
Invalid
ReEntry
All Module
All Module
Add InOut
LED
All Module
Sound
Error
LED
Bell
All Module
Show Data
SY200
Add InOut
30
Invalid
All Module
ReEntry
Invalid ReExit All Module
31
32
Invalid ReExit All Module
Invalid ReExit All Module
Sound
Show Data
33
34
Invalid ReExit All Module
Card Sense All Module
Add InOut
LED
19
20
21
27
28
29
LED
Error
LED
Bell
SY200
Green
Second
2
Card
Second
Find No
2
Green
Second
2
Card
Second
Find No
2
Red
Second
2
Invalid
Card
Second
2
Red
Second
2
Disable Second
Card
2
Second
2
SY200
Invalid Second
TimeZo
ne
2
Error
LED
Bell
SY200
Red(2)
Second
2
Invalid Second
Door (5)
2
Error
LED
Bell
SY200
Active
LED
Red
Red(2)
Second
2
Invalid Second
ReEntry
(8)
2
Red
Second
2
Invalid
ReExit
Second
2
Red
Second
2
35
36
Flow Control Instruction
Following is a example of flow control after it sense a card.
No
Event
IDEvent
Chanel
Event
Action
IDAction Chanel Method Time
Action
34
1
2
3
4
Card Sense
In Check Ok
In Check Ok
In Check Ok
All Module
All Module
All Module
All Module
Check Card
LED
Sound
Show Data
5
In Check Ok
All Module
Add InOut
Ok LED
Beep
SY200
Green
Second
2
Card
Second
Find No
2
No. 1 Ask all module (reader) of controller to read card and ask controller to check card status.
No. 2 When In Check OK, (reader ID=1, entry reader) the OK LED of controller will changes to green
color and active for 2 seconds.
No. 3 When In Check OK, controller will create a Beep sound.
No. 4 When In Check OK, the controller LCD will show card serial number and it will active for 2
seconds.
No. 5 When in Check OK, controller will add a record to InOut transaction data base.
35
When the controller is "In Check OK" (Valid Card), it will active the output relay where the card is read.
Following is a example of flow control using DI Point for exit button.
No
Event
37
DI On
Flow
Process
IDEvent ChanelE
vent
9
1
Add Flow
Control
Action
SY200 DO
IDAction ChanelAction
Open
1
Method
Time
3
3
Event
Setting
As above setting table:
Event = DI On : Ask controller active when DI Point is On.
Event ID = 9 : the DI Point come from SY200NT internal DI.
Chanel Event = 1 : DI Point is the first one.
Action = SY200 DO : setting SY200 DO is for action point.
IDAction = Open : set action is open.
ChanelAction = 1 : output is come from DO1
Method = 3 : active time is in second
Time = 3 : output active 3 seconds
Program Procedures for above
36
4.10 Flowchart
98/01/08
Thu17:05
System
SYRIS
SY200NT4
Login
Password
_______
Master
Ok
Login
37
Flowchart continue
System
Previous
page
Message
Process
Press
or
EN
Idle
Screen
Press
or
EN
Change
Time
Press
or
EN
Change
Date
Press
or
EN
Software
Reset
Press
or
EN
Show OS
Version
Press
or
EN
Alarm
Test
Press
or
EN
Login
Press
or
EN
Logout
38
4.11 Typical Wiring Connection
39
5
Technical Information
5.1
SY210NT Controller Specification
SY210NT Controller Specification
Items / Spec
Number of Cards
Number of Readers
Door Control
Reader Technologies
User P.I.N. code
Input Points
Control relay Output
Communication ports
Baud rate
Programmable time zone
Group (application set)
Holidays
Controller ID
Expand modules
Anti-passback
Keypad input
Keypad backlight
LCD display
Speaker output
Indicator
Operating temperature
Storage temperature
Power supply input
Power consumption
Dimensions (mm)
5.2
SY210NT2
9,999
4 (2In,2Out)
4
SYRIS RS485 format
4 digital code
Normally 4, Expandable to 64
Normally 2, Expandable to 64
RS485, 2 Ports
19,200 bauds
60 time zone
16
366
01-99
SYRIS NT Serial Module
Up to 3 level of local and / or
group anti-passback
16 key keypad
Built-in
8 x 2 LCD with backlight
Maximun 0.2 W
5 LED
2 C to 55 C
-25 C to 85 C
DC 11V to 20V
1W to 10W
107W x 150H x 27D
SYW95A Access Control Software
•
•
•
•
Link up to 99 Controllers, 396 doors, 792 Readers
3 level of anti-passback
User define language
6000 card holders
40
SY210NT4
9,999
8 (8In,8Out)
4
SYRIS RS485 format
4 digital code
Normally 4, Expandable to 64
Normally 4, Expandable to 64
RS485, 2 Ports
19,200 bauds
60 time zone
16
366
01-99
SYRIS NT Serial Module
Up to 3 level of local and / or
group anti-passback
16 key keypad
Built-in
8 x 2 LCD with backlight
Maximun 0.2 W
5 LED
2 C to 55 C
-25 C to 85 C
DC 11V to 20V
1W to 10W
107W x 150H x 27D
5.5
Power Consumption (DC12V)
Items / Spec
Controller
Card reader
Printer Module
DIDO Module
Power consumption per unit
400ma
100ma
100ma
250ma
42