ASTAT SD
Soft starters for 3ph motors up to 20 kW
Solid state soft starter for 3ph AC motors up to 20kW
Working voltage up to 500VAC
With built-in analogue control panel
Three phase - full wave control (6 thyristors)
Excellent basic functions
Motorstarters
•
•
•
•
•
A
Analogue control panel
Technical data
Ratings
3ph AC systems
B
Frequency range
C
up to 440V, + 10%, - 15% for types QS1_NA
up to 500V, + 10%, - 15% for types QS2_NA
49 - 62 Hz
Control specifications
Control system
Initial voltage (pedestal)
Starting torque
Kick start
Motor current (Im)
Current limitation
Acceleration ramp time
Energy savings
Override
Soft stop time
D
E
F
Digital system with microcontroller. Starting ramp with
progressive increase in voltage and current limitation
40% - 90% Un
15% - 80% Mdir.start
90% Un (80% Mdir.start), 400ms
0.5 to 1 Ir (nominal ASTAT)
2 to 5 x Ir
0.5 to 60 s
Output voltage reduction according to power factor
Fixed output voltage permanently equal to supply voltage
Max. 2 x t acceleration time
Operation
External control
Acceleration phase
Permanent phase (choice)
Stop phase (choice)
G
H
Start - Stop
Adjustable time
Energy savings / Override
Power cutt-off / Ramp
Inputs / Outputs
Input
Output
I
Two optical couplings for Start/Stop
One relay either Run or End of ramp (1NO)
Protections
X
Order codes ! page D.73
Diagrams ! page D.74
Dimensions ! page D.76
D.72
D.72
Current limit
Loss on input phase
Thyristor short-circuit
Loss on output phase
Supply frequency error
Error (CPU)
Adjustable from 2 to 5 Ir
Trip at 3 sec.
Trip at 200 ms
Trip at 3 sec.
Will not start if f < 4a8Hz or f > 62Hz
60ms