Download Building Access Controller 32
Transcript
17 9 Web Browser (Editing) 9.1 System In the Edit > System menu, fill in the following fields with the appropriate information to begin configuring your Building Access Controller 32. The Edit > System menu Field Description Name Name of this device, used for your reference. Location Location of this Building Access Controller 32, used for your reference. Contact Contact phone number for the person responsible for this Building Access Controller 32. Serial Number Assigned at the DPS Telecom factory for unique unit identification. DCP Port Enter the DCP Port for this Building Access Controller 32, then select between UDP/TCP. In-Facility Broadcast When checked, the "In-Facility Broadcast" function is active. This is an alternate mode of operation and is not commonly used. (see later section for description) In-Facility UDP Port The UDP port used to broadcast "In-Facility" notices to other BACTL 32 units. This port is also used to listen for incoming broadcasts. Default port is 6000. The number of broadcasts (from 1 to 3) that will be executed for each "In-Facility" notice. In-Facility Send Since broadcasts receive no response, sending more than one broadcast increases Count reliability. Broadcast retries occur within a few seconds of each other. Default send value is 1. Normally Open Door Alarms When checked, all door alarms attached to this Building Access Controller 32 will reverse their polarity from "normally closed" to "normally open". Door Unlock Duration The number of seconds (from 1 to 30) that a door will remain unlocked after a valid electronic entry (manual card swipe or keypad, or remote unlock from T/Mon).