4-2 Function Mode
Ready Function
Data
Symbol
52
RDY
Function name
Status
Description
ON
The Inverter is ready.
OFF
Normal stop status
Ready function
Available input terminals
C001, C002, C003, C004, C005
•Inputting this signal shortens the time between the RUN command input and the start of actual
operation. In normal status, this is approx. 20 ms. Shortened time through this function varies
depending on timing.
When the Inverter is in ready status, high voltage is applied to terminals U, V, and W on the main
circuit terminal block. This happens even if the motor is stopped with the RUN command turned off.
Do not touch the main circuit terminal block.
Parameter No.
Function name
Data
C021
Multi-function output
terminal P1 selection
C026
Relay output (MA, MB)
function selection
Default setting
Unit
00

05

00: RUN (signal during RUN)
01: FA1 (constant speed arrival signal)
02: FA2 (over set frequency arrival signal)
03: OL (overload warning)
04: OD (excessive PID deviation)
05: AL (alarm output)
06: Dc (disconnection detected)
07: FBV (PID FB status output)
08: NDc (network error)
09: LOG (logic operation output)
10: ODc (communication option
disconnected)
43: LOC (light load detection signal)
•You can allocate the following functions to multi-function output terminal P1 and the relay output
terminals.
•While the multi-function output terminal P1 selection is for open collector output (allocated in
C021), the relay output function (MA, MB) selection is for SPDT-contact relay output (allocated in
C026).
•You can select NO- or NC-contact output for each output terminal with C031 or C036.
Data
Description
Reference item
Page
Signal during RUN
4-61
00
RUN: Signal during RUN
01
FA1: Constant speed arrival signal
FA2: Over set frequency arrival
signal
Frequency arrival signal
4-61
02
03
OL: Overload warning
Overload warning signal
4-63
04
OD: Excessive PID deviation
Excessive PID deviation output
4-63
05
AL: Alarm output
Alarm output
4-64
06
DC: Disconnection detection
External analog input
disconnection detection
4-64
4-60
Functions
Multi-function Output Terminal Selection
4