D20/D200 Installation and Operations Guide GE Energy Appendix B: 68K Monitor Commands Introduction This appendix outlines some of the 68K Monitor commands that can be used when working with D20ME. Instructions in this chapter are excerpts from the 68K Monitor User's Guide. Refer to the 68K Monitor User's Guide (P136-0UG) for information about other commands not listed here. Changing the Baud Rate The D20ME/ME II Monitor has the ability to change the communication speed of the WESMAINT port. This is useful when downloading large files. Example: A 1 MB code file may take upwards of 40 minutes to download at 9600 bps (the default). At 38400 bps, the transfer is only 10 – 15 minutes. Note: SET BAUD RATE command Most PCs cannot exceed 115,200 bps, and some terminal programs (Windows Terminal for example) may have other restrictions. Check the program's User's Guide for help. The SET BAUD RATE command changes the data rate of the WESMAINT port to a user-supplied value. Command Format BAUD baud_rate WARNING: General Full Variables None Parameters baud_rate Example Type BAUD 4800 and press ENTER. Results: The monitor switches to communicate at 4800 bps. Special Considerations See warning above. = the new data rate for the port, in bps. Speed change made using the SET BAUD RATE command are not saved in NVRAM; the monitor will return to 9600 bps after a restart. It is recommended that this command be only used to speed up a serial download, and not to redefine the operational state. 994-0078-2.00-8 127