Download User Manual
Transcript
Program Synchronization D-3 Adjusted Maximum Program Scan Time The Maximum Program Scan Time parameter you enter for Synchronous mode gets adjusted before being used by the ControlNet PLC-5 Backup system. The Adjusted Maximum Program Scan Time is equal to the smallest integer number of NUT’s whose time value is greater than or equal to the Maximum Program Scan Time parameter. For example, if the configured Maximum Program Scan Time parameter is 65ms and the ControlNet channel NUT value is 10ms, the Adjusted Maximum Program Scan Time would be 70ms (i.e. 10ms x 7). In this example, each program scan time would be fixed at 70ms. Program Scan Overrun For Synchronous mode operation, it is possible for the actual program scan time to exceed the Adjusted Maximum Program Scan Time. When this overrun condition occurs, the Sync LED turns solid red and the Maximum Program Scan Time Exceed Counter (word 48 in the ControlNet Backup Integer File) is incremented. You must zero out the Maximum Program Scan Time Exceed Counter for the Sync LED to turn from solid red to solid green. The Maximum Program Scan Counter is cleared by writing a non-zero value into the Reset Diagnostic Counters word (word 32 of the ControlNet Hot Backup Integer file). When a program scan overrun occurs, the two processors temporarily go out of sync, however they do not stay out of sync. They go back into sync at the earliest time possible. They should be back into sync at the next housekeeping. Even when the processor are resynchronized, the Sync LED remains solid red until you clear the Maximum Program Scan Time Exceed Counter. Should frequent program scan overruns occur, it may be necessary for you to increase the Maximum Program Scan Time parameter. The Maximum Program Scan Time parameter can be changed "on-the-fly" to the primary processor while the processor is in RUN mode. Both processors will automatically begin using the new Adjusted Maximum Program Scan Time parameter. 3XEOLFDWLRQ)HEUXDU\