Download DIGITAL PRESSURE CONTROLLER
Transcript
APPENDIX B SUMMARY OF ERROR MESSAGES Negative error numbers are from the Standard Commands for Programmable Instruments (Version 1991.0). Value 0 Description and Corrective Action No Error. -103 Invalid Separator. Check punctuation in the SCPI command. -104 Data Type. The type of parameter data is incorrected. Check for numeric versus string data. -109 Missing Parameter. No valid parameter was found for the SCPI command. -110 Command Header. The command name is not valid. -113 Command Unknown. The command specified does not exist. -114 Header Suffix. The numeric suffix for the command name is out of range. -221 Settings Conflict. The command could not be executed due to the current state of the DPC. Some commands cannot be executed while a program, self-test, or calibration is in progress. -222 Out of Range. The value is not within the valid range. For pressures check your high and low limits. -281 Cannot create program. Program memory is full. -282 Illegal Program Name. The name specified is not valid or does not exist. -284 Program Currently Running. The command cannot be executed while a program is running. -285 Program Syntax Error. The syntax of the program definition is not correct. -286 Program Runtime Error. An error occurred while running the program. Usually the setpoint is out of range. -313 Calibration Data Lost. The calibration data has been lost and the unit must be recalibrated. -315 Configuration Data Lost. The configuration data has been lost. Check all parameters to be sure they are correct. -330 Self-Test Failed. Check the display for the test that failed. -350 Queue Overflow. The error queue was full and messages were lost. -400 Query Error. A read request was received when there was nothing to read. -500 Controller Malfunction. Internal control failure. -501 High Limit Exceeded. The pressure was greater than the high limit. -502 Low Limit Exceeded. The pressure was less than the low limit. -503 Slew Limit Exceeded. The pressure changed faster than the slew limit allowed. -521 Pressure Overrange. The pressure reading is outside the range of the DPC. B-1 APPENDIX B