Transcript
364xS User’s Manual On Off 53 to start the Totalizer to stop the Totalizer NOTE In case the Totalizer is used in Bidirectional Flow mode the Totalizer LRV (0%) and the Totalizer URV (100%) have to be equal in absolute valu e. If different the Totalizer Status remains OFF. The max integration time selectable is 54 mins. F Digital LCD Integral Display Keys sequence to operate the Totalizer Status: 4 - 1 - Edit To reset the Permanent Totalizer Navigate the Digital LCD Integral Display menu, select Totalizer > Reset > Permanent Totalizer > Reset. To reset select OK. F Digital LCD Integral Display Keys sequence to reset the Permanent Totalizer: 4 – 2 – 1 - OK To reset the Batch Totalizer Navigate the Digital LCD Integral Display menu, select Totalizer > Reset > Batch Totalizer > Reset. To reset select OK. F Digital LCD Integral Display Keys sequence to reset the Batch Totalizer: 4 – 2 – 2 - OK To protect the Permanent Totalizer Navigate the Digital LCD Integral Display menu, select Totalizer > Reset > Permanent Totalizer > Tot. Protection, and the actual protection will be available (Unlock and Lock). To modify select Edit then scroll the desired protection with the up and down keys and confirm with OK. F Digital LCD Integral Displa y Keys sequence to protect the Permanent Totalizer: 4 – 2 – 1 – 2 - Edit To change the Permanent Totalizer protection Password: The Permanent Totalizer Password is a five digit string. The default value, at the transmitter deli very is ¬¬¬¬¬. When this default password is set the protection does not work. Navigate the Digital LCD Integral Display menu, select Totalizer > Reset > Permanent Totalizer > Change Password, and the actual password will be available. To modify select Edit then scroll the desired alphanumeric symbol with the up and down keys and confirm with Next. Repeat the operation for the five digits and confirm with OK. F Digital LCD Integral Display Keys sequence to change the Permanent Totalizer Password: 4 – 2 – 1 – 3 – Edit Totalizer operation by HHT Totalizer operation by Hand Held Terminal is available appropriated operations. . Please refer to the device manual for the Totalizer operation by PC Totalizer operation by PC is available using dedicated Software . ABB can provide the references and the Software. Please refer to the Software instructions for the appropriated operations. Reset to Factory trim The transmitter has in the memory the Sensor Low trim, the Sensor High trim and the Output trimming (Digital to analog trim) defined or calculated during the transmitter assembly. These data have been defined as Factory trim. The Reset to Factory trim allow the restoration of the as -shipped factory settings of the sensor trim and analog output trim. The Reset to Factory trim is suggested in case wrong trim operations are performed and the transmitter is in an undefined condition (i.e.: inadvertent zero trim of an abs olute pressure unit or inaccurate pressure source). Operation