Download ControlLogix Digital I/O Modules
Transcript
ControlLogix Diagnostic Digital I/O Module Features 4-29 Field Power Loss Detection This feature is used when field power to the module is lost or zero cross cannot be detected. A point level fault is sent to the controller to identify the exact point faulted. IMPORTANT Only enable Field Power Loss detection for points that are in use. If this feature is enabled for points that are not in use, you will receive faults for those points during operation. This feature has a corresponding tag that can be examined in the user program in the event of a fault. For more information on these tags, see Appendix A. Enable Field Power Loss Detection as shown below. Enable and disable field power loss detection on the Configuration tab. • Check the box to enable field power loss detection. • Clear the box to disable field power loss detection. For an example of how to enable the Field Power Loss detection diagnostic, see page 6-12. Preliminary Publication 1756-UM058D-EN-P - October 2004