Download - Aplisens SA
Transcript
C1 62 L6 L7 A-A L5 COVER T I G L8 HT E IV L WH E B N KE A EP DTR.APC.APR.ALW.03(ENG) B CI RCU I TS A L4 B-B scale:2:1 A MINIMUM WIDTH OF JOINT AND MAXIMUM GAP FOR GROUP IIC ENCLOSURES width of joint (min. real) L mm diameter D d D-d mm mm mm quantity of joint minimum according to PN-EN 60079-1:2004(U) 2 width of joint min.12,5 L4 13,2 -0,040 15+0,027 15-0,070 L5 12 M72x1,5 M72x1,5 2 L6 9 M20x1,5 M20x1,5 2 L7 12,7 1/2NPT 1/2NPT 2 L8 10 0,097 1 L4 min.5 threads engaged(8) min.5 threads engaged(6) min.6 threads engaged cemented joints width of joint min.10 Fig. 20. The explosion - proof joints of APC..., APR... transmitters. KE EP COVER T I G HT L CIRCUIT IS ALIVE E IV WARNING- CI RCU I TS A Fig. 21. How to lead the casing of APC..., APR... transmitters. WH E FIELD TERMINALS Lock the cover tight by unbolting the screw N N°