Download VCI - MH-3000 Quick Ship Setup Manual
Transcript
Step 6. Apply power • Remove all fuses from the controller. See table below for their description and sizes. • Turn ON the Mainline Disconnect and measure the building supply voltage at F1A, F2A & F3A terminals. • Turn OFF the Mainline Disconnect. • Install fuses F1, F2 & F3. • Turn ON the Mainline Disconnect • Verify that the building supply voltage is present at F1B, F2B & F3B terminals. • Verify that 115VAC is present across terminals F4A & 35. • Turn OFF the Mainline Disconnect. • Install fuses F4, F5 & F6. • Turn ON the Mainline Disconnect and verify the following: o 115VAC is present across terminals 1 & 35 o [With MOD Door] 115VAC is present across terminals AC1 & AC2 o [With MOVFR Door] 230VAC is present across terminals AC1 & AC2 • Turn OFF the Mainline Disconnect. • Install fuse F9. • Turn ON the Mainline Disconnect. Fuse Description Size F1, F2 Controller Mainline 6 Amp 600 Volt F3 Controller Mainline 1 Amp 600 Volt F4 AC supply 3 Amp 250 Volt F5, F6 Door Operator supply 3 Amp 250 Volt F9 Hall Common 1 Amp 250 Volt Fuse Description and Size Page 6 Virginia Controls, Inc. ● 2513 Mechanicsville Turnpike ● Richmond, Virginia 23223 Tel: (804) 225-5530 ● Fax: (804) 225-0116 ● email: [email protected] ● web site: www.vacontrols.com