(c) Operation example of out-of-range output The following figure shows the timing to enable Lower limit value setting (Coincidence output 1) (1000) and Upper limit value setting (Coincidence output 1) (2000) and an operation example of when the present value reaches out of the setting range (1000 to 2000) for the case where out-of-range output is set as the comparison condition. Note that Coincidence output 1 is assigned to CH1. Controlled by the high-speed counter module Controlled by the program CH1 Coincidence output enable command (RY20) ON ON Setting change request (Coincidence output 1) (RY14) 1) OFF Setting change completed (Coincidence output 1) (RX14) OFF Lower limit value setting (Coincidence output 1) (RWw0 to RWw1) Upper limit value setting (Coincidence output 1) (RWw2 to RWw3) Coincidence output 1 (RX10) 3) OFF ON 0 1000 0 2000 ON OFF 2) 5) 6) 5) 6) ON Coincidence output 1 terminal (EQU1) OFF CH1 Present value (RWr10 to RWr11) 0 1 999 1000 2000 2001 ON CH1 Count enable command (RY24) No. OFF 4) Description Start comparison of the present value and values set to Lower limit value setting (Coincidence output 1) (RWw0 to RWw1) and Upper limit value setting (Coincidence output 1) (RWw2 to RWw3) in the following order. (1) Write 1000 into Lower limit value setting (Coincidence output 1) (RWw0 to RWw1). (2) Write 2000 into Upper limit value setting (Coincidence output 1) (RWw2 to RWw3). 1) (3) Turn off then on Setting change request (Coincidence output 1) (RY14). (4) The values set for Lower limit value setting (Coincidence output 1) (RWw0 to RWw1) and Upper limit value setting (Coincidence output 1) (RWw2 to RWw3) are enabled when Setting change completed (Coincidence output 1) (RX14) turns on. After confirming that Setting change completed (Coincidence output 1) (RX14) turns on, turn off Setting change request (Coincidence output 1) (RY14). 2) CH1 Present value (RWr10 to RWr11) becomes less than Lower limit value setting (Coincidence output 1) (RWw0 to RWw1) and Coincidence output 1 (RX10) turns on since the present value is outside the specified range. If performing coincidence output from the coincidence output 1 terminal (EQU1), turn on CH1 Coincidence output enable command 3) (RY20). In this case, the coincidence output 1 terminal (EQU1) turns on immediately since Coincidence output 1 (RX10) is already on. 4) 5) Turn off then on CH1 Count enable command (RY24) to start counting. When CH1 Present value (RWr10 to RWr11) is Lower limit value setting (Coincidence output 1) (RWw0 to RWw1) or more and the present value is within the specified range, Coincidence output 1 (RX10) and the coincidence output 1 terminal (EQU1) turn off. When CH1 Present value (RWr10 to RWr11) is more than Upper limit value setting (Coincidence output 1) (RWw2 to RWw3) and 6) the present value is outside the specified range, Coincidence output 1 (RX10) and the coincidence output 1 terminal (EQU1) turn on. 112