Download CC-Link IE Field Network High-Speed Counter Module User`s Manual
Transcript
(a) Monitoring area of the extension module The remote buffer memory differs depending on the model of the extension module. • Extension input module (NZ2EX2B1-16D) Address Decimal Hexadecimal 1792 0700H Extension module identification code 1793 to 2047 0701H to 07FFH System area *1 *2 Default*1 Description Read/ Write*2 0000H R ⎯ ⎯ This is the value for when the module power supply is turned off then on or at the remote reset. This shows whether read or write from programs is possible. R: Readable W: Writable • Extension output module (NZ2EX2B1-16T) Address Decimal Default*1 Description Hexadecimal 1792 0700H Extension module identification code 1793 to 1807 0701H to 070FH System area 1808 to 1809 0710H to 0711H 1810 to 1811 Read/ Write*2 0000H R ⎯ ⎯ Y0 0 R 0712H to 0713H Y1 0 R 1812 to 1813 0714H to 0715H Y2 0 R 1814 to 1815 0716H to 0717H Y3 0 R 1816 to 1817 0718H to 0719H Y4 0 R 1818 to 1819 071AH to 071BH Y5 0 R 1820 to 1821 071CH to 071DH Y6 0 R 1822 to 1823 071EH to 071FH Number of ON times integration Y7 0 R 1824 to 1825 0720H to 0721H value Y8 0 R 1826 to 1827 0722H to 0723H Y9 0 R 1828 to 1829 0724H to 0725H YA 0 R 1830 to 1831 0726H to 0727H YB 0 R 1832 to 1833 0728H to 0729H YC 0 R 1834 to 1835 072AH to 072BH YD 0 R 1836 to 1837 072CH to 072DH YE 0 R 1838 to 1839 072EH to 072FH YF 0 R 1840 to 2047 0730H to 07FFH ⎯ ⎯ *1 *2 System area This is the value for when the module power supply is turned off then on or at the remote reset. This shows whether read or write from programs is possible. R: Readable W: Writable Number of ON times integration value Y0 to Number of ON times integration value YF are written to a nonvolatile memory in the specified cycle. 46