Download VIPAM user`s manual - Directory listing of

Transcript
Sepam Series 10 - Communication
Remote
Indication No. 1
Word (Address
0102)
Remote
Indication No. 3
Word (Address
0104)
Bit
Bit Address
Remote Indication
00
1020
Protection 50-51 delayed I> set point
01
1021
Protection 50-51 delayed I>> set point
02
1022
Protection 50-51 pick-up I> set point
03
1023
Protection 50-51 pick-up I>> set point
04
1024
Protection 50N-51N delayed Io> set point
05
1025
Protection 50N-51N delayed Io>> set point
06
1026
Protection 50N-51N pick-up Io> set point
07
1027
Protection 50N-51N pick-up Io>> set point
08
1028
Protection 49 RMS thermal alarm
09
1029
Protection 49 RMS thermal tripping
10
102A
Protection 50-51 delayed I> set point back-up
11
102B
Protection 50-51 delayed I>> set point back-up
12
102C
Protection 50N-51N delayed Io> set point back-up
13
102D
Protection 50N-51N delayed Io>> set point back-up
14
102E
Reserved
15
102F
Reserved
Bit
Bit Address
Remote Indication
00
1040
Send blocking input
01
1041
Receive blocking input
02
1042
Local (1)/remote (0) mode
03
1043
Remote control/circuit breaker position discrepancy
04
1044
Non-matching of breaker position auxiliary contacts or failure of the trip circuit (TCS)
05
1045
Closed circuit breaker
06
1046
External reset by logic input
07
1047
External trip by logic input
08
1048
Sepam not reset after fault
09
1049
Tripping
10...15
104A...104F
Reserved
Note: Bits 08 and 09 are only significant in standard operating mode.
Logic Input Word
(Address 0106)
SEPED307003 01/2008
Bit
Bit Address
Status
00
1060
I1 input
01
1061
I2 input
02
1062
I3 input
03
1063
I4 input
04...15
1064...106F
Reserved
181