Download EPM 2200
Transcript
APPENDIX B: MODBUS MAPPING FOR EPM2200 6 M denotes a 1,000,000 multiplier. 7 Not applicable to EPM2200 8 Writing this register causes data to be saved permanently in EEPROM. If there is an error while saving, a slave device failure exception is returned and programmable settings mode automatically terminates via reset. 9 Reset commands make no sense if the meter state is LIMP. An illegal function exception will be returned. 10 Energy registers should be reset after a format change. 11 N/A 13 N/A All 3 voltage angles are measured for Wye and Delta hookups. For 2.5 Element, Vac is measured and Vab & Vbc are calculated. If a voltage phase is missing, the two voltage angles in which it participates are set to zero. A and C phase current angles are measured for all hookups. B phase current angle is measured for Wye and is zero for other hookups. If a voltage phase is missing, its current angle is zero. If any register in the programmable settings section is set to a value other than the acceptable value then the meter will stay in LIMP mode. Please read the comments section or the range for each register in programmable settings section for acceptable settings. N/A 14 15 16 APPENDIX B–12 EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE