Download YOKOGAWA DR232 Communication Interface

Transcript
6.4 Setting the Recording
Example
SB
Print the range list and alarm list but do not print the
parameter list related to printing or the other
parameter list.
SFON, ON, OFF, OFF
Sets whether interpolation is
performed or not.
Example
Perform manual printing for channel 6 in slot 3 of
subunit 4.
PM436, ON
Comments • The optional computation channel number for a
stand-alone model is A01 to A30.
PA
Mode
Setting
Operation mode
SBp1, p2<terminator>
p1
Channel number (001 to 560)
Computation channel number (A01 to A60)
p2
ON/OFF
Example
Perform step interpolation for channel 6 in slot 3 of
subunit 4.
SB436, ON
Comments • If step interpolation is performed, the space
between recorded points is recorded .
• If two or more channels are step-interpolated in
the same position, the recording priority depends
on the recording color, and recording is done in
the following order:
Black > blue-purple > magenta > navy blue > red
> blue > brown > green > orange > yellow-green
For example, if two channels being recorded in
black and in blue are step-interpolated in the same
position, the overlapped parts are recorded in
black.
• The optional computation channel number for a
stand-alone model is A01 to A30.
PT
Turns on or off every channel of trend
record.
Mode
Setting
Operation mode
PTp1, p2<terminator>
p1
Channel number (001 to 560)
Computation channel number (A01 to A60)
p2
ON/OFF
Example
Turn on the analog recording of channel 6 in slot 3 of
subunit 4.
pT436, ON
Comments • The optional computation channel number for a
stand-alone model is A01 to A30.
PD
Turns on or off every channel of
digital records.
Mode
Setting
Operation mode
PDp1, p2, p3<terminator>
p1
Channel number (001 to 560)
Computation channel number (A01 to A60)
p2
ON
Records.
OFF Does not record.
p3
1 to 6 timer number (recording interval:
Effective only when digital records are set
for “multiple”)
Example
Perform digital recording of channel 6 in slot 3 of
subunit 4 at the interval of timer 2.
pD436, ON, 2
Comments • The optional computation channel number for a
stand-alone model is A01 to A30.
PM
Mode
Setting
6-8
Turns on or off every channel of
manual printing.
Operation mode
PMp1, p2<terminator>
p1
Channel number (001 to 560)
Computation channel number (A01 to A60)
p2
ON/OFF
Turns on or off the alarm printing for
every channel level.
Mode
Setting
Operation mode
PAp1, p2, p3, p4<terminator>
p1
Channel number (001 to 560)
Computation channel number (A01 to A60)
p2
Level (1 to 4)
p3
OFF No alarm printing
ON1 Printing when an alarm is generated
ON2 Printing when an alarm is generated
or reset
p4
Selection of additional message
OFF
Does not print an additional message.
01 to 20
Message number
Example
When an alarm of level 2 of channel 6 in slot 3 of
subunit 4 is generated, print the alarm and message
No. 5.
PA436, 2, ON1, 05
Comments • When an alarm is generated or reset, the alarm
generation time or alarm type is printed.
• If an additional message is specified, the message
set with the SG command is also printed.
• The optional computation channel number for a
stand-alone model is A01 to A30.
PC
Turns on or off scale printing for
every channel.
Mode
Setting
Operation mode
PCp1, p2<terminator>
p1
Channel number (001 to 560)
Computation channel number (A01 to A60)
p2
OFF No scale printing
ON1 Printing for every 20% of the scale
length
ON2 Printing at 0% and 100% of the scale
length
ON3 Printing at 0%, 50%, and 100% of
the scale length
Example
Print the scale of channel 6 in slot 3 of subunit 4 at
positions 0%, 50% and 100%.
PC436, ON3
Comments • For a channel for which recording is done in
partially expanded recording, the following
applies regardless of the p2 setting:
If the recording width is 100 mm or more, printing
is carried out at positions 0%, 100% and at a point
on the partially expanded recording boundary.
If the recording width is less than 100 mm but 50
mm or more, printing is carried out at positions
0% and 100%.
If the recording width is less than 50 mm, printing
is not carried out.
• This is effective for analog recording channels.
• A channel whose recording width is less than 50
mm is not printed.
• If ON1 is set to a channel whose recording width
is less than 150 mm, the setting is invalid. Printing
is carried out at positions 0%, 50% and 100%
only.
IM DR231-11E