Fastening Strategy Programming
Sequence 63
Set Point Definitions
Parameter and
Range of Values
Shut-Off Gradient
0 to 100 %
Minimum Gradient
--99.99 to 99.99
Maximum Gradient
--99.99 to 99.99
Minimum Angle
0 to 9,999
Maximum Angle
0 to 9,999
Strobe Multiplier
1 to 30
Trigger Torque
0 to 1.2 x Torque Cal Factor
Definition
Percentage of the maximum gradient as target
value. When it is reached, the sequence is
terminated. If the gradient drops to this percentage
of the maximum value, the sequence is terminated.
Low limit of gradient. If this limit is not reached, the
rundown is terminated (safety shutoff) and the
stage is evaluated as NOK.
High limit of gradient. If this limit is exceeded, the
rundown is terminated (safety shutoff) and the
stage is evaluated as NOK.
Low limit of angle. If this limit value is not reached,
the stage is evaluated NOK.
High limit of angle. If this limit is exceeded, the
rundown is evaluated NOK.
Step width for gradient calculation in angle pulses.
After reaching threshold torque, one measuring
point in excess of the strobe multiplier value (1 to
30) must be collected before the gradient is
calculated. Data collection is made per angle pulse.
With each new angle pulse, the oldest value is
deleted, and a new gradient is calculated. A strobe
multiplier of 1 corresponds to two measuring points
in direst sequence.
When this torque is exceeded, the recording for OScope begins. If the trigger torque value is higher
than the threshold torque, the recording begins
when the threshold torque is exceeded.
USER MANUAL
Tork-Trak TM Fastening Controller
Automated Systems NA
Section 7 - 60