Download VESDA Pipe Network Design Guide
Transcript
VESDA by Xtralis VESDA Pipe Network Design Guide 4.6 Object Protection 4.6.1 Above Cabinet Sampling The sampling pipe is installed directly over the cabinets to be protected. Sampling holes are placed over the cabinet ventilation grille. The holes are drilled so that they face into the air stream from the cabinet. Each monitored cabinet must have at least one sampling hole. The exhaust fan can cause sampling problems due to the high airflow around the sample pipe. Figure 4-15: Exhaust grille sampling on a bank of cabinets Legend A Sampling Hole B Air Grille Figure 4-16: Cabinet sampling for convection cooled cabinet www.xtralis.com 17