Download LogMessage
Transcript
Rules for settings 1. Digital input 4 and digital output 4 are used internally for synchronization. Both channels should be set to inactive. Set Value source to Manual value for digital output 4. 2. Manual configuration amendments to a "slave" require subsequent amendments to the "master" to avoid the handshake becoming incompatible. 3. If no external Trigger signal is used, the time period (of "master") must be set higher than the natural cycle (Recording time + Calculation time + 2 x Measured data transmit ti me) to avoid the handshake becoming incompatible. See timing diagram. Procedure The outcome of synchronization: Triggering takes place (almost) simultaneously. Measure ment data (time signal / frequency spectrum) are transmitted one after the other Timing diagram for the application example: 203 © 2010-2012 Delphin Technology AG LogMessage July 2012