Download PI to PI Interface User Guide

Transcript
PI ICU reference for the PI to PI Interface
(minimum one second, maximum 28800 seconds, which is eight hours). The time is
converted to milliseconds before being saved in the batch file. (/DELAYR=x)
• Suppress writing I/O Timeout to tags upon reestablishment of a lost
connection to the source PI Server
When setting Location3 to write I/O Timeout for any tags, enable this setting to suppress
the I/O Timeout state that is normally written to tags when the interface reconnects to the
PI Data Archive. If this parameter is not set, the I/O Timeout state that is written at reconnection prevents history from being recovered for the period of disconnection. (/TS)
Source PI Server Failover tab
The settings on this tab enable you to configure failover for source PI Data Archives, so that if
one source server fails, the interface can collect data from the other.
• Enable PItoPI Failover
Check to enable server failover.
• Source Server Interface Status Utility Tag
The PI Interface Status Utility point on the source server that tracks the status of the
primary server. Used by failover to determine whether the server is up and running. (/
SSU1=tagname )
• Secondary Source Server Node Name
The port number of 5450 is appended to the name when PI ICU saves the setting in the
batch file. (/SEC_SRC=nodename:5450)
• Secondary Source Int Status Utility Tag
Specifies the PI Interface Status Utility point on the secondary source server that tracks the
status of the server. Used by failover to determine whether the server is up and running. (/
SSU2=tagname)
• Number of connection attempts to source server
Configures the number of connection retries that the interface attempts before failing over
to the secondary source server. Default is 1. (/NT= x)
• Enable failover status logging
Enable failover status logging. If you enable this setting, you must configure the failover
status point on target server. (/FST=tagname)
PI to PI Interface User guide
33