Manual 37393B easYgen-1000 Series - Interfaces Remote Control Telegram 503 Object ID Parameter No. ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ 21F7h Name Control word 1 Bit 15 Not used Bit 14 Not used Bit 13 Not used Bit 12 Not used Bit 11 Not used Bit 10 Not used Bit 9 Not used Bit 8 Not used Bit 7 Not used Bit 6 Not used Bit 5 Not used Remote acknwledgement : Bit 4 reset alarm messages (rise of the pulse) Bit 3 Must always be configured to 0 Bit 2 Must always be configured to 0 Bit 1 Remote stop (rise of the pulse) Bit 0 Remote start (rise of the pulse) Unit Data type Bit field Unsigned16 Note Transmit first a 0, then a 1 to acknowledge Transmit first a 0, then a 1 to stop Transmit first a 0, then a 1 to start Remark : Bits may also be used for a different purpose than start/stop. Bit 0 "Remote start" If this bit changes from Low to High, the easYgen enables the remote start (logical command variable 04.13). The condition of the start command is stored and may be used as command variable for the LogicsManager. Bit 1 "Remote stop" If this bit changes from Low to High, the easYgen enables the remote stop (logical command variable 04.13). The condition of the stop command is stored and may be used as command variable for the LogicsManager. Bit 4 "Remote acknowledgement: reset alarm messages" This bit controls the logical command variable 04.14. This command must be executed twice. The first rise of the pulse resets the horn and the second rise of the pulse acknowledges a fault, which is not present anymore. © Woodward Page 53/96