Installation and de-installation 4.7 51/90 De-installation Dangerous voltage on conductors The connecting wires at the place of installation must not be live when removing the meter. Touching of live parts is dangerous to life. Remove the corresponding supply fuses and keep these in a safe place until work is completed, so that they cannot be replaced by anyone unnoticed. The meter should be removed as follows: 1. Remove the two utility seals at the screws of the terminal cover. 2. Release the two screws of the terminal cover and remove it. 3. Check that the connecting wires are not live using a phase tester or universal measuring instrument. If they are live, remove the corresponding supply fuses and keep these in a safe place until work is completed, so that they cannot be replaced by anyone unnoticed. 4. Remove the connecting wires of the signal inputs and outputs from the screwless spring-loaded terminals as follows: – Place a size 1 screwdriver in the upper opening and insert it turning slightly upwards (figure 50 A). – Then draw the wire from the lower opening (figure 50 B). – Withdraw the screwdriver (figure 50 C). Figure 50 Removing connections in screwless spring-loaded terminals Damage to terminals Never withdraw connecting wires from closed terminals. The terminals could be damaged. 5. Release the terminal screws 1, 3, 4, 6, 7, 9, 10 and 12 of the phase connecting wires with a suitable screwdriver and withdraw the phase connecting wires from the terminals. 6. Fit a substitute meter as described in section 4.3 "Connecting meter" and the following sections. D000045598 en a – S650 Series 3 – SMA300AR/CR – User Manual © Landis+Gyr