4.5.2.2
df1_xxao
1, 4, 8 or 18 Channel DF1 PLC Analog Output Board
Description
The df1_xxao I/O board provides 1, 4, 8 or 16 analog output channels to a SCADAPack E Series
RTU to communicate with an Allen Bradley PLC peripheral I/O device via a serial connection. The
analog channels can be connected to an Integer or Real variable within an ISaGRAF application.
The connected I/O points are continuously controlled by the Current Value of the ISaGRAF
variable. This information is cache internally by the RTU and made available to the I/O point.
I/O Connection
Board Reference (hex)
Library type
Data type
Channel type
Number of channels
0011
IO board
Analog (Integer or Real)
Output
1, 4, 8 or 16
Board Configuration
board_address
plc_data_type
must_write_rate
plc_device_add
timeout
Port
DF1 File address
SLC500 INT, SLC500 REAL, PLC INT, PLC5 REAL, GEN INT
Unit in mS
DF1 Slave address (1-254)
Unit in mS
0-3 = Port 0-3 on ES RTU, 4 = Diag Port
comms_options
XXX YYYY ZZZ
where:
XXX is the DF1 Address that the PDS RTU will appear as (default is
0).
YYYY is HALF or FULL for the duplex setting (default is FULL).
ZZZ is CRC or BCC (default is CRC).
Offset in file
address
E Series ISaGRAF IO Connection Reference Manual
February 7, 2006
63