5-. SOFTWARE DESCRIPTION
- TYPE:
The type of transformer being used.
transformer nameplate.
This information is shown on the
- Transformer/Autotransformer:
Indicates whether the transformer in question is actually a transformer or an
autotransformer.
- No Tertiary/Tertiary:
Indicates whether the transformer does or does not have a tertiary winding.
- Single phase/Three-phase:
Indicates whether the transformer is single phase or three-phase.
- Y. OF MANUFACTURING:
Year in which the transformer was manufactured.
- COOLING:
Type of cooling of the transformer. May be by oil or dry.
- POWER (MVA):
Maximum power of the transformer in millions of volt-amperes.
- RATED Vsc:
Rated short-circuit voltage in percentage terms. This is the percentage of the
rated voltage that needs to be applied to the high voltage winding in order for
the rated current to flow through the low voltage winding under short-circuit
conditions. This is shown on the nameplate.
- CONNECTION GROUP:
This is the coil connection group for three-phase transformers. By clicking on
the indicator, a list of the existing possibilities is unscrolled. Those groups for
which „N/n‟ appears have one of the windings with the neutral accessible: if
„N‟ is shown (e.g., YNy0), the high voltage winding has the accessible
neutral, while if „n‟ is shown (e.g., Dyn5), it is the low voltage or tertiary
winding.
- TERTIARY GROUP:
This indicates whether the transformer has a third winding, in addition to the
high and low voltage windings.
- 46 -