SPM-8 Multi-Function Power Meter
User guide
1
Content
Chapter 1 Introduction
1.1 Product Introduction
1.2 Caution
1.2.1 Danger
1.2.2 PRODUCT WARRANTY & CUSTOMER SUPPORT
1.2.3 LIMITATION OF WARRANTY
Chapter 2 Detail Specification
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
Power parameters measure
Energy measure
Demand measure
Power Quality measure
Report and event logging
Display and input/output
Communication
Environmental & Physical
Ordering Code
Chapter 3 Installation
3.1 Safety
3.2 Mounting
Chapter 4 Connection
4.1 Back view of connect port
4.1.1 Digital Output
4.1.2 Analog Output
4.1.3 Digital Input
4.1.4 Analog Input
4.1.5 Aux. Power Supply
4.1.6 Current Terminal
4.1.7 Voltage Terminal
4.2 Wiring diagram
4.2.1 1P2W/1CT
4.2.2 1P3W/2CT
4.2.3 3P3W/2CT
4.2.4 3P3W/3CT
4.2.5 3P4W/3CT
Chapter 5 Function Tree
Chapter 6 RunTime
6.1 Display
6.2 Runtime auto scroll
Chapter 7 Set up mode operation
7.1 SPM-8 display and keyboard
7.2 Set up
7.2.1 Clear Function
7.2.2 Basic Setup
7.2.2.1 Communication
7.2.2.2
7.2.2.3
7.2.2.4
7.2.2.5
Measurement
Security
Alarm Set Point
Clock Setup
2
7.2.2.6 Digital Output
7.2.2.7 Analog Output
7.2.2.8 Analog Input
7.2.2.9 Demand Setup
7.2.2.10 Period Reset
7.2.3 Display Setup
7.2.4 TOU Setup
7.3 Report
7.3.1 Daily Report
7.3.2 Diagnostic
7.3.3 Harmonics
7.3.4 Current on alarm
7.3.5 Event log
7.3.5.1 Sag Record
7.3.5.2 Swell record
7.3.5.3 Alarm Record
7.3.6 Analog input
7.3.7 Nameplate Info
Chapter 8 Communication format
8.1 RS485
8.1.1 RS485 standard
8.1.2 Wiring for instruments communication
8.2 Modbus
8.2.1 Modbus Format8.3 Communication protocol
8.3 Communication protocol
8.4 IEEE 754 Format
8.5 Modbus RTU Mode
8.6 Modbus Function Code
8.7 Detail Parameter
3
Chapter 1 Introduction
1.1 Product Introduction
SPM-8 series power meter is designed for continuous monitoring of 3 phase system. All essential
power parameters measure including current, voltage, power, active and reactive energy are
integrated in a single meter. Its bi-directional energy measurement and harmonic analysis function
makes SPM-8 suitable for modern industrial power management. The built-in RS485 and rich
communication abilities enable SPM-8 to be easily connected with most modern third-party SCADA
systems.
Features
Standard
Model
Power parameters measure
Current:3 phase, neutral, accuracy 0.1%
Voltage:3 phase phase-phase, phase-neutral, accuracy 0.1%
Frequency:47-63 Hz
Total power:Active, reactive, apparent power, accuracy 0.5%
Power per phase:Active, reactive, apparent power, accuracy 0.5%
Power factor:Total, per phase
Auto wiring detection
Energy measure
Energy:Active, reactive, apparent energy, accuracy 0.5%
Bi-directional energy:Deliver and receive kWh, kVARh, kVAh
Display and input/output
Panel display:Mono 128 x 128 STN-LCD
Digital input:12 channel dry contact inputs
Digital output:2 channel relay for alarm and kWh pulse output
Analog input:4 channel 4-20mA input(option)
Analog output:4 channel 4~20 mA for V, I, kW, kVA, kVAR(option)
Voltage connection:10- 600 V RMS(ph-ph)
Current connection:5A RMS, minimum detetable current 2 mA
Power supply:86~242 Vac or100~300 VDC
Communication
Primary port:RS485 Modbus
Secondary port:Ethernet : 10/100 Mbps, Modbus over TCP/IP protocol(option)
Demand measure
Block/Rolling demand
Power Quality measure
Harmonic:V, I THD and individual harmonics
Sag/Swell:Configurable setting points
Report and event logging
Report:Daily report : this day, yesterday;Regular report : this period, last reset
Event logging:Sag, swell, alarm logging
4
Advance
Model
1.2 Caution
1.2.1 Danger
The meter contains hazardous voltages. The meter should never be disassembled. Failure to observe
this practice can result in serious injury or death. Any work on or near energized meters, meter
sockets, or other metering equipment can present a danger of electrical shock. It is strongly
recommended that all work should be performed only by qualified industrial electricians and
metering specialist. Shihlin assumes no responsibility if your electrical installer does not follow the
appropriate national and local electrical codes.
1.2.2 PRODUCT WARRANTY & CUSTOMER SUPPORT
Shihlin warrants all products free from defects in material and workmanship for a period of one year
from the date of shipping. During the warranty period, we will, at our position, either repair any
product that proves to be defective. To report any defect, please contact :+886-3-5981921 or
[email protected]
Please have the model, serial number and a detailed problem description available when you call. If
the problem concerns a particular reading, please have all meter readings available. When returning
any merchandise to Shihlin, a return materials calibration number is required.
1.2.3 LIMITATION OF WARRANTY
This warranty does not apply to defects resulting from unauthorized modification, misuse, or use for
reason other than electrical power monitoring. The supplied meter is not a user-serviceable product.
5
Chapter 2 General Features
*:only in Advance model
2.1 Power parameters measure and accuracy
Current:3 phase, neutral, accuracy < 0.1%
Voltage:3 phase phase-phase, phase-neutral, accuracy < 0.1%
Frequency:47-63 Hz
Total power:Active, reactive, apparent power, accuracy < 0.5%
Power per phase:Active, reactive, apparent power, accuracy < 0.5%
Power factor:Total, per phase
2.2 Energy measure
Energy:Active, reactive, apparent energy, accuracy < 0.5%
Bi-directional energy:Deliver and receive kWh, kVARh, kVAh
2.3 Demand measure*
Bi-directional Block/Rolling demand
2.4 Power Quality measure*
Harmonic:V, I THD and individual harmonics, up to 31 orders
Sag/Swell:Configurable setting points
2.5 Report and event logging*
Report:Daily report : this day, yesterday
Regular report : this period, last reset
Event logging:Sag, swell, alarm logging
2.6 Display and input/output
Panel display:Mono 128 x 128 STN-LCD
Digital input:12 channel dry contact inputs
Digital output:2 channel relay for alarm and kWh pulse output
Analog input:4 channel 4-20mA input(option)
Analog output:4 channel 4~20 mA for V, I, kW, kVA, kVAR(option)
Voltage connection:10-600Vrms
Current connection: 5Arms, minimun detetable current 2 mA
Power supply:86~242 Vac or 100~300Vdc
Power consumption:8W/15VA
2.7 Communication
Primary port:RS485 Modbus or DNP 3.0 protocol
*
Secondary port :Ethernet : 10/100 Mbps, Modbus over TCP/IP protocol,
2.8 Environmental & Physical
Operation temperature:-20℃to 60℃
Storage temperature:-25℃ to 80℃
Humidity:20-90%RH (non-condensing)
Dimensions:144mm(L) x 144mm(W) x 94mm(H)
6
2.9 Ordering Code
SPM-8 □ □ □ □
Model
0:Standard
1:Advanced
Secondary Port
0:No secondary port
1:Ethernet
AI function
0:Without AI function
1:With AI function
AO function
0:Without AO function
1:With AO function
Note:Standard Model offers no secondary port
7
Chapter 3 Installation
3.1 Safety
On receipt of the instrument and prior to installation, makes sure it has not been damaged during
shipment.
The instrument is no longer safe when,
a) shows clear signs of damage
b) does not work
c) long storage under extreme conditions
d) damage during shipment
3.2 Mounting
This instrument should install on vibration free switchboard and with environment temperature
between -20℃~60℃, humility between 20-90%RH(no condensing)
For the instrument is already equipped with an internal protection fuse, a 1AmAT HBC fuse is
recommended during installation
Prior to maintain/repair this instrument, always disconnect this instrument from all power
sources
Only have qualified and authorited personnel to carry out installation, maintainance and repair
Water profe for front panel IP54, case IP20
After mounting the instrument, place all four support latch in position.
Pannel cut-out area is 138x138mm(+or- 0.5mm)
8
Chapter 4 Connection
4.1 Back view of connect port
9.
8.
7.
4.
3.
2.
10.
1.
5.
6.
12.
11.
1.
2
3.
4.
5.
6.
7.
8.
9.
10.
11
12
AUX. power
Digital output (Com2 DO2 Com1 DO1)
Analog output (Com1 AO4 AO3 AO2 AO1)
Digital input (Com1 DI4 DI3 DI2 DI1)
Digital input (DI5 DI6 DI7 DI8 Com2)
Digital input (DI9 DI10 DI11 DI12 Com3)
RS485 port (D- D+)
RS485 port (D- D+)
Ethernet port
Analog input (AI1+ AI1- AI2+ AI2- AI3+ AI3- AI4+ AI4-)
Current terminal (3L 3S 2L 2S 1L 1S)
Voltage terminal (C.B.A.N)
9
4.1.1 Digital Output
2 channel 4 pin digital output (Com2 DO2 Com1 DO1)
12-240VAC-DC/120mA max
Com0 DO0 for digital output1, Com1 DO1 for digital output 2
Port 1 assign selection : V/I Unbal Alarm, THD Alarm, Over V/I Alarm, Under V Alarm, V/I Loss
Alarm
Port 2 assign selection : Energy pulse (pulse/kWh)
4.1.2 Analog Output
4 channel 5 pin current output (Com1 AO4 AO3 AO2 AO1)
4-20mA current output
4 analog output selection:phase, voltage, current, power…
4.1.3 Digital Input
3 groups of 12 channel, 15 pin digital input (Com1 DI4 DI3 DI2 DI1)、(DI5 DI6 DI7 DI8 Com2)、
(DI9 DI10 DI11 DI12 Com3)
5-24Vdc
4.1.4 Analog Input
4 channel 8 pin analog input(AI1+ AI1- AI2+ AI2- AI3+ AI3- AI4+ AI4-)
4-20mA input
10
4.1.5 Aux. Power Supply
Before powering the instrument, verify the pin position at L and N, leave the middle pin blank.
Power standard is 86-242Vac/100-300Vdc.
An internal protection fuse 250V, 1A is equipped.
The instrument power supply must not be earthed.
4.1.6 Current Terminal
The current input are 3 channels/6 terminals(3L 3S 2L 2S 1L 1S)
Input current range from 2mA to 5A (CT secondary)
Warning !
The CT input current must not exceed 10A
Warning !
Be sure to short secondaries of each current transformer, before removing the CT connection inputs.
4.1.7 Voltage Terminal
There are 4 voltage terminals(C.B.A.N) 。
The instrument measure voltage from 10V-600V.(PT secondary)
Voltage must not exceed 600V, in case of over 600V, voltage transformer need to be applied.
Note !
3P3W/2CT and 3P3W/3CT wiring, only connect “C A N”, and leave “B” blank
OR
11
4.2 Wiring diagram
4.2.1 1P2W/1CT
3L
3S
2L
2S
1L
1S
C
B
L
N
4.2.2 1P3W/2CT
4.2.3 3P3W/2CT
12
A
N
4.2.4 3P3W/3CT
4.2.5 3P4W/3CT
13
Chapter 5 Function Tree
Select Manual
Clear Function
Basic Setup
Setup
Report
Daily Reset
Energy Reset
Sag Reset
Swell Reset
Sag/ Swell Reset
Alarm Rcd Rese
Reset to Default
Reset All
Demand Reset
Period Reset
Communication
Modbus
Baud Rate
CM1 Unit ID
Stop Bit
Parity Bit
Ethernet
IP Address
Port No
Subnet Mask
Gateway
Mac Address
Measurement
Volts Mode
PT Primary
PT Secondary
CT Primary
CT Secondary
Frequency
Security
Alarm Set Point
Modify PWord
Enable/Disable
Sag/Swell Limit
Sag Limit
Swell Limit
Ref. Primary Voltage
Alarm Set Point
Alarm Clear Point
Setup
Display Setup
Clock Setup
Date
Time
Digital Output
Digital Output 1
Digital Output 2
Analog Output
Analog Output 1
Analog Output 2
Analog Output 3
Analog Output 4
Analog Input
Analog Input 1
Analog Input 2
Analog Input 3
Analog Input 4
Demand Setup
Mode
No. of Subinterval
Subinterval Length
Period Reset
Mode
Date
Auto Scroll
Backlight Timeout
Runtime
Language
Voltage
Line Current
Power
Power Factor
Energy
Demand
Status
Item
Kh
Phase
Item
AI High Value
AI Low Value
Phase Voltage
Line Voltage
Active Power
Apparent Power
Reactive Power
14
Report
Daily Report
Diagnostic
Harmonics
Alarm
Event Log
Analog Input
Nameplate Info
Run Hour
Phasor
Today
Energy
Max/Min Total Power
Max/Min V Avg
Max/Min I Avg
Yesterday
Energy
Max/Min Total Power
Max/Min V Avg
Max/Min I Avg
This Period
Last Reset
Va Harmonics
Vb Harmonics
Vc Harmonics
Ia Harmonics
Ib Harmonics
Ic Harmonics
Sag Record
Swell Record
Alarm Record
15
Chapter 6 Run Time
In runtime mode, the instrument is able to measure and store all real time electrical parameters.
Following is the table that this instrument can display.
6.1 Display
Display
Average / ΣResult
Phase Voltage
Line Voltage
Line Current
Active Power
Apparent Power
Reactive Power
Power Factor
Total Energy
Total Energy
(Fundamental*、True)
Demand*
Items
Vavg、Iavg、ΣW、ΣVAR
L12 、L23 、L31 V, kV, MV
L1 、L2 、L3
V, kV, MV
L1 、L2 、L3、N A, kA, MA
L1、L2、L3、ΣL
W, kW, MW
L1、L2、L3、ΣL
kVA, kVA,
MVA
L1、L2、L3、ΣL
kVAr, kVAr,
MVAr
L1、L2、L3、ΣL
kWh del、rec、total
kVARh +(lagging)、-
(leading)、total
Last kW、kW、Last kVA*、kVA*、
Last kvar*、kvar*、Time
Freq: Hz
Digital Output 1~2 ON/OFF
Digital Input 1~4 ON/OFF
Digital Input 5~12 ON/OFF
Frequency / Status
Frequency / Status
*only in advanced modal
6.2 Run Time Auto scroll
Each screen except Average/Result can be disable/enable individually in the setup mode, and auto
scroll time can be disabled or set from 1 to 6 second. The cruise keys are used to move from one
page to another one manually.
Use
Use
to next page
to previous page
6.3 Worning for incorrection of wiring or phase
“Ø” “△-Y” symbols will be shown on the upper corner of
16
Chapter 7 Set up mode
7.1 Display and keyboard
LCD grapic, LED back-lighted, 128 ×128
kWh light:Pulse output
Back light:1-99 minute
Enter key:Entering setup mode, or confirm the selection
Esc key:Back to runtime mode or return to previous setup page
Arrow Key:Scroll select item or change the input number or shift input position
17
7.2 Set up
Press Enter to setup mode, enter password-xxxxxxx-7 digits,(default as 0000000), user can modify
password by:Setup→Basic Setup→Security→Modify pword
In Main Menu “Setup”, we have:
Clear Function
Basic Setup
Display Setup
7.2.1 Clear Function
Clear function was designed to allow user to easily move and/or reset different data stored in this
instrument.
Nevertheless, energy data will not be reset due to its accumulation characteristics expect using the
function of “energy reset”.
In the standard model, to “energy reset” please press the
button at the same time at least 5
seconds.
Item
Setup
Daily Reset
Energy Reset
Sag Reset
No
Yes
Swell Reset
Sag/ Swell Reset
Alarm Rcd Reset
Reset to Default
Reset All
Demand Reset
Period Reset
Meter R-Hour Reset
Load R-Hour Reset
Daily Reset:Clear this Day Max/Min & Yesterday Max/Min Record
Energy Reset:Reset kWh_del、kWh_rec、kWh_tot、kWh_net、kVarh_lagging、kVarh_leading、
kVArh_tot、 kVArh_net、kVAh
Sag Reset:Reset Sag Record
Swell Reset:Reset Swell Record
Sag/Swell Reset:Reset Sag/Swell Record
Alarm Rcd Reset:Reset Alarm Record
18
Reset to Default:Reset all the parameters to default value
Reset All:Clear This Day Max/Min、Yesterday Max/Min 、Energy、Sag、Swell、Alarm、Demand
and move This Period Max/Min to Last Reset Max/Min, also recode reset time. Clear This Period
Max/Min
Demand Reset:Clear Demand data, restart Demand Interval
Period Reset:Move This Period Max/Min data to Last Reset Max/Min, record reset time, and clear
This Period Max/Min data
Meter R-Hour Reset:Clear Meter R-Hour data
Load R-Hour Reset:Clear Load R-Hour data
7.2.2 Basic Setup
7.2.2.1 Communication
Modbus
Please refer to the modbus format and parameters in the chapter 8
Baud Rate:Default is 19200
CM1 Unit ID (1~255):RS485 Modbus ID address, default is 15
Stop Bit:bit to signal the end of communication, depending on PC side. Default is 1
Parity Bit:The total number of bit is always either odd or even, therefore it can be checked
during the communication. Default is none
Ethernet
IP Address:The IP address of SPM-8, “xxx.xxx.xxx.xxx” is required, here xxx is 0-255
Port No.:Port no. has been defined as 502 or 503, please select 502 or 503
Subnet Mask:If subnet was used, host and subnet IP address are required, please use
“xxx.xxx.xxx.xxx” to set
Gateway:Gateway is used to enter other internet, “xxx.xxx.xxx.xxx” is required
Mac Address:It is a fixed number, can not be changed(xx-xx-xx-xx-xx-xx, 0-FF)
19
7.2.2.2 Measurement
Volts Mode:If auto is selected, the wiring method will be detected automatically. Default is Auto
PT Primary:60~600000(primary voltage)
PT Secondary:1~600(secondary voltage)
CT Primary:1~5000(primary max. current)
CT Secondary:1~5(secondary max. current)
Frequency:50 or 60 Hz. Default is 60Hz
kWh Direction:Bi-Direction/Single Direction(default)
7.2.2.3 Security
If password can not be recalled, please contact your local dealer. You can press “Enter” and “ key”
at the same time to reset every parameter to default values including password. The default value
of password is “0000000”, 7 digits.
Press
keys to move the desired position,
keys can change the numerical or alphabetic letters
in the selected position
7.2.2.4 Alarm Set Point
Enable/Disable
To enable or disable the alarm setting, if enable is selected, it will be recorded as an event when the
alarm was triggered.
Sag/Swell Limit
Sag Limit
Sag limit can be set between 80 to 100%, “%” is the unit used. When measured voltage is lower than
the sag limit setting but no longer than 1 min. continuously, it will be treated as “Voltage Sag”. If
longer than 1 min., it will be recorded as “Low Voltage”. Use
keys to change the setting value.
Swell Limit
Swell limit will be set between 100~120%. When the measure voltage is high than the swell limit
compared to primary voltage setting, for less than 1 min. it is treated as “voltage swell”. If longer
than 1 min., it will be recorded as “Over Voltage”. Use
keys to chang the setting value.
Sag and Swell will be stored in their record, and will not be shown as an alarm event.
Ref. Primary Voltage
Reference Voltage for sag and swell to compare with. (60~600000)
Alarm Set Point
20
Events due to alarm can be read through communication as defined in the following table:
Item
Description
0x10
Over Current Phase A Alarm
0x11
Over Current Phase B Alarm
0x12
Over Current Phase C Alarm
0x13
Over Current Neutral Alarm
0x14
Current Unbalance Alarm
0x15
Current Loss Alarm
0x20
Over Current Phase A Condition Clear
0x21
Over Current Phase B Condition Clear
0x22
Over Current Phase C Condition Clear
0x23
Over Current Neutral Condition Clear
0x24
Current Unbalance Condition Clear
0x25
Current Loss Condition Clear
0x30
0x31
0x32
0x33
0x34
0x35
0x36
0x37
0x40
0x41
0x42
0x43
0x44
0x45
0x46
0x47
Over Voltage Phase A Alarm
Over Voltage Phase B Alarm
Over Voltage Phase C Alarm
Under Voltage Phase A Alarm
Under Voltage Phase B Alarm
Under Voltage Phase C Alarm
Voltage Unbalance Alarm
Voltage Loss Alarm
Over Voltage Phase A Condition Clear
Over Voltage Phase B Condition Clear
Over Voltage Phase C Condition Clear
Under Voltage Phase A Condition Clear
Under Voltage Phase B Condition Clear
Under Voltage Phase C Condition Clear
Voltage Unbalance Condition Clear
Voltage Loss Condition Clear
0x50
0x51
0x52
0x53
0x54
0x55
0x60
0x61
0x62
0x63
0x64
0x65
THD
THD
THD
THD
THD
THD
THD
THD
THD
THD
THD
THD
0x70
Over kW Dmd Alarm
x80
Over kW Dmd Alarm Condition Clear
Va Alarm
Vb Alarm
Vc Alarm
Ia Alarm
Ib Alarm
Ic Alarm
Va Alarm Condition Clear
Vb Alarm Condition Clear
Vc Alarm Condition Clear
Ia Alarm Condition Clear
Ib Alarm Condition Clear
Ic Alarm Condition Clear
21
V Unbal Alarm
The range of V unbal Alarm alarm limit can be set between 0~10%. Comparing voltage of any phase
with the average value of all three phase, if the ratio is greater than the set limit, the alarm will be
triggered. As the ratio become lower than the set limit, alarm will be cleared.
I Unbal Alarm
The range of I unbal Alarm alarm limit can be set between 0~10%. Comparing current of any phase
with the average value of all three phase, if the ratio is greater than the set limit, the alarm will be
triggered. As the ratio become lower than the set limit, alarm will be cleared.
V/I THD Alarm
Toal harmonic distortion can be set between 0~50%.
Over I Phase Alarm
The overI phase limit can be set between 0~9999 of primary current. As the current of any phase is
over the set limit, alarm triggered. When the over I phase is below the limit, alarm cleared.
Over I Neutral Alarm
The over I neutral alarm can be set between 0-9999 of primary current. As the I neutral is over the
set limit, alarm triggered. When the I neutral is below the set limit, alarm cleared.
I Loss Alarm
I loss alarm value can be set between 0-5000 of primary current. As only one or two I phase is below
the alarm setting value, alarm triggered. However, when all three I phase is either greater or lower
than the limit, alarm cleared.
V Loss Alarm
V loss alarm value can be set between 0-6000 of primary voltage. As only one or two V phase is
below the alarm setting value, alarm triggered. However, when all three V phase is either greater or
lower than the limit, alarm cleared.
Over KW Alarm
The demand limit can be set between 0-65535, default value is 0.
7.2.2.5 Clock Setup
Date and time will be setup here for use in daily report and regular report and event logging. They
will be shown as yy/mm/dd and hh:mm:ss.
7.2.2.6 Digital Output
2 channels of digital output for alarm output and pulse output.
Digital Output 1
22
DO1 is desinated as the alarm output, and can be selected from the list
Digital Output 2
The output item can be none, kWh, kVARh, kVAh.
Pulse output: default is 10(1~6000), equals 1kWh.
7.2.2.7 Analog Output
4 channels of 4-20mA setting, can be assigned to V, I, kW, kVA or kVAR
Data measured from secondary V, I, kW, kVA or kVAR;4-20mA are corresponding to the value each
items are:
Each phase (A,B.C phase): V:0~600V
three phase (ΣL): V:0~600V
I:0~5A
I:0~5A
kW:0~3 kWatt
kW:0~9 kWatt (total)
kvar:0~3 kVAr
kvar:0~9 kVAr (total)
kVA:0~3 kVA
kVA:0~9 kVA (total)
For each analog output, users can choose item like V, I and phase like A, B, all.
Output(Phase)
Once None is chosen, the channel can be used as outpit assigned by communication from upper
control software.
Output(Item)
Selected output item。
7.2.2.8 Analog input
AI high value can be from 0-65535, and the corresponding external input is 20mA;low value can be
from 0-65535, and the corresponding external value is 4mA.
7.2.2.9 Demand Setup
23
Mode
Block
Calculation updates at the end of the interval
15-minute interval
15
20
25
15-minute interval
30
35
15-min
Time
(min)
40
Block Mode
Rolling
Calculation updates at the end of the subinterval
15-minute interval
15
20
25
30
35
40
45
Time
(min)
Rolling
No. of Subinterval
The No. of subinterval is only needed for Rolling mode, can be 1, 2, 3, 4, 5, 6,10,12,15
Subinterval Length
Function for both Block and Rolling mode. In block mode, it stands for the total interval time.(No.
of subinterval is always 1). In rolling mode, it stands for only lenght of the subinterval time, the total
interval time will be No. of subinterval times the subinterval length.
24
7.2.2.10 Period Reset
The function of period reset is designed to move the max/min data happened in one current month
to last period, and clearn all the max/min data in this month period for the new coming max/min
data except the energy data. Energy data will be not reset, instead it will be accumulated.
Mode
When manual is selected, the reset action will be triggered only the reset all or period reset in clear
function has been applied.
If auto is selected, users will also be asked to enter the date. The system will perform the move and
clear action at the date assigned every month.
If date is 2, then at date 2 and 00:00:00 period reset will be excuted.
If date is 1, then at date 1 and 00:00:00 period reset will be excuted.
If date is 31, then only the month with 31st period reset will be excuted at 31st 00:00:00. However,
those months without 31st, period reset will excuted at 1st 00:00:00 next month.
7.2.3 Display Setup
Auto Scroll:Can be set between 1-6 sec. or disable. Default is disable.
Backlight Timeout:Can be set between 1~99 min.
Runtime:This setting allows users to select what to display and not to display during the
runtime mode. Run time mode display setting is as following:
Language:English
Contrast:Can be set between 0-20, default is 10.
Item
Setup
Voltage
L-L Voltage
L-N Voltage
Line Current
Active Power
Power
Apparent
Power
Reactive
Power
Power Factor
● Disable
● Enable
Energy
Demand
Status
7.3 Report
25
7.3.1 Daily Report
Every day at 00:00:00, data in today will move to yesterday and clear today’s record except energy
data will be accumulated.
7.3.2 Diagnostic
In this section, only max/ min and when they happened in one month period has been stored. The
reset will then move this period data to last reset data and clear this period data except energy data.
This Period
Item
Setup
Current Time
Date:
Time:
Max/Min Va
Max/Min Vb
Max
Max/Min Vc
Date:
Max/Min Ia
Time:
Max/Min Ib
Max/Min Ic
Min
Max/Min KWa
Date:
Max/Min KWb
Time:
Max/Min KWc
Max/Min KVAa
Max/Min KVAb
Max/Min KVAc
Min PFa
Min
Date:
Min PFb
Time:
Min PFc
Max VaTHD
Max
Max VbTHD
Date:
Max VcTHD
Time:
Max IaTHD
Max IbTHD
Max IcTHD
Max Demand
26
Last Reset
Item
Current Time
Max/Min Va
Max/Min Vb
Max/Min Vc
Max/Min Ia
Max/Min Ib
Max/Min Ic
Max/Min KWa
Max/Min KWb
Max/Min KWc
Max/Min KVAa
Max/Min KVAb
Max/Min KVAc
Min PFa
Min PFb
Min PFc
Max VaTHD
Max VbTHD
Max VcTHD
Max IaTHD
Max IbTHD
Max IcTHD
Max Demand
Energy
Setup
Date:
Time:
Max
Date:
Time:
Min
Date:
Time:
Min
Date:
Time:
Max
Date:
Time:
del:
rec:
tot:
7.3.3 Harmonics
Item
Va Harmonics
Vb Harmonics
Vc Harmonics
Ia Harmonics
Ib Harmonics
Ic Harmonics
Report Chart
7.3.4 Current on alarm
If no current alarm is on, none will be shown. In this instrument up to eight items will be set to alarm
as following:
V Unbal Alarm
I Unbal Alarm
THD Alarm
I THD Alarm
27
Over V Alarm
Under V Alarm
Over I Alarm
I Loss Alarm
V Loss Alarm
Over KW Dmd Alarm
7.3.5 Event log
In this event log section, up to 20 lastest record has been recorded.
7.3.5.1 Sag Record
No:to select the sag record from 1 to 20 using
keys
Cycle:sag cycles between 0-65535
Data:sag percentage between -327.68%-327.67%
Phase:A/B/C phase voltage
Begin:begin date and time
End:end date and time
7.3.5.2 Swell record
No:to select the swell record from 1 to 20 using
keys
Cycle:swell cycles between 0-65535
Data:swell percentage between -327.68%-327.67%
Phase:A/B/C phase voltage
Begin:begin date and time
End:end date and time
7.3.5.3 Alarm Record
No:to select the alarm record from 1 to 20 using
keys
Item:items can be current voltage…etc., as listed in the table of page 27
Data:percentage between -327.68%-327.67%
Date:date of accruing
Time:time of accuring
28
7.3.6 Analog Input
The AI option was originally setup by entering high value and low value to correspond 4-20mA input.
In this report section, users can observe the input data for each channel.
7.3.7 Nameplate Info
7.3.8 Runing Hour
Meter Running Hour and Load Running Hour
29
Chapter 8 Communication format
8.1 RS485
8.1.1 RS485 standard
PARAMETERS
Mode of Operation
Number of Drivers and Receives
Maximum cable length( meters)
Maximum data rate ( baud )
Maximum common mode voltage ( Volts )
Maximum Driver Output Levels ( Loaded )
Maximum Driver Output Levels ( Unloaded )
Drive Load ( Ohms)
Driver Output short circuit Resistance ( kohms)
Minimum receiver input Resistance ( kohms)
Receiver sensitivity
Differential
32 Drivers / 32 Receivers
1200
10M
12 to -7
+/- 1.5
+/- 6
60( min )
150 to Gnd, 250 to -7 or 12V
12
+/- 200mv
8.1.2 Wiring for instruments communication
RS485communication must used twisted paired wire, as show in the following program. “D+”
connect to one wire and “D-” to the other one
Master
DD+
Slave
D-
Slave
D+
D-
D+
Slave
D-
D+
120 ohm
120 ohm
Cautions :
.There must be no more than two wires connected to each terminal, this ensures
that a “Daisy Chain” or “Straight Line” configuration is used. A “star” or a network
with “Stubs(Tees)” is not recommended as reflections within the cable may result in
data corruption。
30
8.2 Modbus
In the start of modus communication, master will issu a “Query” to the slave. Every slaves will
monitor the “Query” address, so as to “execute’ or give “response” when the address is right
8.2.1 Modbus Format
The Query-Response Cycle
Slave 1
Slave 2
Slave 3
Slave n
Master
Query
Response
Query message from Master
Device Address
Device Address
Function Code
Function Code
8 bit Data Bytes
8 bit Data Bytes
Error Check
Error Check
Response messages from Slave
31
8.3 Communication protocol
SPM-8 use Modus RTU as the communication protocol. The following shows Query and Response
format.
Query:
Slave
Address
Function
Code
0x03,
0x04
Response:
Slave
Function
Address Code
0x03,
0x04
Query:
Slave
Addres
s
Functio
n Code
0x10
Response:
Slave
Function
Address
Code
0x10
Start
Address
(Hi)
Byte
Count
Start
Addres
s (Hi)
Start
Address
(Lo)
Number
of Points
(Hi)
Data
(Hi)
Data
(Lo)
Start
Address
(Lo)
Number
of
Points
(Hi)
Start
Address
(Hi)
Start
Address
(Lo)
Number
of Points
(Lo)
Error
Check
(Lo)
Number
of
Points
(Lo)
Number
of Points
(Hi)
32
Byte
Coun
t
Number
of Points
(Lo)
Error
Check
(Lo)
Error
Check
(Hi)
Error
Check
(Hi)
Data
(Hi)
Error
Check
(Lo)
Data
(Lo)
Error
Check
(Lo)
Error
Check
(Hi)
Error
Check
(Hi)
8.4 IEEE 754 Format
The bits in an IEEE 754 format have the following significance:
Data Hi Word,
Data Hi Word,
Data Lo Word,
Data Lo Word,
Hi Byte
Lo Byte
Hi Byte
Lo Byte
SEEE EEEE
EMMM MMMM
MMMM MMMM
MMMM MMMM
Where:
S represents the sign bit where 1 is negative and 0 is positive
E is the two’s complement exponent with an offset of 127 i.e. an exponent of zero is represented
by 127, an exponent of 1 by 128 etc.
M is the 23-bit normal mantissa. The highest bit is always 1 and, therefore, is not stored.
For each floating point value requested two MODBUS_ registers or points (four bytes) must be
requested. The received order and significance of these four bytes for the Integral products is shown
below:
Data Lo Word,
Data Lo Word,
Data Hi Word,
Data Hi Word,
Hi Byte
Lo Byte
Hi Byte
Lo Byte
8.5 Modbus RTU Mode
Since Controllers can be setup to communicate on standard Modbus networks using either of two
transmission modes:ASCII or RTU. SPM-8 uses RTU transmission mode only. Users select the RTU
mode, along with the serial port communication parameters( baud rate, parity mode, etc ), during
configuration of each controller. The mode and serial parameters must be the same for all devices on
a Modbus connection.
RTU Mode
Coding System
8-bit binary, hexadecimal 0-9, A-F
Bits per Byte
1
8
1
1
Error Check Field
Cyclical Redundancy Check(CRC)
Two hexadecimal character contained in each 8-bit field of
the message
start bit
data bits, least significant bit sent first
bit for even/odd parity;no bit for no parity
stop bit if parity is used;2 bits if no parity
33
8.6 Modbus Function Code
The function code of a Modbus message defines the action to be taken by the slave.
Function code use by SPM-8 is described below:
Code
Modbus name
03
Read Holding Registers
Description
Read the content of read/write location
( 4X
reference )
04
Read Input Registers
Read the contents of read only location
( 3X
reference )
16
Pre-set Multiple
Set the contents of read/write location
Registers
reference )
Note: The maximum registers of Function 03 &Function 04 is 125
34
( 4X
8.7 Detail parameter
Modbus Module #0 Coil Status : Digital Output
Parameter name
Digital Output 1
Digital Output 2
Modbus
Register
00000
00001
Comment
for function code 01: Read Coil Status & 05 : Force Single Coil
for function code 01: Read Coil Status & 05 : Force Single Coil
Modbus Module #1 Holding Register : Digital Output
Modbus Register
Parameter name
Modicom
Format
Len
Data
Type
Range
Default
value
bit 0 : Digital Output 1
bit 1 : Digital Output 2
0
Hex
Digital Output
44097
0x1000
Word
UInt
Digital_Output_Reserved
44098
0x1001
Word
UInt
Units
Comment
Modbus Module #2 Holding Register : Setup Parameter
Modbus Register
Parameter name
Modicom
Format
Len
Hex
Data
Type
Comm_485_BaudRate
44099
0x1002
Word
UInt
Comm_485_Address
44100
0x1003
Word
UInt
Comm_485_StopBit
44101
0x1004
Word
UInt
Comm_485_Parity
44102
0x1005
Word
UInt
Reserved
Ethernet_IP_0*
Ethernet_IP_1*
Ethernet_IP_2*
Ethernet_IP_3*
Ethernet_PortNo*
Subnet_Mask_0*
Subnet_Mask _1*
Subnet_Mask _2*
Subnet_Mask _3*
Gateway_0*
Gateway_1*
Gateway_2*
Gateway_3*
Mac_Address_1*
Mac_Address_2*
Mac_Address_3*
Mac_Address_4*
Mac_Address_5*
Mac_Address_6*
44103
0x1006
44104
0x1007
44105
0x1008
44106
0x1009
44107
0x100A
44108
0x100B
44109
0x100C
44110
0x100D
44111
0x100E
44112
0x100F
44113
0x1010
Word
Hi B
Lo B
Hi B
Lo B
Word
Hi B
Lo B
Hi B
Lo B
Hi B
Lo B
Hi B
Lo B
Hi B
Lo B
Hi B
Lo B
Hi B
Lo B
UInt
Byte
Byte
Byte
Byte
UInt
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Hi B
Byte
Lo B
Byte
DWord
Word
Word
Word
Word
Word
Volts_Mode
PT_Primary
PT_Secondary
CT_Primary
CT_Secondary
Frequency
Demand_Mode*
44114
4411544116
44117
44118
44119
44120
44121
0:
2:
4:
6:
1200 , 1: 2400 ,
4800 , 3: 9600 ,
19200, 5:38400
57600
1-255
0:1 Stop bit,
1:2 Stop bit
0:No, 1:Even,
2:Odd
Default
value
Units
4
bps
0
0
192
168
1
210
0
255
255
255
0
0
0
0
0
00
18
D8
0
0
0
Float
60-600000
110
Volts
UInt
UInt
UInt
UInt
UInt
1-600
1-5000
1-5
0:50Hz, 1:60Hz
0:Block, 1:Rolling
110
1
1
1
0
Volts
Amp.
Amp.
35
Comment
15
0-255
0-255
0-255
0-255
0:502, 1:503
0-255
0-255
0-255
0-255
0-255
0-255
0-255
0-255
0-ffh
0-ffh
0-ffh
0-ffh
0-ffh
0-ffh
Volts Mode at
present
0 : 1P2W ,
1 : 1P3W ,
2 : 3P3W_Delta 2CT,
3 : 3P3W_Delta 3CT,
4 : 3P4W_Wye ,
5 : Auto
0x1011
0x10120x1013
0x1014
0x1015
0x1016
0x1017
0x1018
Range
optional
optional
optional
optional
optional
optional
optional
optional
optional
optional
optional
optional
optional
optional
optional
optional
optional
optional
optional
5
1,2,3,4,5,6,10,12,1
5
1,2,3,4,5,6,10,12,1
5,20,30,60
1
Number_of_Subinterval*
44122
0x1019
Word
UInt
Demand_Subinterval_
Length*
44123
0x101A
Word
UInt
Password
4412444125
0x101B0x101C
DWord
Uint3
2
0xxxxxxxh
Over_kW_Dmd_Limit*
44126
0x101D
Word
UInt
0-65535
65535
kW.
Over_kW_Dmd_Clear*
44127
0x101E
Word
UInt
0-65535
0
kW.
Alarm_Enable
44128
0x101F
Word
UInt
0 : disable , 1 :
enable
0
SAG_Limit
44129
0x1020
Word
UInt
Range : 80% 100%
100
%
SWELL_Limit
44130
0x1021
Word
UInt
Range : 100% 120%
100
%
Reference_Primary_Volta
ge
4413144132
0x10220x1023
DWord
Float
60-600000
110
Volts
Voltage_Unbal_Limit
44133
0x1024
Word
UInt
Range : 0% - 10%
10
%
Current_Unbal_Limit
44134
0x1025
Word
UInt
Range : 0% - 10%
10
%
Hi B
Byte
Range : 0% - 50%
50
%
44135
0x1026
Lo B
Byte
Range : 0% - 50%
50
%
I_THD_Limit*
V_THD_Limit*
15
Min
0000000
Over_Current_Phase_Li
mit
44136
0x1027
Word
UInt
0-9999
9999
Amp.
Over_Current_Neutral
_Limit
44137
0x1028
Word
UInt
0-9999
9999
Amp.
Current_Loss_Limit
44138
0x1029
Word
UInt
0-5000
0
Amp.
Voltage_Loss_Limit
4413944140
0x102A
DWord
Float
0-600000
0
Volts
Voltage_Unbal_Clear
44141
0x102B
Word
UInt
Range : 0% - 10%
1
%
Current_Unbal_ Clear
44142
0x102C
Word
UInt
Range : 0% - 10%
1
%
Hi B
Byte
Range : 0% - 50%
1
%
44143
0x102D
Lo B
Byte
Range : 0% - 50%
1
%
I_THD_ Clear*
V_THD_ Clear*
Over_Current_Phase_
Clear
44144
0x102E
Word
UInt
0-9999
0
Amp.
Over_Current_Neutral _
Clear
44145
0x102F
Word
UInt
0-9999
0
Amp.
Current_Loss_ Clear
44146
0x1030
Word
UInt
0-5000
0
Amp.
Voltage_Loss_ Clear
4414744148
0x10310x1032
DWord
Float
0-600000
0
Volts
36
For Over kW
Dmd alarm
For Over kW
Dmd alarm
clear
For Sag &
UnderVoltag
e alarm
For Swell &
OverVoltage
alarm
For
Sag/Swell &
Under/Over
Voltage
For Voltage
unbalance
alarm
For Current
unbalance
alarm
For I THD
alarm
For V THD
alarm
For Over
Current
Phase alarm
For Over
Current
Neutral
alarm
For Phase
Loss-Current
alarm
For Phase
Loss-Voltage
alarm
For Voltage
unbalance
alarm clear
For Current
unbalance
alarm clear
For I THD
alarm
For V THD
alarm clear
For Over
Current
Phase alarm
clear
For Over
Current
Neutral
alarm clear
For Phase
Loss-Current
alarm clear
For Phase
Loss-Voltage
alarm clear
0 : None
1 : Voltage
unbalance alarm
2 : Current
unbalance alarm
3 : Over Voltage
alarm
4 : Under Voltage
alarm
5 : Over Current
alarm
6 : Current Loss
alarm
7 : Voltage Loss
alarm
8 : Any
0 : None
1 : Voltage
unbalance alarm
2 : Current
unbalance alarm
3 : V THD alarm*
4 : Over Voltage
alarm
5 : Under Voltage
alarm
6 : Over Current
alarm
7 : Current Loss
alarm
8 : Voltage Loss
alarm
9 : Over kW Dmd
alarm*
10: I THD alarm*
11: Any
0
for standard
0
for advance
DO1_Select_Item
44149
0x1033
Word
Uint
DO1_Select_Item*
44149
0x1034
Word
Uint
44150
0x1035
Hi B
Byte
Reserved
Lo B
Byte
AO1_Select_Phase
Hi B
Byte
0:None, 1:A phase,
2:B phase, 3:C
phase, 4:Total
0
optional
AO1_Select_ Item
Lo B
Byte
0:V, 1:I , 2:kW ,
3:kvar, 4:kVA
0
optional
AO2_Select_Phase
Hi B
Byte
0:None, 1:A phase,
2:B phase, 3:C
phase, 4:Total
0
optional
AO2_Select_ Item
Lo B
Byte
0:V, 1:I , 2:kW ,
3:kvar, 4:kVA
0
optional
AO3_Select_Phase
Hi B
Byte
0:None, 1:A phase,
2:B phase, 3:C
phase, 4:Total
0
optional
AO3_Select_ Item
Lo B
Byte
0:V, 1:I , 2:kW ,
3:kvar, 4:kVA
0
optional
AO4_Select_Phase
Hi B
Byte
0:None, 1:A phase,
2:B phase, 3:C
phase, 4:Total
0
optional
Lo B
Byte
0:V, 1:I , 2:kW ,
3:kvar, 4:kVA
0
optional
Word
Hi B
Lo B
UInt
Byte
Byte
0 - 6 sec
1 - 99 min
0
1
DO2_Select_Item
44151
44152
44153
44154
0x1036
0x1037
0x1038
0x1039
AO4_Select_ Item
Reserved
Display_Auto_Scroll
Display_BK_Timeout
44155
0x103A
44156
0x103B
37
0 : None , 1 : kWh
2 : kvarh , 3 : kVAh
0
0
Runtime_Screen_Set
44157
0x103C
Word
UInt
Byte
Byte
UInt
UInt
UInt
UInt
UInt
UInt
UInt
UInt
UInt
UInt
UInt
UInt
UInt
UInt
UInt
Reset_Mode*
Reset_Date*
Reserved
AI1_Eng_High
AI1_Eng_Low
AI2_Eng_High
AI2_Eng_Low
AI3_Eng_High
AI3_Eng_Low
AI4_Eng_High
AI4_Eng_Low
Reserved
Reserved
AO1_Set_Value
AO2_Set_Value
AO3_Set_Value
AO4_Set_Value
44158
0x103D
44159
44160
44161
44162
44163
44164
44165
44166
44167
44168
44169
44170
44171
44172
44173
0x103E
0x103F
0x1040
0x1041
0x1042
0x1043
0x1044
0x1045
0x1046
0x1047
0x1048
0x1049
0x104A
0x104B
0x104C
Hi B
Lo B
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Language
44174
0x104D
Word
UInt
kWh_Direction
44175
0x104E
Word
UInt
Contrast
44176
0x104F
Word
UInt
Bit=0 : Disable
Bit=1 : Enable
bit 0 : Phase Voltage
bit 1 : Line Voltage
bit 2 : Line Current
bit 3 : Active Power
bit 4 : Apparent
Power
bit 5 : Reactive
Power
bit 6 : Power Factor
bit 7 : Energy
bit 8 : Demand*
bit 9 : Status
0:Manual, 1:Auto
1~31
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0 : English
1 : Secondary
Language
0 : Single direction
1 : Bi-direction
0 ~20
2ff/3ff
0
1
65535
0
65535
0
65535
0
65535
0
optional
optional
optional
optional
optional
optional
optional
optional
0
0
0
0
optional
optional
optional
optional
1
0: SPM-8-0
1: SPM-8-1
10
Modbus Module #2-1 Holding Register : Setup Parameter
Modbus Register
Parameter name
AO_Wtot_High_Limit
Modicom
Format
44300
Len
Data
Type
Word
UInt
Hex
0x10CB
Default
value
Units
9000
W
Range
Default
value
Units
1200 , 1: 2400 ,
4800 , 3: 9600 ,
19200, 5:38400
57600
4
bps
Range
0~9000
Comment
secondary
Modbus Module #2-2 Holding Register : Setup Parameter
Modbus Register
Parameter name
Modico
m
Format
Len
Hex
Data
Type
Snd_485_BaudRate*
44353
0x1100
Word
UInt
0:
2:
4:
6:
Snd_485_Address*
44354
0x1101
Word
UInt
1-255
Snd_485_StopBit*
44355
0x1102
Word
UInt
0:1 Stop bit,
1:2 Stop bit
0
Snd_485_Parity*
44356
0x1103
Word
UInt
0:No, 1:Even, 2:Odd
0
DO2_Select_Kh
44357
0x1104
Word
UInt
1-6000
Comment
16
10
Modbus Module #3 Holding Register : Realtime Clock
Parameter name
Modbus Register
Len
Data
Type
38
Range
Default
value
Units
Comment
Year
Month
Date
Hour
Min
Second
Modicom
Format
44177
44178
44179
44180
44181
44182
Hex
0x1050
0x1051
0x1052
0x1053
0x1054
0x1055
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
Modbus Module #4 Holding Register : Clear Function
Modbus Register
Parameter name
Reset_ Daily*
Reset_ Energy
Reset _Sag _Record*
Reset_Swell_Record*
Reset_Sag_Swell_Record
*
Reset_Alarm_Record*
Reset_to_Default
Reset_All*
Reset_Demand*
Period_Reset*
Len
Data
Type
Range
Default
value
0x1060
0x1061
0x1062
0x1063
Word
Word
Word
Word
UInt
Uint
Uint
Uint
0x5aa5
0x5aa5
0x5aa5
0x5aa5
0
0
0
0
0x5aa5:
0x5aa5:
0x5aa5:
0x5aa5:
44197
0x1064
Word
Uint
0x5aa5
0
0x5aa5: clear
44198
44199
44200
44201
44202
0x1065
0x1066
0x1067
0x1068
0x1069
Word
Word
Word
Word
Word
Uint
Uint
Uint
Uint
Uint
0x5aa5
0x5aa5
0x5aa5
0x5aa5
0x5aa5
0
0
0
0
0
0x5aa5:
0x5aa5:
0x5aa5:
0x5aa5:
0x5aa5:
Modicom
Format
44193
44194
44195
44196
Hex
Units
Comment
clear
clear
clear
clear
clear
clear
clear
clear
clear
Modbus Module #5 Holding Register : Alarm Counter*
Modbus Register
Len
Data
Type
Range
0x1070
0x1071
0x1072
Word
Word
Word
Uint
Uint
Uint
0-20
0-20
0-20
44212
0x1073
Word
Uint
0-20
Sag_Total_Counter
44213
0x1074
Word
Uint
0-20
Swell_Total_Counter
44214
0x1075
Word
Uint
0-20
Parameter name
Alarm_New_Counter
Sag_New_Counter
Swell_New_Counter
Modicom
Format
44209
44210
44211
Alarm_Total_Counter
Hex
Default
value
Units
Comment
Current total accumulates(up
to 20 data)
Current total accumulates(up
to 20 data)
Current total accumulates(up
to 20 data)
Modbus Module #6 Input Register : Digital Output
Modbus Register
Parameter name
Modicom
Format
Len
Data
Type
Range
Default
value
bit 0 : Digital Output 1
bit 1 : Digital Output 2
0
Hex
Digital Output
34097
0x1000
Word
UInt
Digital_Output_Reserved
34098
0x1001
Word
UInt
Units
Comment
Units
Comment
Modbus Module #7 Input Register : Digital Intput
Modbus Register
Parameter name
Digital Input
Modicom
Format
34099
Len
Hex
0x1002
Word
Data
Type
UInt
39
Default
value
Range
bit
bit
bit
bit
bit
bit
bit
bit
bit
bit
0
1
2
3
4
5
6
7
8
9
:
:
:
:
:
:
:
:
:
:
Digital
Digital
Digital
Digital
Digital
Digital
Digital
Digital
Digital
Digital
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
1
2
3
4
5
6
7
8
9
10
bit 10 : Digital Input 11
bit 11 : Digital Input 12
Digital_Input_Reserved
34100
0x1003
Word
UInt
Modbus Module #8 Input Register : Alarm Counter*
Modbus Register
Len
Data
Type
Range
0x1004
0x1005
0x1006
Word
Word
Word
UInt
UInt
UInt
0-20
0-20
0-20
34104
0x1007
Word
UInt
0-20
Sag_Total_Counter
34105
0x1008
Word
UInt
0-20
Swell_Total_Counter
34106
0x1009
Word
UInt
0-20
Parameter name
Alarm_New_Counter
Sag_New_Counter
Swell_New_Counter
Modicom
Format
34101
34102
34103
Alarm_Total_Counter
Hex
Default
value
Units
Comment
Current total accumulates(up
to 20 data)
Current total accumulates(up
to 20 data)
Current total accumulates(up
to 20 data)
Modbus Module #9 Input Register : Realtime Data Voltage, Current, Frequency (Float)
Modbus Register
Parameter name
Vln_a
Vln_b
Vln_c
Vln_avg
Vll_ab
Vll_bc
Vll_ca
Vll_avg
I_a
I_b
I_c
I_avg
I_n
Freq
Modicom
Format
3410734108
3410934110
3411134112
3411334114
3411534116
3411734118
3411934120
3412134122
3412334124
3412534126
3412734128
3412934130
3413134132
3413334134
Data
Type
Range
DWord
Float
Primary Voltage
Volts
DWord
Float
Primary Voltage
Volts
DWord
Float
Primary Voltage
Volts
DWord
Float
Primary Voltage
Volts
DWord
Float
Primary Voltage
Volts
DWord
Float
Primary Voltage
Volts
DWord
Float
Primary Voltage
Volts
DWord
Float
Primary Voltage
Volts
DWord
Float
Primary Current
Amp.
DWord
Float
Primary Current
Amp.
DWord
Float
Primary Current
Amp.
DWord
Float
Primary Current
Amp.
DWord
Float
Primary Current
Amp.
DWord
Float
Hex
0x100A0x100B
0x100C0x100D
0x100E0x1000F
0x10100x1011
0x10120x1013
0x10140x1015
0x10160x1017
0x10180x1019
0x101A0x101B
0x101C0x101D
0x101E0x101F
0x10200x1021
0x10220x1023
0x10240x1025
Default
value
Len
Units
Hz
Comment
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
Modbus Module #10 Input Register : Realtime Data Power Result (Float)
Modbus Register
Parameter name
KW_a
KW_b
KW_c
KW_tot
KVAR_a
Modicom
Format
3413534136
3413734138
3413934140
3414134142
34143-
Len
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Hex
0x10260x1027
0x10280x1029
0x102A0x102B
0x102C0x102D
0x102E-
40
Range
Default
value
Units
Comment
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
KVAR_b
KVAR_c
KVAR_tot
KVA_a
KVA_b
KVA_c
KVA_tot
34144
3414534146
3414734148
3414934150
3415134152
3415334154
3415534156
3415734158
0x102F
0x10300x1031
0x10320x1033
0x10340x1035
0x10360x1037
0x10380x1039
0x103A0x103B
0x103C0x103D
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
Modbus Module #11 Input Register : Realtime Data Power Factor(True) & Phase Angle
(Float)
Modbus Register
Parameter name
PF_true_a
PF_true_b
PF_true_c
PF_true_avg
PhaseAngle_V_a
PhaseAngle_V_b
PhaseAngle_V_c
PhaseAngle_I_a
PhaseAngle_I_b
PhaseAngle_I_c
Pre_Demand_KW*
Reserved
Reserved
Modicom
Format
3415934160
3416134162
3416334164
3416534166
3416734168
3416934170
3417134172
3417334174
3417534176
3417734178
3417934180
3418134182
3418334184
Len
Hex
0x103E0x103F
0x10400x1041
0x10420x1043
0x10440x1045
0x10460x1047
0x10480x1049
0x104A0x104B
0x104C0x104D
0x104E0x104F
0x10500x1051
0x10520x1053
0x10540x1055
0x10560x1057
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Range
Default
value
Units
Comment
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
Modbus Module #12 Input Register : Realtime Data Energy (Float)
Modbus Register
Parameter name
KWH_del
KWH_rec
KWH_tot
KWH_net
KVARH_ lagging
KVARH_ leading
KVARH_tot
Modicom
Format
3418534186
3418734188
3418934190
3419134192
3419334194
3419534196
3419734198
Len
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Hex
0x10580x1059
0x105A0x105B
0x105C0x105D
0x105E0x105F
0x10600x1061
0x10620x1063
0x10640x1065
41
Range
Default
value
Units
Comment
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
KVARH_net
KVAH
3419934200
3420134202
0x10660x1067
0x10680x1069
DWord
Float
DWord
Float
with Runtime
display
Modbus Module #13 Input Register : Realtime data Demand-1*
Modbus Register
Parameter name
Demand_KW*
Demand_Remain_Time*
Modicom
Format
3420334204
34205
Len
Data
Type
DWord
Float
Word
UInt
Hex
0x106A0x106B
0x106C
Range
Default
value
Units
Comment
sec
Modbus Module #14 Input Register : AI Result(optional)
Modbus Register
Parameter name
Modicom
Format
Len
Hex
Data
Type
Range
AI1 Value
34206
0x106D
Word
UInt
0~65535
AI2 Value
34207
0x106E
Word
UInt
0~65535
AI3 Value
34208
0x106F
Word
UInt
0~65535
AI4 Value
34209
0x1070
Word
UInt
0~65535
Default
value
Units
Comment
Default
value
Units
Comment
Modbus Module #15 Input Register : Fundamental PF*
Modbus Register
Parameter name
PF_Fundamental_a
PF_Fundamental_b
PF_Fundamental_c
PF_Fundamental_d
Modicom
Format
3421034211
3421234213
3421434215
3421634217
Len
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Hex
0x10710x1072
0x10730x1074
0x10750x1076
0x10770x1078
Range
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
Modbus Module #13-1 Input Register : Realtime data Demand-2*
Modbus Register
Parameter name
Pre_Demand_kW
Demand_kW
Pre_Demand_kvar
Demand_kvar
Pre_Demand_kVA
Demand_kVA
Demand_Remain_Time
Modicom
Format
3422234223
3422434225
3422634227
3422834229
3423034231
3423234233
34234
Len
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Word
UInt
Hex
0x107D0x107E
0x107F0x1080
0x10810x1082
0x10830x1084
0x10850x1086
0x10870x1088
0x1089
Range
Default
value
Units
Comment
sec
Modbus Module #16-1 Input Register : kWh used Report *
Parameter name
Modbus Register
Len
Data
Type
42
Range
Default
value
Units
Comment
KWH_used_Yesterday
KWH_used_LastReset
Modicom
Format
3460534606
3460734608
Hex
0x11FC0x11FD
0x11FE0x11FF
DWord
Float
DWord
Float
Modbus Module #16 Input Register : Daily Report This Day Max/Min*
Modbus Register
Parameter name
KWH_del_DT
KWH_rec_DT
KWH_tot_DT
KW_tot_max_DT
KW_tot_max_DT_Year
KW_tot_max_DT_Month
KW_tot_max_DT_Date
KW_tot_max_DT_Hour
KW_tot_max_DT_Min
KW_tot_max_DT_Second
KW_tot_min_DT
KW_tot_min_DT_Year
KW_tot_min_DT_Month
KW_tot_min_DT_Date
KW_tot_min_DT_Hour
KW_tot_min_DT_Min
KW_tot_min_DT_Second
Vavg_max_DT
Vavg_max_DT_Year
Vavg_max_DT_Month
Vavg_max_DT_Date
Vavg_max_DT_Hour
Vavg_max_DT_Min
Vavg_max_DT_Second
Vavg_min_DT
Vavg_min_DT_Year
Vavg_min_DT_Month
Vavg_min_DT_Date
Vavg_min_DT_Hour
Vavg_min_DT_Min
Vavg_min_DT_Second
Iavg_max_DT
Iavg_max_DT_Year
Iavg_max_DT_Month
Iavg_max_DT_Date
Iavg_max_DT_Hour
Iavg_max_DT_Min
Iavg_max_DT_Second
Iavg_min_DT
Iavg_min_DT_Year
Iavg_min_DT_Month
Iavg_min_DT_Date
Iavg_min_DT_Hour
Iavg_min_DT_Min
Iavg_min_DT_Second
Demand_max_DT
Demand_max_DT_Year
Modicom
Format
3460934610
3461134612
3461334614
3461534616
34617
34618
34619
34620
34621
34622
3462334624
34625
34626
34627
34628
34629
34630
3463134632
34633
34634
34635
34636
34637
34638
3463934640
34641
34642
34643
34644
34645
34646
3464734648
34649
34650
34651
34652
34653
34654
3465534656
34657
34658
34659
34660
34661
34662
3466334664
34665
Len
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
BCD
Hex
0x12000x1201
0x12020x1203
0x12040x1205
0x12060x1207
0x1208
0x1209
0x120A
0x120B
0x120C
0x120D
0x120E0x120F
0x1210
0x1211
0x1212
0x1213
0x1214
0x1215
0x12160x1217
0x1218
0x1219
0x121A
0x121B
0x121C
0x121D
0x121E0x121F
0x1220
0x1221
0x1222
0x1223
0x1224
0x1225
0x12260x1227
0x1228
0x1229
0x122A
0x122B
0x122C
0x122D
0x122E0x122F
0x1230
0x1231
0x1232
0x1233
0x1234
0x1235
0x12360x1237
0x1238
43
Range
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
Default
value
Units
Comment
Demand_max_DT_Month
Demand_max_DT_Date
Demand_max_DT_Hour
Demand_max_DT_Min
Demand_max_DT_Secon
d
34666
34667
34668
34669
0x1239
0x123A
0x123B
0x123C
Word
Word
Word
Word
BCD
BCD
BCD
BCD
1-12
1-31
0-23
0-59
34670
0x123D
Word
BCD
0-59
Modbus Module #17 Input Register : Daily Report Yesterday Max/Min*
Modbus Register
Parameter name
KWH_del_DY
KWH_rec_DY
KWH_tot_DY
KW_tot_max_DY
KW_tot_max_DY_Year
KW_tot_max_DY_Month
KW_tot_max_DY_Date
KW_tot_max_DY_Hour
KW_tot_max_DY_Min
KW_tot_max_DY_Secon
d
KW_tot_min_DY
KW_tot_min_DY_Year
KW_tot_min_DY_Month
KW_tot_min_DY_Date
KW_tot_min_DY_Hour
KW_tot_min_DY_Min
KW_tot_min_DY_Second
Vavg_max_DY
Vavg_max_DY_Year
Vavg_max_DY_Month
Vavg_max_DY_Date
Vavg_max_DY_Hour
Vavg_max_DY_Min
Vavg_max_DY_Second
Vavg_min_DY
Vavg_min_DY_Year
Vavg_min_DY_Month
Vavg_min_DY_Date
Vavg_min_DY_Hour
Vavg_min_DY_Min
Vavg_min_DY_Second
Iavg_max_DY
Iavg_max_DY_Year
Iavg_max_DY_Month
Iavg_max_DY_Date
Iavg_max_DY_Hour
Iavg_max_DY_Min
Iavg_max_DY_Second
Iavg_min_DY
Iavg_min_DY_Year
Iavg_min_DY_Month
Iavg_min_DY_Date
Iavg_min_DY_Hour
Iavg_min_DY_Min
Iavg_min_DY_Second
Demand_max_DY
Modicom
Format
3467134672
3467334674
3467534676
3467734678
34679
34680
34681
34682
34683
0x123E0x123F
0x12400x1241
0x12420x1243
0x12440x1245
0x1246
0x1247
0x1248
0x1249
0x124A
34684
0x124B
3468534686
34687
34688
34689
34690
34691
34692
3469334694
34695
34696
34697
34698
34699
34700
3470134702
34703
34704
34705
34706
34707
34708
3470934710
34711
34712
34713
34714
34715
34716
3471734718
34719
34720
34721
34722
34723
34724
3472534726
0x124C0x124D
0x124E
0x124F
0x1250
0x1251
0x1252
0x1253
0x12540x1255
0x1256
0x1257
0x1258
0x1259
0x125A
0x125B
0x125C0x125D
0x125E
0x125F
0x1260
0x1261
0x1262
0x1263
0x12640x1265
0x1266
0x1267
0x1268
0x1269
0x126A
0x126B
0x126C0x126D
0x126E
0x126F
0x1270
0x1271
0x1272
0x1273
0x12740x1275
Len
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
00-99
1-12
1-31
0-23
0-59
Word
BCD
0-59
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Hex
44
Range
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
Default
value
Units
Comment
Demand_max_DY_Year
Demand_max_DY_Month
Demand_max_DY_Date
Demand_max_DY_Hour
Demand_max_DY_Min
Demand_max_DY_Secon
d
34727
34728
34729
34730
34731
0x1276
0x1277
0x1278
0x1279
0x127A
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
00-99
1-12
1-31
0-23
0-59
34732
0x127B
Word
BCD
0-59
Modbus Module #18 Input Register : Diagnostic This Period Max/Min*
Modbus Register
Parameter name
Va_max_TP
Va_max_TP_Year
Va_max_TP_Month
Va_max_TP_Date
Va_max_TP_Hour
Va_max_TP_Min
Va_max_TP_Second
Va_min_TP
Va_min_TP_Year
Va_min_TP_Month
Va_min_TP_Date
Va_min_TP_Hour
Va_min_TP_Min
Va_min_TP_Second
Vb_max_TP
Vb_max_TP_Year
Vb_max_TP_Month
Vb_max_TP_Date
Vb_max_TP_Hour
Vb_max_TP_Min
Vb_max_TP_Second
Vb_min_TP
Vb_min_TP_Year
Vb_min_TP_Month
Vb_min_TP_Date
Vb_min_TP_Hour
Vb_min_TP_Min
Vb_min_TP_Second
Vc_max_TP
Vc_max_TP_Year
Vc_max_TP_Month
Vc_max_TP_Date
Vc_max_TP_Hour
Vc_max_TP_Min
Vc_max_TP_Second
Vc_min_TP
Vc_min_TP_Year
Vc_min_TP_Month
Vc_min_TP_Date
Vc_min_TP_Hour
Vc_min_TP_Min
Vc_min_TP_Second
Ia_max_TP
Ia_max_TP_Year
Ia_max_TP_Month
Ia_max_TP_Date
Ia_max_TP_Hour
Ia_max_TP_Min
Modicom
Format
3473334734
34735
34736
34737
34738
34739
34740
3474134742
34743
34744
34745
34746
34747
34748
3474934750
34751
34752
34753
34754
34755
34756
3475734758
34759
34760
34761
34762
34763
34764
3476534766
34767
34768
34769
34770
34771
34772
3477334774
34775
34776
34777
34778
34779
34780
3478134782
34783
34784
34785
34786
34787
Len
Data
Type
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
Hex
0x127C0x127D
0x127E
0x127F
0x1280
0x1281
0x1282
0x1283
0x12840x1285
0x1286
0x1287
0x1288
0x1289
0x128A
0x128B
0x128C0x128D
0x128E
0x128F
0x1290
0x1291
0x1292
0x1293
0x12940x1295
0x1296
0x1297
0x1298
0x1299
0x129A
0x129B
0x129C0x129D
0x129E
0x129F
0x12A0
0x12A1
0x12A2
0x12A3
0x12A40x12A5
0x12A6
0x12A7
0x12A8
0x12A9
0x12AA
0x12AB
0x12AC0x12AD
0x12AE
0x12AF
0x12B0
0x12B1
0x12B2
45
Range
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
Default
value
Units
Comment
Ia_max_TP_Second
Ia_min_TP
Ia_min_TP_Year
Ia_min_TP_Month
Ia_min_TP_Date
Ia_min_TP_Hour
Ia_min_TP_Min
Ia_min_TP_Second
Ib_max_TP
Ib_max_TP_Year
Ib_max_TP_Month
Ib_max_TP_Date
Ib_max_TP_Hour
Ib_max_TP_Min
Ib_max_TP_Second
Ib_min_TP
Ib_min_TP_Year
Ib_min_TP_Month
Ib_min_TP_Date
Ib_min_TP_Hour
Ib_min_TP_Min
Ib_min_TP_Second
Ic_max_TP
Ic_max_TP_Year
Ic_max_TP_Month
Ic_max_TP_Date
Ic_max_TP_Hour
Ic_max_TP_Min
Ic_max_TP_Second
Ic_min_TP
Ic_min_TP_Year
Ic_min_TP_Month
Ic_min_TP_Date
Ic_min_TP_Hour
Ic_min_TP_Min
Ic_min_TP_Second
KWa_max_TP
KWa_max_TP_Year
KWa_max_TP_Month
KWa_max_TP_Date
KWa_max_TP_Hour
KWa_max_TP_Min
KWa_max_TP_Second
KWa_min_TP
KWa_min_TP_Date
KWa_min_TP_Month
KWa_min_TP_Date
KWa_min_TP_Hour
KWa_min_TP_Min
KWa_min_TP_Second
KWb_max_TP
KWb_max_TP_Year
KWb_max_TP_Month
KWb_max_TP_Date
KWb_max_TP_Hour
KWb_max_TP_Min
KWb_max_TP_Second
KWb_min_TP
KWb_min_TP_Year
KWb_min_TP_Month
KWb_min_TP_Date
34788
3478934790
34791
34792
34793
34794
34795
34796
3479734798
34799
34800
34801
34802
34803
34804
3480534806
34807
34808
34809
34810
34811
34812
3481334814
34815
34816
34817
34818
34819
34820
3482134822
34823
34824
34825
34826
34827
34828
3482934830
34831
34832
34833
34834
34835
34836
3483734838
34839
34840
34841
34842
34843
34844
3484534846
34847
34848
34849
34850
34851
34852
3485334854
34855
34856
34857
0x12B3
0x12B40x12B5
0x12B6
0x12B7
0x12B8
0x12B9
0x12BA
0x12BB
0x12BC0x12BD
0x12BE
0x12BF
0x12C0
0x12C1
0x12C2
0x12C3
0x12C40x12C5
0x12C6
0x12C7
0x12C8
0x12C9
0x12CA
0x12CB
0x12CC0x12CD
0x12CE
0x12CF
0x12D0
0x12D1
0x12D2
0x12D3
0x12D40x12D5
0x12D6
0x12D7
0x12D8
0x12D9
0x12DA
0x12DB
0x12DC0x12DD
0x12DE
0x12DF
0x12E0
0x12E1
0x12E2
0x12E3
0x12E40x12E5
0x12E6
0x12E7
0x12E8
0x12E9
0x12EA
0x12EB
0x12EC0x12ED
0x12EE
0x12EF
0x12F0
0x12F1
0x12F2
0x12F3
0x12F40x12F5
0x12F6
0x12F7
0x12F8
Word
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
BCD
BCD
BCD
46
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
KWb_min_TP_Hour
KWb_min_TP_Min
KWb_min_TP_Second
KWc_max_TP
KWc_max_TP_Year
KWc_max_TP_Month
KWc_max_TP_Date
KWc_max_TP_Hour
KWc_max_TP_Min
KWc_max_TP_Second
KWc_min_TP
KWc_min_TP_Year
KWc_min_TP_Month
KWc_min_TP_Date
KWc_min_TP_Hour
KWc_min_TP_Min
KWc_min_TP_Second
KVAa_max_TP
KVAa_max_TP_Year
KVAa_max_TP_Month
KVAa_max_TP_Date
KVAa_max_TP_Hour
KVAa_max_TP_Min
KVAa_max_TP_Second
KVAa_min_TP
KVAa_min_TP_Year
KVAa_min_TP_Month
KVAa_min_TP_Date
KVAa_min_TP_Hour
KVAa_min_TP_Min
KVAa_min_TP_Second
KVAb_max_TP
KVAb_max_TP_Year
KVAb_max_TP_Month
KVAb_max_TP_Date
KVAb_max_TP_Hour
KVAb_max_TP_Min
KVAb_max_TP_Second
KVAb_min_TP
KVAb_min_TP_Year
KVAb_min_TP_Month
KVAb_min_TP_Date
KVAb_min_TP_Hour
KVAb_min_TP_Min
KVAb_min_TP_Second
KVAc_max_TP
KVAc_max_TP_Year
KVAc_max_TP_Month
KVAc_max_TP_Date
KVAc_max_TP_Hour
KVAc_max_TP_Min
KVAc_max_TP_Second
KVAc_min_TP
KVAc_min_TP_Year
KVAc_min_TP_Month
KVAc_min_TP_Date
KVAc_min_TP_Hour
KVAc_min_TP_Min
KVAc_min_TP_Second
PFa_min_TP
PFa_min_TP_Year
34858
34859
34860
3486134862
34863
34864
34865
34866
34867
34868
3486934870
34871
34872
34873
34874
34875
34876
3487734878
34879
34880
34881
34882
34883
34884
3488534886
34887
34888
34889
34890
34891
34892
3489334894
34895
34896
34897
34898
34899
34900
3490134902
34903
34904
34905
34906
34907
34908
3490934910
34911
34912
34913
34914
34915
34916
3491734918
34919
34920
34921
34922
34923
34924
3492534926
34927
0x12F9
0x12FA
0x12FB
0x12FC0x12FD
0x12FE
0x12FF
0x1300
0x1301
0x1302
0x1303
0x13040x1305
0x1306
0x1307
0x1308
0x1309
0x130A
0x130B
0x130C0x130D
0x130E
0x130F
0x1310
0x1311
0x1312
0x1313
0x13140x1315
0x1316
0x1317
0x1318
0x1319
0x131A
0x131B
0x131C0x131D
0x131E
0x131F
0x1320
0x1321
0x1322
0x1323
0x13240x1325
0x1326
0x1327
0x1328
0x1329
0x132A
0x132B
0x132C0x132D
0x132E
0x132F
0x1330
0x1331
0x1332
0x1333
0x13340x1335
0x1336
0x1337
0x1338
0x1339
0x133A
0x133B
0x133C0x133D
0x133E
Word
Word
Word
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
BCD
47
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
PFa_min_TP_Month
PFa_min_TP_Date
PFa_min_TP_Hour
PFa_min_TP_Min
PFa_min_TP_Second
PFb_min_TP
PFb_min_TP_Year
PFb_min_TP_Month
PFb_min_TP_Date
PFb_min_TP_Hour
PFb_min_TP_Min
PFb_min_TP_Second
PFc_min_TP
PFc_min_TP_Year
PFc_min_TP_Month
PFc_min_TP_Date
PFc_min_TP_Hour
PFc_min_TP_Min
PFc_min_TP_Second
VaTHD_max_TP
VaTHD_max_TP_Year
VaTHD_max_TP_Month
VaTHD_max_TP_Date
VaTHD_max_TP_Hour
VaTHD_max_TP_Min
VaTHD_max_TP_Second
VbTHD_max_TP
VbTHD_max_TP_Year
VbTHD_max_TP_Month
VbTHD_max_TP_Date
VbTHD_max_TP_Hour
VbTHD_max_TP_Min
VbTHD_max_TP_Second
VcTHD_max_TP
VcTHD_max_TP_Year
VcTHD_max_TP_Month
VcTHD_max_TP_Date
VcTHD_max_TP_Hour
VcTHD_max_TP_Min
VcTHD_max_TP_Second
IaTHD_max_TP
IaTHD_max_TP_Year
IaTHD_max_TP_Month
IaTHD_max_TP_Date
IaTHD_max_TP_Hour
IaTHD_max_TP_Min
IaTHD_max_TP_Second
IbTHD_max_TP
IbTHD_max_TP_Year
IbTHD_max_TP_Month
IbTHD_max_TP_Date
IbTHD_max_TP_Hour
IbTHD_max_TP_Min
IbTHD_max_TP_Second
IcTHD_max_TP
IcTHD_max_TP_Year
IcTHD_max_TP_Month
IcTHD_max_TP_Date
IcTHD_max_TP_Hour
IcTHD_max_TP_Min
IcTHD_max_TP_Second
Demand_max_TP
34928
34928
34930
34931
34932
3493334934
34935
34935
34937
34938
34939
34940
3494134942
34943
34944
34945
34946
34947
34948
3494934950
34951
34952
34953
34954
34955
34956
3495734958
34959
34960
34961
34962
34963
34964
3496534966
34967
34968
34969
34970
34971
34972
3497334974
34975
34976
34977
34978
34979
34980
3498134982
34983
34984
34985
34986
34987
34988
3498934990
34991
34992
34993
34994
34995
34996
34997-
0x133F
0x1340
0x1341
0x1342
0x1343
0x13440x1345
0x1346
0x1347
0x1348
0x1349
0x134A
0x134B
0x134C0x134D
0x134E
0x134F
0x1350
0x1351
0x1352
0x1353
0x13540x1355
0x1356
0x1357
0x1358
0x1359
0x135A
0x135B
0x135C0x135D
0x135E
0x135F
0x1360
0x1361
0x1362
0x1363
0x13640x1365
0x1366
0x1367
0x1368
0x1369
0x136A
0x136B
0x136C0x136D
0x136E
0x136F
0x1370
0x1371
0x1372
0x1373
0x13740x1375
0x1376
0x1377
0x1378
0x1379
0x137A
0x137B
0x137C0x137D
0x137E
0x137F
0x1380
0x1381
0x1382
0x1383
0x1384-
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
DWord
BCD
BCD
BCD
BCD
BCD
BCD
Float
48
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
Demand_max_TP_Year
Demand_max_TP_Month
Demand_max_TP_Date
Demand_max_TP_Hour
Demand_max_TP_Min
Demand_max_TP_Secon
d
34998
34999
35000
35001
35002
35003
0x1385
0x1386
0x1387
0x1388
0x1389
0x138A
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
2000-2099
1-12
1-31
0-23
0-59
35004
0x138B
Word
BCD
0-59
Modbus Module #19 Input Register : Diagnostic Last Reset Max/Min*
Modbus Register
Parameter name
LR_Year
LR_Month
LR_Date
LR_Hour
LR_Min
LR_Second
Va_max_LR
Va_max_LR_Year
Va_max_LR_Month
Va_max_LR_Date
Va_max_LR_Hour
Va_max_LR_Min
Va_max_LR_Second
Va_min_LR
Va_min_LR_Year
Va_min_LR_Month
Va_min_LR_Date
Va_min_LR_Hour
Va_min_LR_Min
Va_min_LR_Second
Vb_max_LR
Vb_max_LR_Year
Vb_max_LR_Month
Vb_max_LR_Date
Vb_max_LR_Hour
Vb_max_LR_Min
Vb_max_LR_Second
Vb_min_LR
Vb_min_LR_Year
Vb_min_LR_Month
Vb_min_LR_Date
Vb_min_LR_Hour
Vb_min_LR_Min
Vb_min_LR_Second
Vc_max_LR
Vc_max_LR_Year
Vc_max_LR_Month
Vc_max_LR_Date
Vc_max_LR_Hour
Vc_max_LR_Min
Vc_max_LR_Second
Vc_min_LR
Vc_min_LR_Year
Vc_min_LR_Month
Vc_min_LR_Date
Vc_min_LR_Hour
Vc_min_LR_Min
Vc_min_LR_Second
Modicom
Format
35005
35006
35007
35008
3509
35010
3501135012
35013
35014
35015
35016
35017
35018
3501935020
35021
35022
35023
35024
35025
35026
3502735028
35029
35030
35031
35032
35033
35034
3503535036
35037
35038
35039
35040
35041
35042
3504335044
35045
35046
35047
35048
35049
35050
3505135052
35053
35054
35055
35056
35057
35058
Len
Data
Type
Range
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
00-99
1-12
1-31
0-23
0-59
0-59
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
Hex
0x138C
0x138D
0x138E
0x138F
0x1390
0x1391
0x13920x1393
0x1394
0x1395
0x1396
0x1397
0x1398
0x1399
0x139A0x139B
0x139C
0x139D
0x139E
0x139F
0x13A0
0x13A1
0x13A20x13A3
0x13A4
0x13A5
0x13A6
0x13A7
0x13A8
0x13A9
0x13AA0x13AB
0x13AC
0x13AD
0x13AE
0x13AF
0x13B0
0x13B1
0x13B20x13B3
0x13B4
0x13B5
0x13B6
0x13B7
0x13B8
0x13B9
0x13BA0x13BB
0x13BC
0x13BD
0x13BE
0x13BF
0x13C0
0x13C1
49
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
Default
value
Units
Comment
Ia_max_LR
Ia_max_LR_Year
Ia_max_LR_Month
Ia_max_LR_Date
Ia_max_LR_Hour
Ia_max_LR_Min
Ia_max_LR_Second
Ia_min_LR
Ia_min_LR_Year
Ia_min_LR_Month
Ia_min_LR_Date
Ia_min_LR_Hour
Ia_min_LR_Min
Ia_min_LR_Second
Ib_max_LR
Ib_max_LR_Year
Ib_max_LR_Month
Ib_max_LR_Date
Ib_max_LR_Hour
Ib_max_LR_Min
Ib_max_LR_Second
Ib_min_LR
Ib_min_LR_Year
Ib_min_LR_Month
Ib_min_LR_Date
Ib_min_LR_Hour
Ib_min_LR_Min
Ib_min_LR_Second
Ic_max_LR
Ic_max_LR_Year
Ic_max_LR_Month
Ic_max_LR_Date
Ic_max_LR_Hour
Ic_max_LR_Min
Ic_max_LR_Second
Ic_min_LR
Ic_min_LR_Year
Ic_min_LR_Month
Ic_min_LR_Date
Ic_min_LR_Hour
Ic_min_LR_Min
Ic_min_LR_Second
KWa_max_LR
KWa_max_LR_Year
KWa_max_LR_Month
KWa_max_LR_Date
KWa_max_LR_Hour
KWa_max_LR_Min
KWa_max_LR_Second
KWa_min_LR
KWa_min_LR_Date
KWa_min_LR_Month
KWa_min_LR_Date
KWa_min_LR_Hour
KWa_min_LR_Min
KWa_min_LR_Second
KWb_max_LR
KWb_max_LR_Year
KWb_max_LR_Month
KWb_max_LR_Date
KWb_max_LR_Hour
3505935060
35061
35062
35063
35064
35065
35066
3506735068
35069
35070
35071
35072
35073
35074
3507535076
35077
35078
35079
35080
35081
35082
3508335084
35085
35086
35087
35088
35089
35090
3509135092
35093
35094
35095
35096
35097
35098
3509935100
35101
35102
35103
35104
35105
35106
3510735108
35109
35110
35111
35112
35113
35114
3511535116
35117
35118
35119
35120
35121
35122
3512335124
35125
35126
35127
35128
0x13C20x13C3
0x13C4
0x13C5
0x13C6
0x13C7
0x13C8
0x13C9
0x13CA0x13CB
0x13CC
0x13CD
0x13CE
0x13CF
0x13D0
0x13D1
0x13D20x13D3
0x13D4
0x13D5
0x13D6
0x13D7
0x13D8
0x13D9
0x13DA0x13DB
0x13DC
0x13DD
0x13DE
0x13DF
0x13E0
0x13E1
0x13E20x13E3
0x13E4
0x13E5
0x13E6
0x13E7
0x13E8
0x13E9
0x13EA0x13EB
0x13EC
0x13ED
0x13EE
0x13EF
0x13F0
0x13F1
0x13F20x13F3
0x13F4
0x13F5
0x13F6
0x13F7
0x13F8
0x13F9
0x13FA0x13FB
0x13FC
0x13FD
0x13FE
0x13FF
0x1400
0x1401
0x14020x1403
0x1404
0x1405
0x1406
0x1407
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
BCD
BCD
BCD
BCD
50
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
KWb_max_LR_Min
KWb_max_LR_Second
KWb_min_LR
KWb_min_LR_Year
KWb_min_LR_Month
KWb_min_LR_Date
KWb_min_LR_Hour
KWb_min_LR_Min
KWb_min_LR_Second
KWc_max_LR
KWc_max_LR_Year
KWc_max_LR_Month
KWc_max_LR_Date
KWc_max_LR_Hour
KWc_max_LR_Min
KWc_max_LR_Second
KWc_min_LR
KWc_min_LR_Year
KWc_min_LR_Month
KWc_min_LR_Date
KWc_min_LR_Hour
KWc_min_LR_Min
KWc_min_LR_Second
KVAa_max_LR
KVAa_max_LR_Year
KVAa_max_LR_Month
KVAa_max_LR_Date
KVAa_max_LR_Hour
KVAa_max_LR_Min
KVAa_max_LR_Second
KVAa_min_LR
KVAa_min_LR_Year
KVAa_min_LR_Month
KVAa_min_LR_Date
KVAa_min_LR_Hour
KVAa_min_LR_Min
KVAa_min_LR_Second
KVAb_max_LR
KVAb_max_LR_Year
KVAb_max_LR_Month
KVAb_max_LR_Date
KVAb_max_LR_Hour
KVAb_max_LR_Min
KVAb_max_LR_Second
KVAb_min_LR
KVAb_min_LR_Year
KVAb_min_LR_Month
KVAb_min_LR_Date
KVAb_min_LR_Hour
KVAb_min_LR_Min
KVAb_min_LR_Second
KVAc_max_LR
KVAc_max_LR_Year
KVAc_max_LR_Month
KVAc_max_LR_Date
KVAc_max_LR_Hour
KVAc_max_LR_Min
KVAc_max_LR_Second
KVAc_min_LR
KVAc_min_LR_Year
KVAc_min_LR_Month
35129
35130
3513135132
35133
35134
35135
35136
35137
35138
3513935140
35141
35142
35143
35144
35145
35146
3514735148
35149
35150
35151
35152
35153
35154
3515535156
35157
35158
35159
35160
35161
35162
3516335164
35165
35166
35167
35168
35169
35170
3517135172
35173
35174
35175
35176
35177
35178
3517935180
35181
35182
35183
35184
35185
35186
3518735188
35189
35190
35191
35192
35193
35194
3519535196
35197
35198
0x1408
0x1409
0x140A0x140B
0x140C
0x140D
0x140E
0x140F
0x1410
0x1411
0x14120x1413
0x1414
0x1415
0x1416
0x1417
0x1418
0x1419
0x141A0x141B
0x141C
0x141D
0x141E
0x141F
0x1420
0x1421
0x14220x1423
0x1424
0x1425
0x1426
0x1427
0x1428
0x1429
0x142A0x142B
0x142C
0x142D
0x142E
0x142F
0x1430
0x1431
0x14320x1433
0x1434
0x1435
0x1436
0x1437
0x1438
0x1439
0x143A0x143B
0x143C
0x143D
0x143E
0x143F
0x1440
0x1441
0x14420x1443
0x1444
0x1445
0x1446
0x1447
0x1448
0x1449
0x144A0x144B
0x144C
0x144D
Word
Word
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
BCD
BCD
51
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
KVAc_min_LR_Date
KVAc_min_LR_Hour
KVAc_min_LR_Min
KVAc_min_LR_Second
PFa_min_LR
PFa_min_LR_Year
PFa_min_LR_Month
PFa_min_LR_Date
PFa_min_LR_Hour
PFa_min_LR_Min
PFa_min_LR_Second
PFb_min_LR
PFb_min_LR_Year
PFb_min_LR_Month
PFb_min_LR_Date
PFb_min_LR_Hour
PFb_min_LR_Min
PFb_min_LR_Second
PFc_min_LR
PFc_min_LR_Year
PFc_min_LR_Month
PFc_min_LR_Date
PFc_min_LR_Hour
PFc_min_LR_Min
PFc_min_LR_Second
VaTHD_max_LR
VaTHD_max_LR_Year
VaTHD_max_LR_Month
VaTHD_max_LR_Date
VaTHD_max_LR_Hour
VaTHD_max_LR_Min
VaTHD_max_LR_Second
VbTHD_max_LR
VbTHD_max_LR_Year
VbTHD_max_LR_Month
VbTHD_max_LR_Date
VbTHD_max_LR_Hour
VbTHD_max_LR_Min
VbTHD_max_LR_Second
VcTHD_max_LR
VcTHD_max_LR_Year
VcTHD_max_LR_Month
VcTHD_max_LR_Date
VcTHD_max_LR_Hour
VcTHD_max_LR_Min
VcTHD_max_LR_Second
IaTHD_max_LR
IaTHD_max_LR_Year
IaTHD_max_LR_Month
IaTHD_max_LR_Date
IaTHD_max_LR_Hour
IaTHD_max_LR_Min
IaTHD_max_LR_Second
IbTHD_max_LR
IbTHD_max_LR_Year
IbTHD_max_LR_Month
IbTHD_max_LR_Date
IbTHD_max_LR_Hour
IbTHD_max_LR_Min
IbTHD_max_LR_Second
IcTHD_max_LR
35199
35200
35201
35202
3520335204
35205
35206
35207
35208
35209
35210
3521135212
35213
35214
35215
35216
35217
35218
3521935220
35221
35222
35223
35224
35225
35226
3522735228
35229
35230
35231
35232
35233
35234
3523535236
35237
35238
35239
35240
35241
35242
3524335244
35245
35246
35247
35248
35249
35250
3525135252
35253
35254
35255
35256
35257
35258
3525935260
35261
35262
35263
35264
35265
35266
3526735268
0x144E
0x144F
0x1450
0x1451
0x14520x1453
0x1454
0x1455
0x1456
0x1457
0x1458
0x1459
0x145A0x145B
0x145C
0x145D
0x145E
0x145F
0x1460
0x1461
0x14620x1463
0x1464
0x1465
0x1466
0x1467
0x1468
0x1469
0x146A0x146B
0x146C
0x146D
0x146E
0x146F
0x1470
0x1471
0x14720x1473
0x1474
0x1475
0x1476
0x1477
0x1478
0x1479
0x147A0x147B
0x147C
0x147D
0x147E
0x147F
0x1480
0x1481
0x14820x1483
0x1484
0x1485
0x1486
0x1487
0x1488
0x1489
0x148A0x148B
0x148C
0x148D
0x148E
0x148F
0x1490
0x1491
0x14920x1493
Word
Word
Word
Word
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
DWord
Float
52
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
00-99
1-12
1-31
0-23
0-59
0-59
IcTHD_max_LR_Year
IcTHD_max_LR_Month
IcTHD_max_LR_Date
IcTHD_max_LR_Hour
IcTHD_max_LR_Min
IcTHD_max_LR_Second
Demand_max_LR
Demand_max_LR_Year
Demand_max_LR_Month
Demand_max_LR_Date
Demand_max_LR_Hour
Demand_max_LR_Min
Demand_max_LR_Secon
d
KWH_del_LR
KWH_rec_LR
KWH_tot_LR
35269
35270
35271
35272
35273
35274
3527535276
35277
35278
35279
35280
35281
0x1494
0x1495
0x1496
0x1497
0x1498
0x1499
0x149A0x149B
0x149C
0x149D
0x149E
0x149F
0x14A0
35282
0x14A1
3528335284
3528535286
3528735288
0x14A20x14A3
0x14A40x14A5
0x14A60x14A7
Word
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
BCD
00-99
1-12
1-31
0-23
0-59
0-59
DWord
Float
Word
Word
Word
Word
Word
BCD
BCD
BCD
BCD
BCD
2000-2099
1-12
1-31
0-23
0-59
Word
BCD
0-59
DWord
Float
DWord
Float
DWord
Float
Modbus Module #20 Input Register : Event Log Sag Record*
Modbus Register
Len
Data
Type
0x14A8
Word
UINT
35290
0x14A9
Word
INT
Sag01_Phase
35291
0x14AA
Word
UINT
Sag01_Start_Time
3529235297
0x14AB0x14B0
Word x
6
Date
&
Time
(BCD)
Parameter name
Sag01_Duration_Cycles
Modicom
Format
35289
Sag01_Data
Hex
Sag01_End_Time
3529835303
0x14B10x14B6
Word x
6
Date
&
Time
(BCD)
Sag02_Duration_Cycles
35304
0x14B7
Word
UINT
Sag02_Data
35305
0x14B8
Word
INT
Sag02_Phase
35306
0x14B9
Word
UINT
Sag02_Start_time
3530735312
0x14BA0x14BF
Word x
6
Date
&
Time
(BCD)
Word x
6
Date
&
Time
(BCD)
Sag02_End_time
3531335318
0x14C00x14C5
Sag03_Duration_Cycles
35319
0x14C6
Word
UINT
Sag03_Data
35320
0x14C7
Word
INT
Sag03_Phase
35321
0x14C8
Word
UINT
53
Range
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Default
value
Units
Comment
Sag03_Start_time
3532235327
0x14C90x14CE
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Sag03_End_time
3532835333
0x14CF0x14D4
Word x
6
Date
&
Time
(BCD)
Sag04_Duration_Cycles
35334
0x14D5
Word
UINT
Sag04_Data
35335
0x14D6
Word
INT
Sag04_Phase
35336
0x14D7
Word
UINT
Sag04_Start_time
3533735342
0x14D80x14DD
Word x
6
Date
&
Time
(BCD)
Sag04_End_time
3534335348
0x14DE0x14E3
Word x
6
Date
&
Time
(BCD)
Sag05_Duration_Cycles
35349
0x14E4
Word
UINT
Sag05_Data
35350
0x14E5
Word
INT
Sag05_Phase
35351
0x14E6
Word
UINT
Sag05_Start_time
3535235357
0x14E70x14EC
Word x
6
Date
&
Time
(BCD)
Word x
6
Date
&
Time
(BCD)
Sag05_End_time
3535835363
0x14ED0x14F2
Sag06_Duration_Cycles
35364
0x14F3
Word
UINT
Sag06_Data
35365
0x14F4
Word
INT
Sag06_Phase
35366
0x14F5
Word
UINT
Sag06_Start_time
3536735372
0x14F60x14FB
Word x
6
Date
&
Time
(BCD)
Sag06_End_time
3537335378
0x14FC0x1501
Word x
6
Date
&
Time
(BCD)
Sag07_Duration_Cycles
35379
0x1502
Word
UINT
Sag07_Data
35380
0x1503
Word
INT
Sag07_Phase
35381
0x1504
Word
UINT
54
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Sag07_Start_time
3538235387
0x15050x150A
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Sag07_End_time
3538835393
0x150B0x1510
Word x
6
Date
&
Time
(BCD)
Sag08_Duration_Cycles
35394
0x1511
Word
UINT
Sag08_Data
35385
0x1512
Word
INT
Sag08_Phase
35396
0x1513
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Sag08_Start_time
Sag08_End_time
3539735402
3540335408
0x15140x1519
0x151A0x151F
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Sag09_Duration_Cycles
35409
0x1520
Word
UINT
Sag09_Data
35410
0x1521
Word
INT
Sag09_Phase
35411
0x1522
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Sag09_Start_time
3541235417
0x15230x1528
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Sag09_End_time
3541835423
0x15290x152E
Word x
6
Date
&
Time
(BCD)
Sag10_Duration_Cycles
35424
0x152F
Word
UINT
Sag10_Data
35425
0x1530
Word
INT
Sag10_Phase
35426
0x1531
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Sag10_Start_time
3542735432
0x15320x1537
Sag10_End_time
3543335438
0x15380x153D
Word x
6
Date
&
Time
(BCD)
Sag11_Duration_Cycles
35439
0x153E
Word
UINT
Sag11_Data
35440
0x153F
Word
INT
Sag11_Phase
35441
0x1540
Word
UINT
55
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Sag11_Start_time
3544235447
0x15410x1546
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Sag11_End_time
3544835453
0x15470x154C
Word x
6
Date
&
Time
(BCD)
Sag12_Duration_Cycles
35454
0x154D
Word
UINT
Sag12_Data
35455
0x154E
Word
INT
Sag12_Phase
35456
0x154F
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Sag12_Start_time
Sag12_End_time
3545735462
3546335468
0x15500x1555
0x15560x155B
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Sag13_Duration_Cycles
35469
0x155C
Word
UINT
Sag13_Data
35470
0x155D
Word
INT
Sag13_Phase
35471
0x155E
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Sag13_Start_time
3547235477
0x155F0x1564
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Sag13_End_time
3547835483
0x15650x156A
Word x
6
Date
&
Time
(BCD)
Sag14_Duration_Cycles
35484
0x156B
Word
UINT
Sag14_Data
35485
0x156C
Word
INT
Sag14_Phase
35486
0x156D
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Sag14_Start_time
3548735492
0x156E0x1573
Sag14_End_time
3549335498
0x15740x1579
Word x
6
Date
&
Time
(BCD)
Sag15_Duration_Cycles
35499
0x157A
Word
UINT
56
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Sag15_Data
35500
0x157B
Word
INT
Sag15_Phase
35501
0x157C
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Sag15_Start_time
3550235507
0x157D0x1582
Sag15_End_time
3550835513
0x15830x1588
Word x
6
Date
&
Time
(BCD)
Sag16_Duration_Cycles
35514
0x1589
Word
UINT
Sag16_Data
35515
0x158A
Word
INT
Sag16_Phase
35516
0x158B
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Sag16_Start_time
Sag16_End_time
3551735522
3552335528
0x158C0x1591
0x15920x1597
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Sag17_Duration_Cycles
35529
0x1598
Word
UINT
Sag17_Data
35530
0x1599
Word
INT
Sag17_Phase
35531
0x159A
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Sag17_Start_time
Sag17_End_time
3553235537
3553835543
0x159B0x15A0
0x15A10x15A6
Sag18_Duration_Cycles
35544
0x15A7
Word
UINT
Sag18_Data
35545
0x15A8
Word
INT
Sag18_Phase
35546
0x15A9
Word
UINT
Word x
6
Date
&
Time
(BCD)
Sag18_Start_time
3554735552
0x15AA0x15AF
57
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Sag18_End_time
3555335558
0x15B00x15B5
Word x
6
Date
&
Time
(BCD)
Sag19_Duration_Cycles
35559
0x15B6
Word
UINT
Sag19_Data
35560
0x15B7
Word
INT
Sag19_Phase
35561
0x15B8
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Sag19_Start_time
Sag19_End_time
3556235567
3556835573
0x15B90x15BE
0x15BF0x15C4
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Sag20_Duration_Cycles
35574
0x15C5
Word
UINT
Sag20_Data
35575
0x15C6
Word
INT
Sag20_Phase
35576
0x15C7
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Sag20_Start_time
Sag20_End_time
3557735582
3558335588
0x15C80x15CD
0x15CE0x15D3
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Modbus Module #21 Input Register : Event Log Swell Record*
Modbus Register
Parameter name
Len
Data
Type
0x15D4
Word
UINT
35590
0x15D5
Word
INT
35591
0x15D6
Word
UINT
Word x
6
Date
&
Time
(BCD)
Swell01_Duration_Cycles
Modicom
Format
35589
Swell01_Data
Swell01_Phase
Swell01_Start_Time
3559235597
Hex
0x15D70x15DC
58
Range
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Default
value
Units
Comment
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell01_End_Time
3559835603
0x15DD0x15E2
Word x
6
Date
&
Time
(BCD)
Swell02_Duration_Cycles
35604
0x15E3
Word
UINT
Swell02_Data
35605
0x15E4
Word
INT
Swell02_Phase
35606
0x15E5
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell02_Start_time
3560735612
0x15E60x15EB
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Swell02_End_time
3561335618
0x15EC0x15F1
Word x
6
Date
&
Time
(BCD)
Swell03_Duration_Cycles
35619
0x15F2
Word
UINT
Swell03_Data
35620
0x15F3
Word
INT
Swell03_Phase
35621
0x15F4
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell03_Start_time
3562235627
0x15F50x15FA
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Swell03_End_time
3562835633
0x15FB0x1600
Word x
6
Date
&
Time
(BCD)
Swell04_Duration_Cycles
35634
0x1601
Word
UINT
Swell04_Data
35635
0x1602
Word
INT
Swell04_Phase
35636
0x1603
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell04_Start_time
3563735642
0x16040x1609
Swell04_End_time
3564335648
0x160A0x160F
Word x
6
Date
&
Time
(BCD)
Swell05_Duration_Cycles
35649
0x1610
Word
UINT
Swell05_Data
35650
0x1611
Word
INT
Swell05_Phase
35651
0x1612
Word
UINT
59
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Swell05_Start_time
Swell05_End_time
3565235657
3565835663
0x16130x1618
0x16190x161E
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell06_Duration_Cycles
35664
0x161F
Word
UINT
Swell06_Data
35665
0x1620
Word
INT
Swell06_Phase
35666
0x1621
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell06_Start_time
3566735672
0x16220x1627
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Swell06_End_time
3567335678
0x16280x162D
Word x
6
Date
&
Time
(BCD)
Swell07_Duration_Cycles
35679
0x162E
Word
UINT
Swell07_Data
35680
0x162F
Word
INT
Swell07_Phase
35681
0x1630
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell07_Start_time
3568235687
0x16310x1636
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Swell07_End_time
3568835693
0x16370x163C
Word x
6
Date
&
Time
(BCD)
Swell08_Duration_Cycles
35694
0x163D
Word
UINT
Swell08_Data
35695
0x163E
Word
INT
Swell08_Phase
35696
0x163F
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell08_Start_time
3569735702
0x16400x1645
Swell08_End_time
3570335708
0x16460x164B
Word x
6
Date
&
Time
(BCD)
Swell09_Duration_Cycles
35709
0x164C
Word
UINT
60
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Swell09_Data
35710
0x164D
Word
INT
Swell09_Phase
35711
0x164E
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell09_Start_time
3571235717
0x164F0x1654
Swell09_End_time
3571835723
0x16550x165A
Word x
6
Date
&
Time
(BCD)
Swell10_Duration_Cycles
35724
0x165B
Word
UINT
Swell10_Data
35725
0x165C
Word
INT
Swell10_Phase
35726
0x165D
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell10_Start_time
3572735732
0x165E0x1663
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Swell10_End_time
3573335738
0x16640x1669
Word x
6
Date
&
Time
(BCD)
Swell11_Duration_Cycles
35739
0x166A
Word
UINT
Swell11_Data
35740
0x166B
Word
INT
Swell11_Phase
35741
0x166C
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell11_Start_time
3574235747
0x166D0x1672
Swell11_End_time
3574835753
0x16730x1678
Word x
6
Date
&
Time
(BCD)
Swell12_Duration_Cycles
35754
0x1679
Word
UINT
Swell12_Data
35755
0x167A
Word
INT
Swell12_Phase
35756
0x167B
Word
UINT
Word x
6
Date
&
Time
(BCD)
Swell12_Start_time
3575735762
0x167C0x1681
61
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell12_End_time
3576335768
0x16820x1687
Word x
6
Date
&
Time
(BCD)
Swell13_Duration_Cycles
35769
0x1688
Word
UINT
Swell13_Data
35770
0x1689
Word
INT
Swell13_Phase
35771
0x168A
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell13_Start_time
3577235777
0x168B0x1690
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Swell13_End_time
3577835783
0x16910x1696
Word x
6
Date
&
Time
(BCD)
Swell14_Duration_Cycles
35784
0x1697
Word
UINT
Swell14_Data
35785
0x1698
Word
INT
Swell14_Phase
35786
0x1699
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell14_Start_time
3578735792
0x169A0x169F
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Swell14_End_time
3579335798
0x16A00x16A5
Word x
6
Date
&
Time
(BCD)
Swell15_Duration_Cycles
35799
0x16A6
Word
UINT
Swell15_Data
35800
0x16A7
Word
INT
Swell15_Phase
35801
0x16A8
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell15_Start_time
3580235807
0x16A90x16AE
Swell15_End_time
3580835813
0x16AF0x16B4
Word x
6
Date
&
Time
(BCD)
Swell16_Duration_Cycles
35814
0x16B5
Word
UINT
Swell16_Data
35815
0x16B6
Word
INT
Swell16_Phase
35816
0x16B7
Word
UINT
62
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Swell16_Start_time
3581735822
0x16B80x16BD
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell16_End_time
3582335828
0x16BE0x16C3
Word x
6
Date
&
Time
(BCD)
Swell17_Duration_Cycles
35829
0x16C4
Word
UINT
Swell17_Data
35830
0x16C5
Word
INT
Swell17_Phase
35831
0x16C6
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell17_Start_time
3583235837
0x16C70x16CC
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Swell17_End_time
3583835843
0x16CD0x16D2
Word x
6
Date
&
Time
(BCD)
Swell18_Duration_Cycles
35844
0x16D3
Word
UINT
Swell18_Data
35845
0x16D4
Word
INT
Swell18_Phase
35846
0x16D5
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell18_Start_time
Swell18_End_time
3584735852
3585335858
0x16D60x16DB
0x16DC0x16E1
Swell19_Duration_Cycles
35859
0x16E2
Word
UINT
Swell19_Data
35860
0x16E3
Word
INT
Swell19_Phase
35861
0x16E4
Word
UINT
Word x
6
Date
&
Time
(BCD)
Swell19_Start_time
3586235867
0x16E50x16EA
63
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell19_End_time
3586835873
0x16EB0x16F0
Word x
6
Date
&
Time
(BCD)
Swell20_Duration_Cycles
35874
0x16F1
Word
UINT
Swell20_Data
35875
0x16F2
Word
INT
Swell20_Phase
35876
0x16F3
Word
UINT
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Word x
6
Date
&
Time
(BCD)
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Swell20_Start_time
Swell20_End_time
3587735882
3588335888
0x16F40x16F9
0x16FA0x16FF
Range : -327.68% ~
327.67%
0: A phase 1: B phase
2: C phase
Modbus Module #22 Input Register : Event Log Alarm Record*
Modbus Register
Parameter name
Alarm01_Item
Modicom
Format
35889
Alarm01_Data
35890
Alarm01_Time
3589135896
Len
Data
Type
0x1700
Word
UINT
0x1701
Word
INT
Word x
6
Date
&
Time
(BCD)
Hex
0x17020x1707
Alarm02_Item
35897
0x1708
Word
UINT
Alarm02_Data
35898
0x1709
Word
INT
Alarm02_Time
3589935904
0x170A0x170F
Word x
6
Date
&
Time
(BCD)
Alarm03_Item
35905
0x1710
Word
UINT
Alarm03_Data
35906
0x1711
Word
INT
Alarm03_Time
3590735912
0x17120x1717
Word x
6
Date
&
Time
(BCD)
Alarm04_Item
35913
0x1718
Word
UINT
Alarm04_Data
35914
0x1719
Word
INT
64
Range
Range : -327.68% ~
327.67%
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Default
value
Units
Comment
Alarm04_Time
3591535920
0x171A0x171F
Word x
6
Date
&
Time
(BCD)
Alarm05_Item
35921
0x1720
Word
UINT
Alarm05_Data
35922
0x1721
Word
INT
Alarm05_Time
3592335928
0x17220x1727
Word x
6
Date
&
Time
(BCD)
Alarm06_Item
35929
0x1728
Word
UINT
Alarm06_Data
35930
0x1729
Word
INT
Alarm06_Time
3593135936
0x172A0x172F
Word x
6
Date
&
Time
(BCD)
Alarm07_Item
35937
0x1730
Word
UINT
Alarm07_Data
35938
0x1731
Word
INT
Word x
6
Date
&
Time
(BCD)
Alarm07_Time
3593935944
0x17320x1737
Alarm08_Item
35945
0x1738
Word
UINT
Alarm08_Data
35946
0x1739
Word
INT
Word x
6
Date
&
Time
(BCD)
Alarm08_Time
3594735952
0x173A0x173F
Alarm09_Item
35953
0x1740
Word
UINT
Alarm09_Data
35954
0x1741
Word
INT
Alarm09_Time
3595535960
0x17420x1747
Word x
6
Date
&
Time
(BCD)
Alarm10_Item
35961
0x1748
Word
UINT
Alarm10_Data
35962
0x1749
Word
INT
Alarm10_Time
3596335968
0x174A0x174F
Word x
6
Date
&
Time
(BCD)
Alarm11_Item
35969
0x1750
Word
UINT
Alarm11_Data
35970
0x1751
Word
INT
65
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Year : 2000-2099
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Alarm11_Time
3597135976
0x17520x1757
Word x
6
Date
&
Time
(BCD)
Alarm12_Item
35977
0x1758
Word
UINT
Alarm12_Data
35978
0x1759
Word
INT
Word x
6
Date
&
Time
(BCD)
Alarm12_Time
3597935984
0x175A0x175F
Alarm13_Item
35985
0x1760
Word
UINT
Alarm13_Data
35986
0x1761
Word
INT
Alarm13_Time
3598735992
0x17620x1767
Word x
6
Date
&
Time
(BCD)
Alarm14_Item
35993
0x1768
Word
UINT
Alarm14_Data
35994
0x1769
Word
INT
Alarm14_Time
3599536000
0x176A0x176F
Word x
6
Date
&
Time
(BCD)
Alarm15_Item
36001
0x1770
Word
UINT
Alarm15_Data
36002
0x1771
Word
INT
Alarm15_Time
3600336008
0x17720x1777
Word x
6
Date
&
Time
(BCD)
Alarm16_Item
36009
0x1778
Word
UINT
Alarm16_Data
36010
0x1779
Word
INT
Alarm16_Time
3601136016
0x177A0x177F
Word x
6
Date
&
Time
(BCD)
Alarm17_Item
36017
0x1780
Word
UINT
Alarm17_Data
36018
0x1781
Word
INT
Alarm17_Time
3601936024
0x17820x1787
Word x
6
Date
&
Time
(BCD)
Alarm18_Item
36025
0x1788
Word
UINT
Alarm18_Data
36026
0x1789
Word
INT
Alarm18_Time
3602736032
0x178A0x178F
Word x
6
Date
&
Time
(BCD)
66
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Alarm19_Item
36033
0x1790
Word
UINT
Alarm19_Data
36034
0x1791
Word
INT
Alarm19_Time
3603536040
0x17920x1797
Word x
6
Date
&
Time
(BCD)
Alarm20_Item
36041
0x1798
Word
UINT
Alarm20_Data
36042
0x1799
Word
INT
Alarm20_Time
3604336048
0x179A0x179F
Word x
6
Date
&
Time
(BCD)
Range : -327.68% ~
327.67%
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Range : -327.68% ~
327.67%
Year : 00-99
Month : 1-12
Date : 1-31
Hour : 0-23
Minute : 0-59
Second : 0-59
Modbus Module #23 Input Register : Total Harmonics*
Modbus Register
Parameter name
TOT_HD_V_a
TOT_HD_V_b
TOT_HD_V_c
TOT_HD_I_a
TOT_HD_I_b
TOT_HD_I_c
TOT_HD_I_n
Modicom
Format
3665736658
3665936660
3666136662
3666336664
3666536666
3666736668
3666936670
Len
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Hex
0x1A000x1A01
0x1A020x1A03
0x1A040x1A05
0x1A060x1A07
0x1A080x1A09
0x1A0A0x1A0B
0x1A0C0x1A0D
Range
Default
value
Units
Comment
Units
Comment
Modbus Module #24 Input Register : Total Odd & Even Harmonics*
Modbus Register
Parameter name
TOT_EVEN_HD_V_a
TOT_EVEN_HD_V_b
TOT_EVEN_HD_V_c
TOT_EVEN_HD_I_a
TOT_EVEN_HD_I_b
TOT_EVEN_HD_I_c
TOT_EVEN_HD_I_n
TOT_ODD_HD_V_a
TOT_ODD_HD_V_b
TOT_ODD_HD_V_c
TOT_ODD_HD_I_a
Modicom
Format
3667136672
3667336674
3667536676
3667736678
3667936680
3668136682
3668336684
3668536686
3668736688
3668936690
3669136692
Len
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Hex
0x1A0E0x1A0F
0x1A100x1A11
0x1A120x1A13
0x1A140x1A15
0x1A160x1A17
0x1A180x1A19
0x1A1A0x1A1B
0x1A1C0x1A1D
0x1A1E0x1A1F
0x1A200x1A21
0x1A220x1A23
67
Range
Default
value
TOT_ODD_HD_I_b
TOT_ODD_HD_I_c
TOT_ODD_HD_I_n
3669336694
3669536696
3669736698
0x1A240x1A25
0x1A260x1A27
0x1A280x1A29
DWord
Float
DWord
Float
DWord
Float
Modbus Module #25 Input Register : Phase A Voltage Harmonics*
Modbus Register
Parameter name
Reserved
HD1_V_a
HD2_V_a
HD3_V_a
HD4_V_a
HD5_V_a
HD6_V_a
HD7_V_a
HD8_V_a
HD9_V_a
HD10_V_a
HD11_V_a
HD12_V_a
HD13_V_a
HD14_V_a
HD15_V_a
HD16_V_a
HD17_V_a
HD18_V_a
HD19_V_a
HD20_V_a
HD21_V_a
HD22_V_a
HD23_V_a
HD24_V_a
HD25_V_a
HD26_V_a
HD27_V_a
HD28_V_a
Modicom
Format
3669936700
3670136702
3670336704
3670536706
3670736708
3670936710
3671136712
3671336714
3671536716
3671736718
3671936720
3672136722
3672336724
3672536726
3672736728
3672936730
3673136732
3673336734
3673536736
3673736738
3673936740
3674136742
3674336744
3674536746
3674736748
3674936750
3675136752
3675336754
3675536756
Len
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Hex
0x1A2A0x1A2B
0x1A2C0x1A2D
0x1A2E0x1A2F
0x1A300x1A31
0x1A320x1A33
0x1A340x1A35
0x1A360x1A37
0x1A380x1A39
0x1A3A0x1A3B
0x1A3C0x1A3D
0x1A3E0x1A3F
0x1A400x1A41
0x1A420x1A43
0x1A440x1A45
0x1A460x1A47
0x1A480x1A49
0x1A4A0x1A4B
0x1A4C0x1A4D
0x1A4E0x1A4F
0x1A500x1A51
0x1A520x1A53
0x1A540x1A55
0x1A560x1A57
0x1A580x1A59
0x1A5A0x1A5B
0x1A5C0x1A5D
0x1A5E0x1A5F
0x1A600x1A61
0x1A620x1A63
68
Range
Default
value
Units
Comment
HD29_V_a
HD30_V_a
HD31_V_a
3675736758
3675936760
3676136762
0x1A640x1A65
0x1A660x1A67
0x1A680x1A69
DWord
Float
DWord
Float
DWord
Float
Modbus Module #26 Input Register : Phase B Voltage Harmonics*
Modbus Register
Parameter name
Reserved
HD1_V_b
HD2_V_b
HD3_V_b
HD4_V_b
HD5_V_b
HD6_V_b
HD7_V_b
HD8_V_b
HD9_V_b
HD10_V_b
HD11_V_b
HD12_V_b
HD13_V_b
HD14_V_b
HD15_V_b
HD16_V_b
HD17_V_b
HD18_V_b
HD19_V_b
HD20_V_b
HD21_V_b
HD22_V_b
HD23_V_b
HD24_V_b
HD25_V_b
HD26_V_b
HD27_V_b
HD28_V_b
Modicom
Format
3676336764
3676536766
3676736768
3676936770
3677136772
3677336774
3677536776
3677736778
3677936780
3678136782
3678336784
3678536786
3678736788
3678936790
3679136792
3679336794
3679536796
3679736798
3679936800
3680136802
3680336804
3680536806
3680736808
3680936810
3681136812
3681336814
3681536816
3681736818
3681936820
Len
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Hex
0x1A6A0x1A6B
0x1A6C0x1A6D
0x1A6E0x1A6F
0x1A700x1A71
0x1A720x1A73
0x1A740x1A75
0x1A760x1A77
0x1A780x1A79
0x1A7A0x1A7B
0x1A7C0x1A7D
0x1A7E0x1A7F
0x1A800x1A81
0x1A820x1A83
0x1A840x1A85
0x1A860x1A87
0x1A880x1A89
0x1A8A0x1A8B
0x1A8C0x1A8D
0x1A8E0x1A8F
0x1A900x1A91
0x1A920x1A93
0x1A940x1A95
0x1A960x1A97
0x1A980x1A99
0x1A9A0x1A9B
0x1A9C0x1A9D
0x1A9E0x1A9F
0x1AA00x1AA1
0x1AA20x1AA3
69
Range
Default
value
Units
Comment
HD29_V_b
HD30_V_b
HD31_V_b
3682136822
3682336824
3682536826
0x1AA40x1AA5
0x1AA60x1AA7
0x1AA80x1AA9
DWord
Float
DWord
Float
DWord
Float
Modbus Module #27 Input Register : Phase C Voltage Harmonics*
Modbus Register
Parameter name
Reserved
HD1_V_c
HD2_V_c
HD3_V_c
HD4_V_c
HD5_V_c
HD6_V_c
HD7_V_c
HD8_V_c
HD9_V_c
HD10_V_c
HD11_V_c
HD12_V_c
HD13_V_c
HD14_V_c
HD15_V_c
HD16_V_c
HD17_V_c
HD18_V_c
HD19_V_c
HD20_V_c
HD21_V_c
HD22_V_c
HD23_V_c
HD24_V_c
HD25_V_c
HD26_V_c
HD27_V_c
HD28_V_c
Modicom
Format
3682736828
3682936830
3683136832
3683336834
3683536836
3683736838
3683936840
3684136842
3684336844
3684536846
3684736848
3684936850
3685136852
368536854
3685536856
3685736858
3685936860
3686136862
3686336864
3686536866
3686736868
3686936870
3687136872
3687336874
3687536876
3687736878
3687936880
3688136882
3688336884
Len
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Hex
0x1AAA0x1AAB
0x1AAC0x1AAD
0x1AAE0x1AAF
0x1AB00x1AB1
0x1AB20x1AB3
0x1AB40x1AB5
0x1AB60x1AB7
0x1AB80x1AB9
0x1ABA0x1ABB
0x1ABC0x1ABD
0x1ABE0x1ABF
0x1AC00x1AC1
0x1AC20x1AC3
0x1AC40x1AC5
0x1AC60x1AC7
0x1AC80x1AC9
0x1ACA0x1ACB
0x1ACC0x1ACD
0x1ACE0x1ACF
0x1AD00x1AD1
0x1AD20x1AD3
0x1AD40x1AD5
0x1AD60x1AD7
0x1AD80x1AD9
0x1ADA0x1ADB
0x1ADC0x1ADD
0x1ADE0x1ADF
0x1AE00x1AE1
0x1AE20x1AE3
70
Range
Default
value
Units
Comment
HD29_V_c
HD30_V_c
HD31_V_c
3688536886
3688736888
3688936890
0x1AE40x1AE5
0x1AE60x1AE7
0x1AE80x1AE9
DWord
Float
DWord
Float
DWord
Float
Modbus Module #28 Input Register : Phase A Current Harmonics*
Modbus Register
Parameter name
Reserved
HD1_I_a
HD2_I_a
HD3_I_a
HD4_I_a
HD5_I_a
HD6_I_a
HD7_I_a
HD8_I_a
HD9_I_a
HD10_I_a
HD11_I_a
HD12_I_a
HD13_I_a
HD14_I_a
HD15_I_a
HD16_I_a
HD17_I_a
HD18_I_a
HD19_I_a
HD20_I_a
HD21_I_a
HD22_I_a
HD23_I_a
HD24_I_a
HD25_I_a
HD26_I_a
HD27_I_a
HD28_I_a
Modicom
Format
3689136892
3689336894
3689536896
3689736898
3689936900
3690136902
3690336904
3690536906
3690736908
3690936910
3691136912
3691336914
3691536916
3691736918
3691936920
3692136922
3692336924
3692536926
3692736928
3692936930
3693136932
3693336934
3693536936
3693736938
3693936940
3694136942
3694336944
3694536946
3694736948
Len
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Hex
0x1AEA0x1AEB
0x1AEC0x1AED
0x1AEE0x1AEF
0x1AF00x1AF1
0x1AF20x1AF3
0x1AF40x1AF5
0x1AF60x1AF7
0x1AF80x1AF9
0x1AFA0x1AFB
0x1AFC0x1AFD
0x1AFE0x1AFF
0x1B000x1B01
0x1B020x1B03
0x1B040x1B05
0x1B060x1B07
0x1B080x1B09
0x1B0A0x1B0B
0x1B0C0x1B0D
0x1B0E0x1B0F
0x1B100x1B11
0x1B120x1B13
0x1B140x1B15
0x1B160x1B17
0x1B180x1B19
0x1B1A0x1B1B
0x1B1C0x1B1D
0x1B1E0x1B1F
0x1B200x1B21
0x1B220x1B23
71
Range
Default
value
Units
Comment
HD29_I_a
HD30_I_a
HD31_I_a
3694936950
3695136952
3695336954
0x1B240x1B25
0x1B260x1B27
0x1B280x1B29
DWord
Float
DWord
Float
DWord
Float
Modbus Module #29 Input Register : Phase B Current Harmonics*
Modbus Register
Parameter name
Reserved
HD1_I_b
HD2_I_b
HD3_I_b
HD4_I_b
HD5_I_b
HD6_I_b
HD7_I_b
HD8_I_b
HD9_I_b
HD10_I_b
HD11_I_b
HD12_I_b
HD13_I_b
HD14_I_b
HD15_I_b
HD16_I_b
HD17_I_b
HD18_I_b
HD19_I_b
HD20_I_b
HD21_I_b
HD22_I_b
HD23_I_b
HD24_I_b
HD25_I_b
HD26_I_b
HD27_I_b
HD28_I_b
Modicom
Format
3695536956
3695736958
3695936960
3696136962
3696336964
3696536966
3696736968
3696936970
3697136972
3697336974
3697536976
3697736978
3697936980
3698136982
3698336984
3698536986
3698736988
3698936990
3699136992
3699336994
3699536996
3699736998
3699937000
3700137002
3700337004
3700537006
3700737008
3700937010
3701137012
Len
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Hex
0x1B2A0x1B2B
0x1B2C0x1B2D
0x1B2E0x1B2F
0x1B300x1B31
0x1B320x1B33
0x1B340x1B35
0x1B360x1B37
0x1B380x1B39
0x1B3A0x1B3B
0x1B3C0x1B3D
0x1B3E0x1B3F
0x1B400x1B41
0x1B420x1B43
0x1B440x1B45
0x1B460x1B47
0x1B480x1B49
0x1B4A0x1B4B
0x1B4C0x1B4D
0x1B4E0x1B4F
0x1B500x1B51
0x1B520x1B53
0x1B540x1B55
0x1B560x1B57
0x1B580x1B59
0x1B5A0x1B5B
0x1B5C0x1B5D
0x1B5E0x1B5F
0x1B600x1B61
0x1B620x1B63
72
Range
Default
value
Units
Comment
HD29_I_b
HD30_I_b
HD31_I_b
3701337014
3701537016
3701737018
0x1B640x1B65
0x1B660x1B67
0x1B680x1B69
DWord
Float
DWord
Float
DWord
Float
Modbus Module #30 Input Register : Phase C Current Harmonics*
Modbus Register
Parameter name
Reserved
HD1_I_c
HD2_I_c
HD3_I_c
HD4_I_c
HD5_I_c
HD6_I_c
HD7_I_c
HD8_I_c
HD9_I_c
HD10_I_c
HD11_I_c
HD12_I_c
HD13_I_c
HD14_I_c
HD15_I_c
HD16_I_c
HD17_I_c
HD18_I_c
HD19_I_c
HD20_I_c
HD21_I_c
HD22_I_c
HD23_I_c
HD24_I_c
HD25_I_c
HD26_I_c
HD27_I_c
HD28_I_c
Modicom
Format
3701937020
3702137022
3702337024
3702537026
3702737028
3702937030
3703137032
3703337034
3703537036
3703737038
3703937040
3704137042
3704337044
3704537046
3704737048
3704937050
3705137052
3705337054
3705537056
3705737058
3705937060
3706137062
3706337064
3706537066
3706737068
3707937070
3707137072
3707337074
3707537076
Len
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Hex
0x1B6A0x1B6B
0x1B6C0x1B6D
0x1B6E0x1B6F
0x1B700x1B71
0x1B720x1B73
0x1B740x1B75
0x1B760x1B77
0x1B780x1B79
0x1B7A0x1B7B
0x1B7C0x1B7D
0x1B7E0x1B7F
0x1B800x1B81
0x1B820x1B83
0x1B840x1B85
0x1B860x1B87
0x1B880x1B89
0x1B8A0x1B8B
0x1B8C0x1B8D
0x1B8E0x1B8F
0x1B900x1B91
0x1B920x1B93
0x1B940x1B95
0x1B960x1B97
0x1B980x1B99
0x1B9A0x1B9B
0x1B9C0x1B9D
0x1B9E0x1B9F
0x1BA00x1BA1
0x1BA20x1BA3
73
Range
Default
value
Units
Comment
HD29_I_c
HD30_I_c
HD31_I_c
3707737078
3707937080
3708137082
0x1BA40x1BA5
0x1BA60x1BA7
0x1BA80x1BA9
DWord
Float
DWord
Float
DWord
Float
Modbus Module #31 Input Register : Neutral Current Harmonics*
Modbus Register
Parameter name
Reserved
HD1_I_n
HD2_I_n
HD3_I_n
HD4_I_n
HD5_I_n
HD6_I_n
HD7_I_n
HD8_I_n
HD9_I_n
HD10_I_n
HD11_I_n
HD12_I_n
HD13_I_n
HD14_I_n
HD15_I_n
HD16_I_n
HD17_I_n
HD18_I_n
HD19_I_n
HD20_I_n
HD21_I_n
HD22_I_n
HD23_I_n
HD24_I_n
HD25_I_n
HD26_I_n
HD27_I_n
HD28_I_n
Modicom
Format
3708337084
3708537086
3708737088
3708937090
3709137092
3709337094
3709537096
3709737098
3709937100
3710137102
37103
37104
3710537106
3710737108
3710937110
3711137112
3711337114
3711537116
3711737118
3711937120
3712137122
3712337124
3712537126
3712737128
3712937130
3713137132
3713337134
3713537136
3713737138
3713937140
Len
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Hex
0x1BAA0x1BAB
0x1BAC0x1BAD
0x1BAE0x1BAF
0x1BB00x1BB1
0x1BB20x1BB3
0x1BB40x1BB5
0x1BB60x1BB7
0x1BB80x1BB9
0x1BBA0x1BBB
0x1BBC0x1BBD
0x1BBE0x1BBF
0x1BC00x1BC1
0x1BC20x1BC3
0x1BC40x1BC5
0x1BC60x1BC7
0x1BC80x1BC9
0x1BCA0x1BCB
0x1BCC0x1BCD
0x1BCE0x1BCF
0x1BD00x1BD1
0x1BD20x1BD3
0x1B40x1BD5
0x1BD60x1BD7
0x1BD80x1BD9
0x1BDA0x1BDB
0x1BDC0x1BDD
0x1BDE0x1BDF
0x1BE00x1BE1
0x1BE20x1BE3
74
Range
Default
value
Units
Comment
HD29_I_n
HD30_I_n
HD31_I_n
3714137142
3714337144
3714537146
0x1BE40x1BE5
0x1BE60x1BE7
0x1BE80x1BE9
DWord
Float
DWord
Float
DWord
Float
Modbus Module #32 Input Register : Realtime Data Voltage, Current, Frequency
(Unsigned Int)
Modbus Register
Parameter name
Vln_a
Vln_b
Vln_c
Vln_avg
Vll_ab
Vll_bc
Vll_ca
Vll_avg
I_a
I_b
I_c
I_avg
I_n
Freq
Modicom
Format
38449
38450
38451
38452
38453
38454
38455
38456
38457
38458
38459
38460
38461
38462
Len
Data
Type
Range
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-65535
0-9999
Hex
0x2100
0x2101
0x2102
0x2103
0x2104
0x2105
0x2106
0x2107
0x2108
0x2109
0x210A
0x210B
0x210C
0x210D
Default
value
Units
0.1V
0.1V
0.1V
0.1V
0.1V
0.1V
0.1V
0.1V
mA.
mA.
mA.
mA.
mA.
0.01Hz
Comment
Secondary
Secondary
Secondary
Secondary
Secondary
Secondary
Secondary
Secondary
Secondary
Secondary
Secondary
Secondary
Secondary
Modbus Module #33 Input Register : Realtime Data Power Result (Int)
Modbus Register
Parameter name
KW_a
KW_b
KW_c
KW_tot
KVAR_a
KVAR_b
KVAR_c
KVAR_tot
KVA_a
KVA_b
KVA_c
KVA_tot
Modicom
Format
38463
38464
38465
38466
38467
38468
38469
38470
38471
38472
38473
38474
Len
Data
Type
Range
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
INT
INT
INT
INT
INT
INT
INT
INT
INT
INT
INT
INT
-32768-32767
-32768-32767
-32768-32767
-32768-32767
-32768-32767
-32768-32767
-32768-32767
-32768-32767
0-32767
0-32767
0-32767
0-32767
Hex
0x210E
0x210F
0x2110
0x2111
0x2112
0x2113
0x2114
0x2115
0x2116
0x2117
0x2118
0x2119
Default
value
Units
W
W
W
W
var
var
var
var
VA
VA
VA
VA
Comment
Secondary
Secondary
Secondary
Secondary
Secondary
Secondary
Secondary
Secondary
Secondary
Secondary
Secondary
Secondary
Modbus Module #34 Input Register : Realtime Data Power Factor & Phase Angle (Int)
Modbus Register
Parameter name
PF_signed_a
PF_signed_b
PF_signed_c
PF_signed_avg
PhaseAngle_V_a
PhaseAngle_V_b
PhaseAngle_V_c
PhaseAngle_I_a
PhaseAngle_I_b
PhaseAngle_I_c
Reserved
Reserved
Reserved
Modicom
Format
38475
38476
38477
38478
38479
38480
38481
38482
38483
38484
38485
38486
38487
Len
Data
Type
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
INT
INT
INT
INT
INT
INT
INT
INT
INT
INT
INT
INT
INT
Hex
0x211A
0x211B
0x211C
0x211D
0x211E
0x211F
0x2120
0x2121
0x2122
0x2123
0x2124
0x2125
0x2126
75
Range
-1000~+1000
-1000~+1000
-1000~+1000
-1000~+1000
-1800~+1800
-1800~+1800
-1800~+1800
-1800~+1800
-1800~+1800
-1800~+1800
Default
value
Units
0.001
0.001
0.001
0.001
0.1
0.1
0.1
0.1
0.1
0.1
Comment
Modbus Module #35 Input Register : Realtime Data Energy & Demand(Unsigned Int)
Modbus Register
Parameter name
KWH_del
KWH_rec
KWH_tot
KWH_net
KVARH_del (+ lagging)
KVARH_rec (- leading)
KVARH_tot
KVARH_net
KVAH
Demand_kW*
Demand_Remain_Time*
Pre_Demand_kW*
Pre_Demand_kvar*
Demand_kvar*
Pre_Demand_kVA*
Demand_kVA*
Modicom
Format
38488
38489
38490
38491
38492
38493
38494
38495
38496
38497
38498
38499
38500
38501
38502
38503
38504
38505
38506
38507
38508
38509
38510
38511
38512
38513
38514
38515
38516
38517
38518
38519
38520
38521
Len
Data
Type
Range
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
INT
UINT
INT
INT
INT
INT
INT
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
0-999
-32768-32767
0-65535
-32768-32767
-32768-32767
-32768-32767
-32768-32767
-32768-32767
Hex
0x2127
0x2128
0x2129
0x212A
0x212B
0x212C
0x212D
0x212E
0x212F
0x2130
0x2131
0x2132
0x2133
0x2134
0x2135
0x2136
0x2137
0x2138
0x2139
0x213A
0x213B
0x213C
0x213D
0x213E
0x213F
0x2140
0x2141
0x2142
0x2143
0x2144
0x2145
0x2146
0x2147
0x2148
Default
value
Units
1000000
1000
0.1
1000000
1000
0.1
1000000
1000
0.1
1000000
1000
0.1
1000000
1000
0.1
1000000
1000
0.1
1000000
1000
0.1
1000000
1000
0.1
1000000
1000
0.1
W
sec
W
W
W
W
W
Comment
Secondary
Secondary
Secondary
Secondary
Secondary
Secondary
Modbus Module #36 Holding Register : Realtime Data Voltage, Current, Frequency (Float)
Modbus Register
Parameter name
Vln_a
Vln_b
Vln_c
Vln_avg
Vll_ab
Vll_bc
Vll_ca
Vll_avg
I_a
I_b
I_c
I_avg
Modicom
Format
4600146002
4600346004
4600546006
4600746008
4600946010
4601146012
4601346014
4601546016
4601746018
4601946020
4602146022
46023-
Data
Type
Range
DWord
Float
Primary Voltage
Volts
DWord
Float
Primary Voltage
Volts
DWord
Float
Primary Voltage
Volts
DWord
Float
Primary Voltage
Volts
DWord
Float
Primary Voltage
Volts
DWord
Float
Primary Voltage
Volts
DWord
Float
Primary Voltage
Volts
DWord
Float
Primary Voltage
Volts
DWord
Float
Primary Current
Amp.
DWord
Float
Primary Current
Amp.
DWord
Float
Primary Current
Amp.
DWord
Float
Primary Current
Amp.
Hex
0x17700x1771
0x17720x1773
0x17740x1775
0x17760x1777
0x17780x1779
0x177A0x177B
0x177C0x177D
0x177E0x177F
0x17800x1781
0x17820x1783
0x17840x1785
0x1786-
Default
value
Len
76
Units
Comment
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
46024
4602546026
4602746028
I_n
Freq
0x1787
0x17880x1789
0x178A0x178B
DWord
Float
DWord
Float
Primary Current
Amp.
Hz
display
with Runtime
display
with Runtime
display
Modbus Module #37 Holding Register : Realtime Data Power Result (Float)
Modbus Register
Parameter name
KW_a
KW_b
KW_c
KW_tot
KVAR_a
KVAR_b
KVAR_c
KVAR_tot
KVA_a
KVA_b
KVA_c
KVA_tot
Modicom
Format
4602946030
4603146032
4603346034
4603546036
4603746038
4603946040
4604146042
4604346044
4604546046
4604746048
4604946050
4605146052
Len
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Hex
0x178C0x178D
0x178E0x178F
0x17900x1791
0x17920x1793
0x17940x1795
0x17960x1797
0x17980x1799
0x179A0x179B
0x179C0x179D
0x179E0x179F
0x17A00x17A1
0x17A20x17A3
Range
Default
value
Units
Comment
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
Modbus Module #38 Holding Register : Realtime Data Power Factor & Phase Angle (Float)
Modbus Register
Parameter name
PF_true_a
PF_ true_b
PF_ true_c
PF_ true_avg
PhaseAngle_V_a
PhaseAngle_V_b
PhaseAngle_V_c
PhaseAngle_I_a
PhaseAngle_I_b
PhaseAngle_I_c
Pre_Demand_KW*
Reserved
Reserved
Modicom
Format
4605346054
4605546056
4605746058
4605946060
4606146062
4606346064
4606546066
4606746068
4606946070
4607146072
4607346074
4607546076
4607746078
Len
Hex
0x17A40x17A5
0x17A60x17A7
0x17A80x17A9
0x17AA0x17AB
0x17AC0x17AD
0x17AE0x17AF
0x17B00x17B1
0x17B20x17B3
0x17B40x17B5
0x17B60x17B7
0x17B80x17B9
0x17BA0x17BB
0x17BC0x17BD
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
77
Range
Default
value
Units
Comment
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
Modbus Module #39 Holding Register : Realtime Data Energy (Float)
Modbus Register
Parameter name
KWH_del
KWH_rec
KWH_tot
KWH_net
KVARH_ lagging
KVARH_ leading
KVARH_tot
KVARH_net
KVAH
Modicom
Format
4607946080
4608146082
4608346084
4608546086
4608746088
4608946090
4609146092
4609346094
4609546096
Len
Data
Type
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
DWord
Float
Hex
0x17BE0x17BF
0x17C00x17C1
0x17C20x17C3
0x17C40x17C5
0x17C60x17C7
0x17C80x17C9
0x17CA0x17CB
0x17CC0x17CD
0x17CE0x17CF
Range
Default
value
Units
Comment
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
with Runtime
display
Modbus Module #40 Holding Register : Realtime data Demand*
Modbus Register
Parameter name
Demand_KW
Demand_Remain_Time
Modicom
Format
4609746098
46099
Len
Data
Type
DWord
Float
Word
UInt
Hex
0x17D00x17D1
0x17D2
Range
Default
value
Units
Comment
sec
Modbus Module #41 Holding Register : AI Result
Modbus Register
Parameter name
Modicom
Format
Len
Hex
Data
Type
Range
Default
value
Units
Comment
AI1 Value
46100
0x17D3
Word
UInt
0~65535
optional
AI2 Value
46101
0x17D4
Word
UInt
0~65535
optional
AI3 Value
46102
0x17D5
Word
UInt
0~65535
optional
AI4 Value
46103
0x17D6
Word
UInt
0~65535
optional
78