Download MT-102
Transcript
8.2.6.2.2.1. Name Function - allows setting a friendly name for the input usually connected with performed function. Assigned name appears on the terminals list Data type - text Range - letters and numerals, max. 16 characters Default value - Resource Name (A1, A2, AE3, …,AE6) Comments - entering a friendly name facilitates distinguishing destination, performed function and required settings. 8.2.6.2.2.2. Operating mode Function - defines analogue inputs operating mode Data type - selection list Range - Analogue input the input operates as 4-20 mA standard input Default value - Analogue input Comments - Parameter preserved for legacy support, not important for operating analogue inputs AN1, AN2, AE3, ..., AE6 8.2.6.2.2.3. Filtering constant Function - Defines filter filtering constant Data type - number Range - 0,0…25,5 [s] Default value - 0 Comments - for 0 (zero) value filtering is off. Setting high time value influences stabilizing of result after signal value change, but allows better precision of measuring noisy signal. It is recommended to set filtering constant of AE1...4 to values 6,4 and higher to provide satisfying precision of measurements. Assuming that measured value will raise from minimum to maximum value (unit step), value from measurement will achieve X% of real value within time specified by table: Time of measurement Percent of real value 1 filtering constant 63,2% 2 filtering constants 86,5% 3 filtering constants 95,0% 4 filtering constants 98,2% 5 filtering constants 99,3% 8.2.6.2.2.4. Engineering units 66 Function - Defines a name for engineering units for measured values. Data type - text Range - letters and numerals, max 16 characters