Download User`s Manual - Frequency inverter
Transcript
segment after powering up. 1: memory It memorizes PLC running status when powering down, including powering down time stage, running frequency, and run time. It re-starts running after powering up and enters into the stage automatically. It takes segment defined frequency and continues running of residual time. Multi-segment speed frequency 1 F8.01 - Upper limit frequency–upper limiting frequency 5.0 Multi-segment speed frequency 2 F8.02 - Upper limit frequency–upper limiting frequency 10.0 Multi-segment speed frequency 3 F8.03 - Upper limit frequency–upper limiting frequency 15.0 Multi-segment speed frequency 4 F8.04 - Upper limit frequency–upper limiting frequency 20.0 Multi-segment speed frequency 5 F8.05 - Upper limit frequency–upper limiting frequency 25.0 Multi-segment speed frequency 6 F8.06 - Upper limit frequency–upper limiting frequency 37.0 Multi-segment speed frequency 7 F8.07 - Upper limit frequency–upper limiting frequency 50.0 The signs of multi-segment speed determine the running direction. Negative means reverse running direction。Frequency input method is set by F0.05 , and starting and stop commands are set by F0.04. 1st segment speed running time F8.08 0.0-6000.0 10.0 2nd segment speed running time F8.09 0.0-6000.0 10.0 3rd segment speed running time F8.10 0.0-6000.0 10.0 4th segment speed running time F8.11 0.0-6000.0 F8.12 10.0 5th segment speed running time 76