Download Reach Drive User Manual
Transcript
! 413 ATTENTION: When operating the drive with encoder feedback selected (Feedback Select (80) = 3 (Encoder)), a loss of encoder signal may produce an overspeed condition. For differential encoders, Motor Fdbk Type (412) should be selected as option 1 or 3 to detect the loss of an encoder signal. The user is responsible for ensuring that the driven machinery, all drive-train mechanisms, and application material are capable of safe operation at the maximum operating speed of the drive. Overspeed detection in the drive determines when the drive shuts down. The factory default for overspeed detection is set to 10.0 Hz (or 300.0 RPM) greater than the Maximum Speed (82). Failure to observe this precaution could result in equipment damage, sever injury or loss of life. Encoder PPR Range: 2 to 20000 PPR [1 PPR] Default: 1024 PPR Access: 1 Path: Motor Control>Speed Feedback See also: Contains the encoder pulses per revolution. For improved operation in FVC Vector mode, PPR should meet or exceed (64 x motor poles). 414 Enc Position Fdbk Range: -/+ 2147483647 [1] Default: Read Only Access: 1 Path: Motor Control>Speed Feedback See also: Displays raw encoder pulse count. For single channel encoders, this count will increase (per rev.) by the amount in Encoder PPR (413). For quadrature encoders, this count will increase by 4 times the amount defined in Encoder PPR (413). 415 Encoder Speed Range: -/+ 420.0 Hz or -/+ 25200.0 RPM [0.1Hz or 0.1 RPM] Default: Read Only Access: 1 See also: 79 Path: Motor Control>Speed Feedback Provides a monitoring point that reflects speed as seen from the feedback device. Parameter Descriptions 3-105