Transcript
Diagnostics and troubleshooting 8.2 Diagnostic messages Wire-Break Diagnostics The following table lists some of the possible causes of an encoder wire-break and some possible actions you can take to remedy the problem. The diagnostic function cannot identify the exact cause of the fault. It is also not possible for wire-break diagnostics to detect all connection and hardware faults. Table 8- 6 Encoder broken wire diagnostics Possible causes Possible corrective actions Encoder cable broken or not plugged in. Check the encoder cable to ensure that wires are properly connected. Encoder has no quadrature signals. Incorrect pin assignment. Encoder signals short-circuited. The encoder is not operating. Ensure that your installation conforms to the encoder specifications and to the FM 352-5 module requirements. Check the parameters that you assigned in the "Hardware Configuration" dialog, "Parameters" tab to ensure correct setup. Note When broken wire diagnostics is enabled and the SSI absolute encoder is not selected, signals A, /A (inverse), B, /B (inverse), and N, /N (inverse) signals are checked. When broken wire diagnostics is enabled for an SSI absolute encoder, only signals D and /D (inverse) are checked. FM 352-5 high-speed Boolean processor 190 Operating Manual, 05/2011, A5E00131318-04