Sigma II User’s Manual
5.8.3
Chapter 5: Parameter Settings and Functions
Using More Than One Servodrive
The following diagram is an example of the wiring when more than one servodrive
is used.
Power supply
R S T
MCCB
Noise filter
Power
Power Supply
Supply
ON
OFF
1RY
1MC
1MC
SUP
Fuse
1MC
Fuse
L1 SGDH
L2 Servo
L3 amplifier
L1C
M
L2C
+24V 1RY
CN1
31 ALM+
32
Fuse
ALM-
L1 SGDH
L2 Servo
L3 amplifier
L1C
M
L2C
CN1
31 ALM+
32
Fuse
ALM-
L1 SGDH
L2 Servo
L3 amplifier
L1C
M
L2C
CN1
31 ALM+
32
ALM-
0V
Note: Wire the system to comply to National Electrical Code.
Connect the alarm output (ALM) terminals for the three servo amplifiers in series to
enable alarm detection relay 1RY to operate. The output transistor is turned OFF
when the ALM output signal enters an alarm state.
Multiple servos can share a single MCCB or noise filter. Always select an MCCB or
noise filter that has enough capacity for the total power capacity (load conditions) of
5-121