DCM 5 Installation
Meter-Contacts
O to V
logging and control. The
optional expansion board
uses these as its
hardware inputs H, I, K, L,
M, and N.
Eight digital inputs,
individually configurable
as meter-volume or
contact set inputs.
Phantom or
Virtual Contact
Inputs W to Z
Relays 1 to 5
Phantom digital inputs
used for logging and
control.
Frequency
Outputs 6 to 9
DC isolated,
non-mechanical
0 to 400Hz
AC Line powered outputs
ON/OFF controls
Contact sets are flow and level switches. They are used to
interlock and to initiate feeds. Input ‘O’ is defaulted as the
Sensor Flow Switch safety interlock and should not be
changed,
Meter-volume inputs calculate flow rates using turbine
(paddlewheel) ‘K’ factors, display flow rate, totalize volume
today and this year
Example: A Paddlewheel Turbine pulse GPM input on ‘P’
may be converted to a minimum recirculation flow switch on
‘X’.
Controller powered outputs switch 120 VAC pumps, valves
& solenoids ON/OFF. Log time ON. Relay 1 is SPST only.
Relays 2-5 are SPDT for motorized valves requiring power
OPEN & power CLOSE if needed. Outputs can alarm on
runtime per actuation and per day.
Variable speed pulse output feeds, with presets for popular
ProMinent and other pump ml/stroke and maximum rates.
Calculates & logs volume fed.
Use volume fed to calculate ppm & inventory.
4.2. Communications
Ethernet LAN TCP-IP:
The DCM5 controller contains a 10 Base T, RJ45 Ethernet port that can use a fixed or Dynamic IP
address assigned by your network server. The controller operates as an HTML micro-server for
command & control using Microsoft® Internet Explorer, Apple® Safari and Mozilla’s® Firefox and other
internet browsers available on most computers.
Logged data is served as an XML file in response to an HTML request. This feature makes
configuration easy using common Ethernet network browsers already installed on most computers, and
easily supported by local IT departments. This port also supports the ProMinent Trackster download,
auto-poll, analysis and report software package.
USB Services
All DCM5 controllers include a USB port which is only used for factory diagnostics, and is not an option
for remote monitoring and control functions.
Configuration-View sets
DCM5 Controllers are loaded with at least 4 View-Configurations (more coming soon). One of these is
selected when the controller is manufactured to be the ‘as shipped’ view-configuration.
Installed View-Configurations represent typical uses of the controller that allow loading a configuration
that closely fits the intended use of the DCM5. For example, residual chlorine sensors and all
associated options related to them can be eliminated for an installation with pH and ORP only.
Configurations and Views are preloaded to support various options. Additional expanded capabilities
and their associated standard views are planned.