Download DCM 5 Installation - ProMinent Fluid Controls, Inc.
Transcript
DCM 5 Installation Meter-Contacts O to V logging and control. The optional expansion board uses these as its hardware inputs H, I, K, L, M, and N. Eight digital inputs, individually configurable as meter-volume or contact set inputs. Phantom or Virtual Contact Inputs W to Z Relays 1 to 5 Phantom digital inputs used for logging and control. Frequency Outputs 6 to 9 DC isolated, non-mechanical 0 to 400Hz AC Line powered outputs ON/OFF controls Contact sets are flow and level switches. They are used to interlock and to initiate feeds. Input ‘O’ is defaulted as the Sensor Flow Switch safety interlock and should not be changed, Meter-volume inputs calculate flow rates using turbine (paddlewheel) ‘K’ factors, display flow rate, totalize volume today and this year Example: A Paddlewheel Turbine pulse GPM input on ‘P’ may be converted to a minimum recirculation flow switch on ‘X’. Controller powered outputs switch 120 VAC pumps, valves & solenoids ON/OFF. Log time ON. Relay 1 is SPST only. Relays 2-5 are SPDT for motorized valves requiring power OPEN & power CLOSE if needed. Outputs can alarm on runtime per actuation and per day. Variable speed pulse output feeds, with presets for popular ProMinent and other pump ml/stroke and maximum rates. Calculates & logs volume fed. Use volume fed to calculate ppm & inventory. 4.2. Communications Ethernet LAN TCP-IP: The DCM5 controller contains a 10 Base T, RJ45 Ethernet port that can use a fixed or Dynamic IP address assigned by your network server. The controller operates as an HTML micro-server for command & control using Microsoft® Internet Explorer, Apple® Safari and Mozilla’s® Firefox and other internet browsers available on most computers. Logged data is served as an XML file in response to an HTML request. This feature makes configuration easy using common Ethernet network browsers already installed on most computers, and easily supported by local IT departments. This port also supports the ProMinent Trackster download, auto-poll, analysis and report software package. USB Services All DCM5 controllers include a USB port which is only used for factory diagnostics, and is not an option for remote monitoring and control functions. Configuration-View sets DCM5 Controllers are loaded with at least 4 View-Configurations (more coming soon). One of these is selected when the controller is manufactured to be the ‘as shipped’ view-configuration. Installed View-Configurations represent typical uses of the controller that allow loading a configuration that closely fits the intended use of the DCM5. For example, residual chlorine sensors and all associated options related to them can be eliminated for an installation with pH and ORP only. Configurations and Views are preloaded to support various options. Additional expanded capabilities and their associated standard views are planned. Page 33