PowerMonitor 1000 Data Tables Appendix A Table 21 - Controller Interface Table Parameters CSP File No. N18 CIP Instance 11 Applies to EM2, EM3 only No. of Elements 8 No. of Words 8 Data Type Integer Data Access Write Table 22 - Controller Interface Table Element No. Modbus Address Element Name Default Value Range Description 0 40801 Password 0 0…9999 When writing the complete table this parameter allows the input data to be accepted. When writing a single parameter the separate password table should be used. Returns -1 on a read. 1 40802 Controller Command Word 0 0…1 Bit 0 = When this bit is written to the power monitor it signals the end of the demand period. The power monitor resets the bit to 0 and sends the end of demand broadcast to all of the slaves configured for the master/slave demand system. The power monitor must be configured as a Master for external demand pulse input. Bit 1…15 = Reserved 2 40803 Reserved 0 0 Reserved for future use. 3 40804 Reserved 0 0 Reserved for future use. 4 40805 Reserved 0 0 Reserved for future use. 5 40806 Reserved 0 0 Reserved for future use. 6 40807 Reserved 0 0 Reserved for future use. 7 40808 Reserved 0 0 Reserved for future use. Rockwell Automation Publication 1408-UM001D-EN-P - September 2013 87