Parameters
Parameter list
r0944
CO: Counter for fault buffer changes / Fault buff change
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Data set: -
Units group: -
Unit selection: -
Min
-
Max
-
Factory setting
-
Description:
Displays fault buffer changes. This counter is incremented every time the fault buffer changes.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109
r0945[0...63]
Fault code / Fault code
Access level: 3
Calculated: -
Data type: Unsigned16
Data set: -
Can be changed: -
Scaling: -
Units group: -
Unit selection: -
Min
-
Max
-
Description:
Displays the numbers of faults that have occurred.
Dependency:
Refer to: r0947, r0948, r0949, r2109, r2130, r2133, r2136
Factory setting
-
Notice:
The properties of the fault buffer should be taken from the corresponding product documentation.
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Fault buffer structure (general principle):
r0945[0], r0949[0], r0948[0], r2109[0] --> actual fault case, fault 1
...
r0945[7], r0949[7], r0948[7], r2109[7] --> actual fault case, fault 8
r0945[8], r0949[8], r0948[8], r2109[8] --> 1st acknowledged fault case, fault 1
...
r0945[15], r0949[15], r0948[15], r2109[15] --> 1st acknowledged fault case, fault 8
...
r0945[56], r0949[56], r0948[56], r2109[56] --> 7th acknowledged fault case, fault 1
...
r0945[63], r0949[63], r0948[63], r2109[63] --> 7th acknowledged fault case, fault 8
r0946[0...65534] Fault code list / Fault code list
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Data set: -
Units group: -
Unit selection: -
Min
-
Max
-
Factory setting
-
Description:
Lists the fault codes stored in the drive unit.
Dependency:
The parameter assigned to the fault code is entered in r0951 under the same index.
r0947[0...63]
Fault number / Fault number
The indices can only be accessed with a valid fault code.
Description:
Access level: 2
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Data set: -
Units group: -
Unit selection: -
Min
-
Max
-
Factory setting
-
This parameter is identical to r0945.