Download Technical Reference
Transcript
Capstone Turbine Corporation • 21211 Nordhoff Street • Chatsworth • CA 91311 • USA Technical Reference: Dual Mode Controller (DMC) Technical Information Voltage [per Unit] Microturbine & UVR Undervoltage Response 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 UVR Settings Microturbine Default Settings 0 2 4 6 8 10 Time [sec] Figure 22. MicroTurbine and UVR Coordination Utility Fault (sag) 5 - 30 min Normal Fault Normal Normal Fault Normal Utility Voltage Protected Load Voltage DMC Switch M1 Closed GC Enable (2 to grd) Active UVR does not open M1 Inactive SA Enable (3 to grd) Stop Start/Stop (4 to grd) Inactive (Open) SA Load (A to B) MicroTurbine Output MicroTurbine State MT Fault Detection Grid Connect Reconnect Time Delay Hot Standby Grid Connect Figure 23. Fast Transfer with DMC – GC to Hot Standby to GC 410039 Rev. G (April 2008) Page 43 of 73 Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without incurring any obligation either with respect to equipment previously sold or in the process of construction.