CHAPTER 5 PARAMETERS
Program Mode
Number of steps
• Specifies the number of steps in the current pattern.
Function
Setting Range
1 to 16
Unit
None
Default
8
Setting
See
F Related description
3.5 Setting Patterns (page 3-14)
F Related parameter
All parameters in the program mode
Step 0 time (Step time)
Target SP 0 (Rate of rise programming)
to
Step 7 SP (Step time)
Target SP 7 (Rate of rise programming)
Conditions of Use
Within the number of steps.
Step 8 SP (Step time)
to
Step 15 SP (Step time)
• Sets the SP of steps 0 to 15 when the step time is set.
• Sets target SP 0 to 7 when the rate of rise programming is set.
Function
• During temperature input, the decimal point position is dependent on the currently selected sensor, and during analog input on the results of scaling.
Setting Range
SP lower limit to SP upper limit
Unit
EU
Default
0
Setting
See
5--12
F Related description
3.5 Setting Patterns (page 3-14)
4.3 Ramp Rise Rate Setup Program (page 4-9)
F Related parameters
All parameters in the program mode
“Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup
mode)
“Step time/Rate of rise programming” (expansion mode)