To avoid contact noises, the OptiClimate comes standard with rubber shock absorbers
that are suitable for suspended installation. If the OptiClimate is going to be placed on a
solid base, the rubber shock absorbers supplied with the connection set need to be used.
Special insulating springs can be supplied for areas that have to be extra quiet. Placing
the insulating springs on the supports will ensure that the unit has automatic fall to the
condensation drain.
Installation of rubbers
Installation
of insulating springs
The rubber feet with which the OptiClimate is placed on the pallet are use to suspend the
unit by means of thread ends. A thread end, a large washer and a nut must be fitted.
(not supplied)
Electrical connections