Transcript
Fig. 4.5 - Linear and square-law characteristic(a), formation of U/f characteristic (b) 4.6.Elimination of frequencies With purpose of elimination of undesirable output frequencies which can result in the resonant phenomena of the drive, it is possible to determine 3 ranges called "ranges of elimination”. Their options can be set up by parameters: Par. 1.90 - bottom frequency of elimination range 1 [Hz] Par. 1.91 - top frequency of elimination range 1 [Hz] Par. 1.92 - bottom frequency of elimination range 2 [Hz] Par. 1.93 - top frequency of elimination range 2 [Hz] Par. 1.94 - bottom frequency of elimination range 3 [Hz] Par. 1.95 - top frequency of elimination range 3 [Hz] Referencing-unit of the electric drive will "bypass" frequencies which are chosen with the help of the parameters above mentioned. Fig. 4.6 shows influence of range elimination procedure on output frequency of referencing-unit. 4.6.Blocking a direction of drive rotation There is a possibility of partial blocking of the electric drive with permission of operation only in one direction. In this case irrespective of control signals the frequency converter will rotate the drive only in one direction. Parameter 1.65 allows to define this option: "Reverser" - operation in two directions (option relative) "To the left" - operation in one direction "To the right" - operation in one direction