Download User`s Manual
Transcript
3. Changing PV Input Type 4. Setting Control Output Type (except for a Position Proportional Controller) The following operating procedure describes an example of changing PV input terminal the setting of K-type thermocouple (-200.0 to 500.0⬚C) to RTD Pt100 Thermocouple/mV/V input.............................. 12 - 13 (-200.0 to 500.0⬚C) and a measurement range of 0.0 to 200.0⬚C. RTD input .................................................. 11 - 12 - 13 The following operating procedure describes an ex- Control output terminal Values in parentheses are setpoints ample of changing time proportional PID relay out- Time proportional PID relay (0)/on-off(3) output........................... 1 - 2 - 3 put (0: factory-set default) to current output (2). Current (2)/time proportional PID voltage pulse (1) output............. 16 - 17 For details on the output terminals for heating/cooling control, see “6. Terminal Wiring Diagrams ” in Installation User’s Manual . 1. Bring the operating display into view (display appears at power-on) PV2 RST lamp ON. PV 1. Bring the operating display into view (display appears at power-on). PVE1 PVE2 PV2 TME 1 2 3 4 AL 1 PRG RST HLD LOC MAN CAS SET/ENT MODE PT.No SP: DISP RUN 0.0°C PTNO: 0 TM=------- RESET RST lamp ON. SET/ENT Press the key for more than 3 seconds to call up the main menu “PROG”. 10. Press the PVE2 AL 1 PRG RST HLD LOC MAN CAS SET/ENT programming main menu MODE SP: DISP RUN IN1 SET/ENT Press the key for more than 3 seconds to call up the main menu “PROG”. SETUP Pt2 = MODE PT.No SET/ENT DISP RUN MODE RUN 7. Press the “OUT”. PROG Press the “STUP”. key once to display the main menu 11. Press the “UNI1”. SET/ENT password input main menu MODE MODE PT.No 4. SET/ENT UNI1 SET/ENT #2 SETUP °C = MODE 12. SET/ENT RUN MODE PT.No RUN 5. Press the “UPMD”. RH1 SET/ENT 8. MODE PT.No RH1 SET/ENT DISP RUN OT1 SET/ENT RUN Press the “MD”. SET/ENT RUN MODE Press the MODE PT.No MODE 9. RH1 SET/ENT RUN PT.No 7. MODE RUN #1 SET/ENT MODE OT1 RUN SET/ENT RUN MODE RUN MODE V.AT SET/ENT #1 changing! ON = MODE RESET 10. 5. Press the “UPMD”. key once to display the main menu 10. Press the SET/ENT RUN Press the “STUP”. SET/ENT SET/ENT RESET MODE OT1 SET/ENT DISP RUN #1 Press the “UPMD”. RUN MODE V.AT SET/ENT DISP RUN key once to display the main menu Press the “MD”. MODE 4. Press the “PARA”. #1 MODE SET/ENT 11. RUN RESET SET/ENT RUN MENU:UPMD/VALV valve auto tuning V.AT MODE RUN MODE SET/ENT DISP RUN RL1 = 5. Press the “UPMD”. MODE MODE IN1 Press the “MD”. SET/ENT key once to display the submenu 12. SET/ENT MODE PT.No #1 RUN Press the SET/ENT key for more than 3 seconds. This returns you to the display shown at power-on (figure below). PV2 MENU:UPMD/VALV valve auto tuning V.AT SET/ENT MODE RL1 DISP RST lamp ON. 7. PVE1 PVE2 TME 1 2 3 4 PRG RST HLD LOC MAN CAS SET/ENT MODE PT.No #4 changing! 0.0 = MODE RESET = 6. Press the “MD”. MENU:UPMD/IN input 1 type select IN1 SET/ENT MODE PT.No Press the DISP RUN SET/ENT RUN SP: DISP MODE Blinks during change DISP PT.No RUN RESET 10. SET/ENT Press the key once. The display momentarily becomes blank (which is normal), indicating the parameters have been initialized. MENU:UPMD/INIT Parameter initialize INI #1 SETUP ON = MODE SET/ENT SET/ENT DISP RUN MODE DISP PT.No RESET RUN RESET key once to display the submenu UP mode set SETUP sub menu SETUP ERR RUN MODE PT.No DISP RUN RESET RESET RUN RESET 11. SET/ENT key for more than 3 seconds. This returns you to the display shown at power-on (figure below). RST lamp ON. valve control SETUP sub menu SEGNO: 0/ 0 RCY: 0/ 0 Press the PV2 VALV 0.0°C PTNO: 0 TM=------- ● List of Control Output Types Parameter Symbol Name of Parameter Blinks during change. Setpoint 0 1 2 3 RESET MODE PT.No Control Output Types Time proportional PID relay contact output (terminals 1 - 2 - 3 ) Time proportional PID voltage pulse output (terminals 16 - 17 ) Current output (terminals 16 - 17 ) On/off control relay contact output (terminals 1 - 2 - 3 ) The following 4 to 12 are displayed only for heating/ cooling type controllers. key once to register the setpoint. MENU:UPMD/IN input 1 range low RL1 Blinks during change. RESET #4 SETUP 0.0 = SET/ENT DISP RUN = RESET PV PVE1 PVE2 TME 1 2 3 4 AL 1 PRG RST HLD LOC MAN CAS MODE DISP PT.No RUN MODE PT.No OT1 #1 changing! Pt2 = 17. #1 changing! ON MD #1 Press the key three times to display the submenu “VALV”. SET/ENT DISP PT.No Press the or key to display the required setpoint. The figure below shows an example of setting the PV input type to a Pt100 resistance temperature detector (-200.0°C to 500.0°C). key to display “ON”. SET/ENT UP550 configuration SETUP main menu DISP 13. Press the SET/ENT DISP RUN Control output type 4 5 6 7 8 9 10 11 12 SP: DISP RUN RESET PTNO: 0 TM=------- 0.0°C SEGNO: 0/ 0 RCY: 0/ 0 RESET key for more than 3 seconds. This returns you to the display shown at power-on (figure below). PRG lamp or LOC lamp ON. PV2 PV PVE1 PVE2 TME 1 2 3 4 AL 1 PRG RST HLD LOC MAN CAS SET/ENT 9. RESET PV RESET MENU:UPMD/IN input 1 range low SET/ENT RUN Press the UPMD SET/ENT Calibration has ended unsuccessfully if the indication changes from “ON” to “ERR”. Check the feedback input wiring and carry out automatic calibration again. UP mode set SETUP sub menu RESET #4 Press the or key to display the required setpoint. The figure below shows an example of setting the minimum value of the PV input range to 0.0°C. SETUP typeK3 = 9. INI SET/ENT MENU:UPMD/IN input 1 type select RUN MENU:UPMD/INIT parameter initialize #1 SETUP OFF PT.No DISP DISP PT.No RESET 16. DISP PT.No key once to display the main menu SET/ENT 11. SETUP -200.0 = SET/ENT DISP SET/ENT MODE RESET RESET MD MENU:UPMD/IN input 1 range low Press the key once to display the parameter “IN1” (PV input type). = DISP UP mode set SETUP sub menu 1 8. #1 SETUP OFF RESET Go to step 13. MD RUN key once to display the parameter INI key once to display the main menu SET/ENT Calibration has ended successfully when the indication changes from “ON” to “OFF”. UP550 configuration SETUP main menu 6. MODE SET/ENT MENU:UPMD/INIT parameter initialize setup parameter SETUP main menu DISP PT.No key once to display the submenu SET/ENT Press the “INI”. PARA DISP #3 RESET 8. password input main menu SETUP ON = RESET key once to display the main menu PT.No SET/ENT RESET RESET MENU:UPMD/VALV valve auto tuning UPMD SETUP 2 = PT.No RESET RUN key once to register the setpoint. 5. UP550 configuration SETUP main menu DISP PT.No STUP Blinks during change. Press the key once. The controller automatically calibrates the valve position (fully open or closed). setup parameter SETUP main menu RESET MENU:UPMD/OUT output 1 select UPMD MODE RESET SET/ENT PARA Blinks during change. RUN DISP PT.No key once to display the main menu SET/ENT DISP DISP PT.No RESET Press the “PARA”. parameter initialize SETUP sub menu RESET MENU:UPMD/VALV valve auto tuning #1 changing! 2 = 4. key twice to display the submenu INIT programming main menu PT.No SET/ENT Press the “INIT”. key to display “ON”. DISP RUN 7. PROG 3. RESET MENU:UPMD/OUT output 1 select AL RUN 9. SEGNO: 0/ 0 RCY: 0/ 0 DISP PT.No Press the 0.0°C PTNO: 0 TM=------- RESET SET/ENT input set SETUP sub menu PT.No MODE RESET RUN SET/ENT SETUP OFF = SP: DISP Press the key for more than 3 seconds to call up the main menu “PROG”. PT.No Blinks during change. Press the key once to display the parameter “RL1” (minimum value of PV input range). IN MODE RUN key once to display the main menu PT.No SET/ENT SET/ENT DISP password input main menu DISP PT.No 15. MODE PT.No SETUP 200.0 = RESET key once to display the submenu “IN”. 2. V.AT MODE In steps 2 and later, illustrations of the LCD are cited to explain the procedure. key once to display the parameter MENU:UPMD/VALV valve auto tuning STUP Press the or key to display the required setpoint. The figure below shows an example of setting to current output (4 to 20 mA DC). DISP PT.No Press the 3. Press the “STUP”. key once to register the setpoint. DISP RUN SET/ENT DISP PT.No PRG RST HLD LOC MAN CAS PT.No PT.No #1 #3 MENU:UPMD/IN input 1 range high UP mode set SETUP sub menu SET/ENT SET/ENT MODE RESET key once to display the main menu SET/ENT 6. MD SET/ENT SETUP 0 = 1 2 3 4 SET/ENT DISP PT.No 14. RESET RESET changing! 200.0 = RESET key once to display the submenu SEGNO: 0/ 0 RCY: 0/ 0 SET/ENT SET/ENT PT.No 6. Press the “V.AT”. programming main menu Press the key once to display the parameter “OT1” (control output type). setup parameter SETUP main menu MENU:UPMD/IN input 1 range high UP550 configuration SETUP main menu 8. PROG PT.No Press the “PARA” DISP Press the or key to display the required setpoint. The figure below shows an example of setting the maximum value of the PV input range to 200.0°C. UPMD SET/ENT MODE PT.No 13. RUN MENU:UPMD/OUT output 1 select SETUP 500.0 = RESET key once to display the main menu PTNO: 0 TM=------- RESET PVE2 TME 1 SET/ENT DISP PT.No 4. #3 MODE PV PVE1 AL RESET MENU:UPMD/IN input 1 range high DISP RUN 0.0°C DISP PT.No PARA SET/ENT MODE RESET key once to display the main menu SET/ENT setup parameter SETUP main menu RUN SET/ENT output set SETUP sub menu STUP Press the key once to display the parameter “RH1” (maximum value of PV input range). PARA DISP Press the key for more than 3 seconds to call up the main menu “PROG”. DISP PT.No RESET key once to display the main menu MODE .SP: L SET/ENT 3. Press the “STUP”. SET/ENT Press the “PARA”. 2. PT.No DISP RUN SET/ENT RST lamp ON. In steps 2 and later, illustrations of the LCD are cited to explain the procedure. OUT password input main menu SET/ENT 1 key twice to display the submenu DISP PT.No key once to display the parameter MENU:UPMD/IN input 1 unit select STUP PV2 PRG RST HLD LOC MAN CAS RESET SET/ENT 3. Bring the operating display into view (display appears at power-on). PVE2 AL MAN lamp ON. SEGNO: 0/ 0 RCY: 0/ 0 DISP PT.No RESET Initializing the above parameter setpoints may initialize the registered operating/setup parameter setpoints. Check that they are correct. If any of them has been changed to its initial value, set it to a required value. 1. PV In steps 2 and later, illustrations of the LCD are cited to explain the procedure. 2. #1 CAUTION PVE1 1 2 3 4 0.0°C PTNO: 0 TM=------- RESET programming main menu SET/ENT PV2 PT.No key once to register the setpoint. 6. Initializing Parameters Be sure to follow the steps below after a change of setting has been made to the data item PV Input Type, PV Input Range or PV Input Scale. TME PT.No MENU:UPMD/IN input 1 type select PROG PRG lamp or LOC lamp ON. PVE1 1 2 3 4 (for a Position Proportional Controller Only) Bring the operating display into view (display appears at power-on). TME SEGNO: 0/ 0 RCY: 0/ 0 SET/ENT 1. PV In steps 2 and later, illustrations of the LCD are cited to explain the procedure. 2. 5. Calibrating Valve Position The following operation describes a procedure of inputting a feedback signal from a control valve to calibrate the full closed and full open positions of the valve automatically. To calibrate the valve position, you need to carry out wire connections and bring the controller into manual mode. For connections, see “6. Terminal Wiring Diagrams” in Installation User’s Manual and for entering the manual mode, see “6. Switching between AUTO and MAN” in Operations User’s Manual . If the controller is in RESET mode, you need to bring the controller into program operation (RUN) or local operation (LOCAL). For entering the program operation, see “5. Switching between RUN and RESET Modes” in Operations User’s Manual , and entering the local operation, see “11, Switching to Local-mode (LOCAL) Operation” in Operations User’s Manual MODE PT.No .SP: L DISP RUN RESET PTNO: 0 TM=------- 0.0°C SEGNO: 0/ 0 RCY: 0/ 0 Heating-side relay output (terminals 1 - 2 - 3 ), cooling-side relay output (terminals 48 - 49 - 50 ) Heating-side pulse output (terminals 16 - 17 ), cooling-side relay output (terminals 48 - 49 - 50 ) Heating-side current output (terminals 16 - 17 ), cooling-side relay output (terminals 48 - 49 - 50 ) Heating-side relay output (terminals 1 - 2 - 3 ), cooling-side pulse output (terminals 46 - 47 ) Heating-side pulse output (terminals 16 - 17 ), cooling-side pulse output (terminals 46 - 47 ) Heating-side current output (terminals 16 - 17 ), cooling-side pulse output (terminals 46 - 47 ) Heating-side relay output (terminals 1 - 2 - 3 ), cooling-side current output (terminals 46 - 47 ) Heating-side pulse output (terminals 16 - 17 ), cooling-side current output (terminals 46 - 47 ) Heating-side current output (terminals 16 - 17 ), cooling-side current output (terminals 46 - 47 ) RESET If the type of Input is voltage, also configure the PV Input Decimal Point Position (SDP1), Maximum Value of PV Input Scale (SH1), and Minimum Value of PV Input Scale (SL1) parameters that follow this step. 18. Press the SET/ENT key for more than 3 seconds. This returns you to the display shown at power-on (figure below). PV2 RST lamp ON. PV PVE1 PVE2 TME 1 2 3 4 AL 1 PRG RST HLD LOC MAN CAS SET/ENT MODE PT.No SP: DISP RUN RESET PTNO: 0 TM=------- 0.0°C SEGNO: 0/ 0 RCY: 0/ 0 IM 05E01C02-02E (2)