Download User`s Manual

Transcript
● Cable Specifications and Recommended Cables
NOTE
Model UP350
Program Controller
User’s Manual
Installation
IM 05E01D02-01E
Purpose
2nd Edition: Jul 1, 2001
To install the controller, select a location where:
(1) no one may accidentally touch the terminals,
(2) mechanical vibrations are minimal,
(3) corrosive gas is minimal,
(4) temperature can be maintained at about 23°C and the fluctuation is minimal,
(5) no direct radiant heat is present,
(6) no magnetic disturbances are caused,
(7) no wind blows against the terminal board (reference junction compensation
element),
(8) no water is splashed,
(9) no flammable materials are around,
Name and Manufacturer
Power supply, grounding, relay contact outputs 600 V PVC insulated wires, JIS C 3307, 0.9 to 2.0 mm2
Thermocouple
Shielded compensating lead wires, JIS C 1610,
(See Yokogawa Electric's GS 6B1U1-E.)
150mm
150mm
150mm
150mm
Shielded wires (three conductors), UL2482 (Hitachi Cable)
Other signals
Shielded wires
Applicable wire size
Tightening torque
Contact Outputs
UP350
UP350
Unit: mm
■ How to Use the Manuals
Media
Describes the tasks (installation, wiring, and others) required
to make the controller ready for operations.
Describes examples of setting PV input types, and control
Initial Settings output types. Making settings described herein and program
creation in Programming User’s Manual allow you to carry
out basic control.
Describes examples of creating basic programs. See Program
Program creation
Programming
Pattern Setup Charts on the back of Installation User’s Manual,
and program functions.
Operating
Describes key operation sequences. For operation control
Operations
procedures
through external contact inputs, see the back of Installation
and troubleshooting
User’s Manual.
Brief operation
Contains the parameter map used as a guideline for setting
Parameters
and setpoint recording
parameters and lists of parameters for recording User Settings.
Basic operation
Detailed description
of functions
A2-size paper,
front
Small bracket
1 to 10 mm (Panel thickness)
A2-size paper,
front
General installation
Side-by-side close installation
117 min.
A2-size paper
back and front
[(N-1)96+92]
A2-size paper,
back
+0.8
0
+0.8
0
Installation
Description
92
Setup
91.8
96
96
Large bracket
100
112
11
A2-size paper,
back and front
145 min.
(53)
User’s Manual Explains more advanced applications than those found in the 4 CD-ROM
hardcopy user’s manuals (A2 size).
(Reference)
92
"N" stands for the number of controllers to be
installed.
However, the measured value applies if N 5.
+0.8
0
1. Safety Precautions
The following symbol is indicated on the controller to ensure safe use.
92
+0.8
0
(25)
After opening the mounting hole on the
Large bracket
(top mounting hardware) panel, follow the procedures below to install
the controller:
1. Insert the controller into the opening
from the front of the panel so that the
terminal board on the rear is at the far
side.
Terminal board
2. Set the brackets in place on the top and
bottom of the controller as shown in the
figure on the left, then tighten the screws
Insert a screwdriver into the
of the brackets. Take care not to overbrackets to tighten the screws.
tighten them.
IMPORTANT
Direction to insert the
controller
Insert the controller
into the opening at
the front of the panel.
Before using the controller, check that the model and suffix codes match your order.
Model
Suffix Code
UP350
Type
Description
Small bracket
-0
Optional functions
None
With communication
● Installation Position
Install the controller at an angle within 30° from horizontal
with the front panel facing upward. Do not install it facing
downward. The position of right and left sides should be horizontal.
Must not
exceed 30
30
Rear of
controller
Output signal
4-20 mA DC
Load resistance
600 or less
Output accuracy
0.3% of span under standard operating
conditions (23 2 C, 55 10% RH,
power frequency of 50/60 Hz)
Number of outputs
1 (switched between a voltage pulse output
and current output)
Output signal
On-voltage = 12 V or more
(load resistance: 600 Ω or more)
Off-voltage = 0.1 V DC or less
Resolution
10 ms
■ For AC Relay Wiring
UP350
External DC power supply
External AC power supply
Number of outputs
1
Output signal
Three terminals (NC, NO, and common)
Contact rating
250 V AC or 30 V DC, 3 A (resistance load)
Resolution
10 ms
for controllers with communication
functions.
Maximum baud rate: 9600 bps
23 SDB(+)
Power supply: Rated voltage of 100 to 240 V AC (10%), 50/60 Hz
Power consumption: Max. 20 VA (8.0 W max.)
Internal fuse rating: 250 V AC, 1.6A time-lug fuse
Data backup: Non-volatile memory (can be written to up to
100,000 times)
• Withstanding voltage
- Between primary terminals* and secondary terminals**:
At least 1500 V AC for 1 minute (Note)
- Between primary terminals* and grounding terminal:
At least 1500 V AC for 1 minute (Note)
- Between grounding terminal and secondary terminals**:
At least 1500 V AC for 1 minute
- Between secondary terminals**:
At least 500 V AC for 1 minute
* Primary terminals indicate power terminals and relay
output terminals
** Secondary terminals indicate analog I/O signal, voltage
pulse output, and contact input terminals
Note: The withstanding voltage is specified as 2300 VAC
per minute to provide a margin of safety.
• Insulation resistance: 20 M or more at 500 V DC between
power terminals and grounding terminal
• Grounding resistance: Class 3 grounding (grounding resistance
of 100 or less)
䊏 Receiving 4-20 mA DC Current
Signals with the Controller
PV input * Not configured at factory before shipment
See Initial Settings User’s Manual ,
for more information.
TC input
* When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint “41”).
mV/V input
RTD input
11 A
24
SDA(-)
12 +
12 +
12 +
13 -
13 -
250 Ω 4-20mA
13 13 B
26
RDA(-)
27
SG
NOTE
Installation category (overvoltage category): II (IEC1010-1)
UP
PV event-2 output PVE2 5
1
11
Time event output TME 4
2
12
Power supply
Power supply
L
N
8
CAUTION
Before carrying out wiring, turn off the power to the
controller and check that cables to be connected
are not alive with a tester or the like because there
is a possibility of electric shock.
9
10
Retransmission output
Note: Connecting a 250 Ω resistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal
lugs)
* PV retransmission is configured at factory
before shipment.
14 +
COM 7
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
■ For DC Relay Wiring
Power Supply Specifications
•
•
•
•
• Voltage pulse output
(Standard type: terminals 16 - 17 )
25 RDB(+)
PV event-1 output PVE1 6
1) Provide power from a single-phase instrument power supply. If there is a lot of noise in the power line, insert
an insulating transformer into the primary side of the line and use a line filter (recommended part: ZAC220500U from TDK) on the secondary side.
As a countermeasures against noise, do not place the primary and secondary power cables close to each other.
2) For thermocouple input, use shielded compensating lead wires for wiring. For RTD input, use shielded wires
that have low conductor resistance and cause no significant differences in resistance between the three wires.
The cables to be used for wiring, terminal specifications, and recommended parts are as shown below.
3) Control output relays may be replaced. However, because they have a life of 100,000 times that of the resistance load, use auxiliary relays to turn on/off a load.
4) The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves causes malfunction or
relay failure; always insert a CR filter for use with alternating current or a diode for use with direct current, as
a spark-removal surge suppression circuit, into the line in parallel with the load.
5) When there is possibility of being struck by external lightening surge, use the arrester to protect the instrument.
UP350
1 (switched between a voltage pulse output
and current output)
12 b
Event output
NOTE
Front panel
of controller
Number of outputs
RS-485 communication * Wiring can only be carried out
3
Common
3. How to Install
Universal output system, The output type can be selected
with the software.
• Current output
(Standard type: terminals 16 - 17 )
Control output
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
1) Before carrying out wiring, turn off the power to the controller and check that the cables to be connected are not
alive with a tester or the like because there is a possibility of electric shock.
2) Wiring must be carried out by personnel who have basic electrical knowledge and practical experience.
Program controller (of ordered model): ......................................................... 1
Brackets (mounting hardware): ...................................................................... 1 pair
Unit label: ....................................................................................................... 1
User’s Manuals: .............................................................................................. 4 (A2 size)
User’s Manual (Reference) (CD-ROM version): ........................................... 1
Control Output
NOTE
Relay contact output Note: Select the control output type
from the OT parameter.
NC
1
*Time proportional PID relay contact
output is configured at factory
NO
2
before shipment.
Relay
•
•
•
•
•
Construction, Installation, and Wiring
• Construction: Only the front panel is dust-proof and drip-proof
(protection class IP55)
For side-by-side close installation the controller loses its
dust-proof and drip-proof protection.
• Material: ABS resin and polycarbonate
• Case color: Black
• Weight: About 1 kg or less
• Dimensions: 96 (W) 96 (H) 100 (depth from panel face) mm
• Installation: Panel-mounting type. With top and bottom
mounting hardware (1 each)
• Panel cutout dimensions: 92+0.8
(W) 92+0.8
(H) mm
0
0
• Installation position: Up to 30° upward facing
(not designed for facing downward)
• Wiring: M3.5 screw terminals (for signal wiring and power/
ground wiring as well)
■ UP350 Standard Type (Model UP350-0ⵧ)
CAUTION
Check that the following items are provided:
•
•
•
•
Environmental Conditions
• Normal operating conditions:
Ambient temperature: 0 to 50C (40C or less for side-by-side
close installation)
Temperature change rate: 10C/h or less
Ambient humidity: 20 to 90% RH (no condensation allowed)
Magnetic field: 400 A/m or less
Continuous vibration at 5 to 14 Hz: Full amplitude of 1.2 mm or
less
Continuous vibration at 14 to 150 Hz: 4.9 m/s2 or less
Short-period vibration: 14.7 m/s2, 15 seconds or less
Shock: 147 m/s2 or less, 11 ms
Installation height: Height above sea level of 2000 m or less
Warm-up time: 30 minutes or more after power on
• Transportation and storage conditions:
Temperature: -25 to 70C
Temperature change rate: 20C/h or less
Humidity: 5 to 95% RH (no condensation allowed)
• Effects of changes in operating conditions
- Effects from changes in ambient temperature:
- On voltage or thermocouple input, 1 V/C or 0.01%
of F.S./C, whichever is larger
- On RTD input, 0.05C /C (ambient temperature) or less
- On analog output, 0.05% of F.S./C or less
- Effects from power supply fluctuation (within rated voltage
range)
- On analog input, 1 V/10 V or 0.01% of F.S./10 V,
whichever is larger
- On analog output, 0.05% of F.S./ 10 V or less
Do not use unassigned terminals as relay terminals.
4. How to Connect Wires
Standard type
0
1
Either PV, program setpoint, or control output is output.
Either the retransmission output or the loop power supply
can be used with terminals 14 - 15 .
Number of outputs: 1 (terminals 14 - 15 )
Output signal: 4-20 mA DC
Load resistance: 600 or less
Output accuracy: 0.3% of span under standard operating
conditions (23 2C, 55 10% RH, power frequency of
50/60 Hz)
• Relay contact output
(Standard type: terminals 1 - 2 - 3 )
6. Terminal Wiring Diagrams
COM
(bottom mounting hardware)
Program controller (provided with retransmission output and15V DC
loop power supply as standard)
• Safety: Compliant with IEC1010-1: 1990 and EN61010-1: 1992
Approved by CSA1010
CSA1010 installation category (overvoltage category):
CATII (IEC1010-1)
Approved by UL508
• EMC standards: Complies with EN61326.
The instrument continues to operate at a measuring
accuracy of within 20% of the range during tests.
Retransmission Output
Power is supplied to a two-wire transmitter.
(15 V DC: terminals 14 - 15 )
A resistor (10 to 250 ) connected between the controller
and transmitter converts a current signal into a voltage
signal, which is then read via the PV input terminal.
Supply voltage: 14.5 to 18.0 V DC, max. 21 mA (provided
with a protection circuit against a field short-circuit)
Turn off the power to the controller before installing it on the panel because there is a possibility of electric shock.
Indicates that operating the hardware or software in a particular manner may damage it or result in a system failure.
2. Model and Suffix Codes
Safety and EMC Standards
Loop Power Supply
Panel
Draws attention to information that is essential for understanding the operation and/or features of the controller.
Sales Unit
1
• Number of inputs: 1 (terminals 11 - 12 - 13 )
• Input type: Universal input system. The input type can be
selected with the software.
• Sampling period: 250 ms
• Burnout detection: Functions at TC, RTD, standard signal
(0.4 to 2 V or 1 to 5 V)
Upscale, downscale, and off can be specified.
For standard signal, burnout is determined to have occurred
if it is 0.1 V or less.
• Input bias current: 0.05 A (for TC or RTD b-terminal)
• Measurement current (RTD): About 0.13 mA
• Input resistance: 1 M or more for thermocouple or mV input
About 1 M for DC voltage input
• Allowable signal source resistance: 250 or less for
thermocouple or mV input
Effects of signal source resistance: 0.1 V/ or less
2 k or less for DC voltage input
Effects of signal source resistance: About 0.01%/100 • Allowable wiring resistance: for RTD input
Maximum 150 /wire: Conductor resistance between three
wires should be equal
However, 10 /wire for a maximum range of -150.0 to 150.0C.
Wire resistance effect: 0.1C /10 • Allowable input voltage: 10 V DC for thermocouple, mV, or
RTD input
20 V DC for DC voltage input
• Noise rejection ratio: 40 dB (50/60 Hz) or more in normal mode
120 dB (50/60 Hz) or more in common mode
• Reference junction compensation error: 1.0C (15 to 35C)
1.5C (0 to 15C, 35 to 50C)
• Applicable standards: JIS, IEC, DIN (ITS-90) for thermocouples
and RTD
CAUTION
NOTE
Part Number
T9115YD
PV Input Signals
■ How to Install
The following symbols are used in the hardcopy user’s manuals and in the user’s manual supplied on the CD-ROM.
Display Specifications
• PV display: 4-digit, 7-segment red LED display, character
height of 20 mm
• Setpoint display: 4-digit, 7-segment red LED display character
height of 9.3 mm
• Status indicating lamps: LEDs
5. Hardware Specifications
CAUTION
This symbol on the controller indicates that the operator must refer to an explanation in the user’s manual in order
to avoid the risk of injury or death of personnel or damage to the instrument. The manual describes how the operator
should exercise special care to avoid electric shock or other dangers that may result in injury or loss of life.
3.7mm
or
Target Model
Introduction
• Purpose: PV event outputs (2) and time event output (1)
• Number of outputs: 3 points
• Relay contact rating: 240 V AC, 1 A, or 30 V DC, 1 A
● Terminal Covers (Optional parts)
Never touch the opening at the bottom of the case. It is to be used in the factory at shipping.
Thank you for purchasing the UP350 program controller.
The controller is shipped from the factory with 4 hardcopy user’s manuals (A2 size) and 1 user’s manual on CD-ROM.
The 4 user’s manuals in hardcopy format describe the operating procedures required for basic use. It is recommended that
you refer to these user’s manuals to understand [1] installation, [2] initial settings, [3] program settings, and [4] operating
procedures of the controller.
The CD-ROM contains an User’s Manual (Reference) with descriptions of various functions and setting ranges that can be
set as necessary.
Moreover, the use of an optional parameter setting tool (model: LL100-E10) allows you to easily perform settings and
adjustments with a PC.
Manual Title
3.7mm
NOTE
■ External Dimensions and Panel Cutout Dimensions
Purpose
0.8 N·m or less
7 mm or less
1. Safety Precautions
2. Model and Suffix Codes
3. How to Install
4. How to Connect Wires
5. Hardware Specifications
6. Terminal Wiring Diagrams
-
● Recommended Terminal Lugs
Never place the controller directly on flammable items or equipment.
If the controller has to be installed close to flammable items or equipment, be sure to provide shielding panels all
around the controller, at least 150mm away from every side; the panels should be made of either 1.43mm-thick
metal-plated steel plates or 1.6mm-thick uncoated steel plates.
Contents
-
RTD
0.3 to 1.65 mm2
This manual describes installation, wiring, and other tasks required to make the controller ready for operation.
X-
Signal Isolations
• PV input terminals: Isolated from other input/output terminals.
Not isolated from the internal circuit.
• 15 V DC loop power supply terminals: Not isolated from 4-20
mA analog output and voltage pulse control output. Isolated
from other input/output terminals and internal circuit.
• 4-20 mA analog output terminals (for control output and
retransmission): Not isolated between 4-20 mA outputs and
from 15 V DC loop power supply and voltage pulse control
output. Isolated from other input/output terminals and
internal circuit.
• Voltage pulse control output terminals: Not isolated from 4-20
mA outputs and 15 V DC loop power supply. Isolated from
other input/output terminals and internal circuit.
• Relay contact control output terminals: Isolated between contact
output terminals and from other input/output terminals and
internal circuit.
• Contact input terminals: Not isolated between contact input
terminals and from communication terminals. Isolated from
other input/output terminals and internal circuit.
• Relay contact event output terminal: Not isolated from each
other; isolated from other input/output terminals and the
internal circuit.
• RS-485 communication terminals: Not isolated from contact
input terminals. Isolated from other input/output terminals
and internal circuit.
• Power terminals: Isolated from other input/output terminals and
internal circuit.
• Grounding terminals: Isolated from other input/output terminals
and internal circuit.
Purpose: Run/Reset switching
Number of inputs: 2 points
Input type: Non-voltage contact or transistor open collector input
Input contact rating: 12 V DC, 10 mA or more
On/off determination: For non-voltage contact input, contact
resistance of 1 k or less is determined as “on” and contact
resistance of 20 k or more as “off.”
For transistor open collector input, input voltage of 2 V or
less is determined as “on” and leakage current must not
exceed 100 A when “off.”
• Minimum status detection hold time: About 1 second
7 mm or less
User’s
Manual
Contact Inputs
•
•
•
•
•
Allowable range: 100 to 240 V AC (10%)
(free voltage)
50/60 Hz shared
3
23
13
4
24
14
5
25
15
6
26
16
7
27
17
8
18
9
19
10
20
4-20 mA DC
15 -
Control output
Current / voltage
pulse output
16 +
17 -
4-20 mA DC,
voltage pulse
(12 V)
Load resistance: 600 Ω or less
15 V DC loop power supply
14 +
15 -
* If 15 V DC loop power supply is used,
retransmission output cannot be used.
14.5-18.0VDC
(21 mA DC max.)
Note:Select the control output
type from the OT
parameter.
15 V DC Power Supply Wiring to Two-wire Sensor
12
External
resistor 100
(Note)
* DIS is a setup parameter.
Changing DIS setpoint allows you to change the function of external contact input.
Correspondence between parameter DIS and external contact input functions
When DIS=OFF (Factory-set default)
When DIS=1
No function
Start program 1 when DI1 = ON
Reset program 1 when DI1 = OFF
No function
Start program 2 when DI2 = ON
Reset program 2 when DI2 = OFF
Common
When DIS=2
UP
When DIS=3
Hide setup parameter lock when DI1 = ON
Show setup parameter lock when DI1 = OFF
Start program 1 when DI1 = ON
Reset program 1 when DI1 = OFF
No function
Hold program when DI2 = ON
Cancel hold when DI2 = OFF
Common
DI2 18
13
+5V
Transistor contact
DI1
19
+5V
DI2
18
Two-wire transmitter
COM
14
20
COM 20
Common
Common
DI1 19
Contact
PV input
0.4 to 2.0 V DC signal
4-20mADC
Relay
Contact rating: 12 V DC, 10 mA or more
R
R
UP’s contact
Relay
(Use one with a relay coil rating
less than the UP’s contact rating.)
Diode
(Mount it directly
to the relay coil
terminal (socket).)
UP’s contact
Relay
(Use one with a relay coil
rating less than the UP’s
contact rating.)
CR filter
(Mount it directly
to the relay coil
terminal (socket).)
* OT is a setup parameter.
You can change the settings of the
parameter OT to change the mode of
control output. See Initial Settings
User’sManual , for more information.
15
Correspondence between parameter OT and control output types
OT=0 (factory-set default)
OT=1
OT=2
OT=3
Time proportional control
Relay output (terminals 1 , 2 and 3 )
Time proportional control
Voltage pulse output (terminals 16 and 17 )
Current output
(terminals 16 and 17 )
On-off control
Relay output (terminals 1 , 2 and 3 )
Loop power
supply
14.5 to
18.0 V DC
Note: Connecting a 100 resistor to the terminals is optional.
Model: X010-100-2 (resistor with M3.5 crimp-on terminal lugs)
IM 05E01D02-01E (1)
Program Pattern Setup Charts
See “1. Overview of Program Patterns” and “2. Example of Program Pattern Setup Charts” in the Programming User’s Manual for details on how to use the setting charts.
There are two identical charts shown below because two programs can be registered with the UP350.
Fill in the fields with bold-face borders in the order of steps 1 to 10, as shown below. Then, input these setup data items to the UP350.
1. Maximum value of PV input range: Setpoint of the setup parameter “Maximum Value of PV Input Range (RH)”
2. Minimum value of PV input range: Setpoint of the setup parameter “Minimum Value of PV Input Range (RL)”
3. PV input unit: Setpoint of the setup parameter “PV Input Unit (UNIT)”
4. Program time unit: Setpoint of the setup parameter “Program Time Unit (TMU)”
5. Segment setting method: Setpoint of the setup parameter “Segment Setting Method (SEG.T)”
6. Starting target setpoint: Setpoint of the program parameter “Starting Target Setpoint (SSP)”
7. Start code: Setpoint of the program parameter “Start Code (STC)”
8. Junction code: Setpoint of the program parameter “Junction Code (JC)”
9. Target setpoint, Segment time, PV events 1 and 2, and Time event: Setpoint of each program parameter
10. Draw the program pattern.
System name
Program No.
Segment setting method (SEG.T) 5
UP350 -
Model
Starting target setpoint (SSP) 6
4
Program time unit (TMU)
Program name
Serial No.
Unit
Start code (STC)
7
Junction code (JC)
8
10
3
Maximum value of PV input range (RH) 1
100%
Minimum value of PV input range (RL) 2
0%
1
Segment No.
2
3
4
5
6
7
8
9
10
9
10
Target setpoint (SP)
Segment time (TM)
9
PV event 1
PV event 2
Time event
Event type (AL1)
Event setpoint (A1)
Event type (AL2)
Event setpoint (A2)
On time of time event (EON)
Off time of time event (EOF)
System name
Program No.
Segment setting method (SEG.T) 5
UP350 -
Model
Starting target setpoint (SSP) 6
4
Program time unit (TMU)
Program name
Serial No.
Unit
Start code (STC)
7
Junction code (JC)
8
10
3
Maximum value of PV input range (RH) 1
100%
Minimum value of PV input range (RL) 2
0%
1
Segment No.
2
3
4
5
6
7
8
Target setpoint (SP)
Segment time (TM)
9
PV event 1
PV event 2
Time event
Event type (AL1)
Event setpoint (A1)
Event type (AL2)
Event setpoint (A2)
On time of time event(EON)
Off time of time event(EOF)
IM 05E01D02-01E (2)
User’s
Manual
The following operating procedure describes an example of setting the controller to a K-type thermocouple (-199.9°C to
500.0°C) and the measurement range of 0.0°C to 200.0°C.
Models UT350 / UT320
Digital Indicating Controllers
User’s Manual
Initial Settings
IM 05D01D02-02E
1.
Display screen at power-on
The parameter “IN” for setting the PV input type
appears.
Displays
parameter “IN”.
PV
SP 2
3
7.
Press the
SET/ENT
key once to register the setpoint.
PV
SP 2
4
AL1
2nd Edition: Jul 1, 2001
3
4
SP
SP
2
MAN
3
AL1
A/M
A/M
SET/ENT
SET/ENT
2
MAN
3
3.
NOTE
Press the
or
key to display the required
setpoint. The figure below is an example of the
controller set to a K-type thermocouple (-199.9⬚C to
500.0⬚C). See “Instrument Input Range Codes.”
This manual describes examples of setting PV input types, control output types, and alarm types. Carrying out settings
described herein allows you to perform basic control. Refer to examples of various settings to understand how to set parameters required. Refer to “1. Parameter Map” in Parameters User’s Manual for an easy to understand explanation of
setting various parameters. If you cannot remember how to carry out an operation during setting, press the
key for
more than 3 seconds. This brings you to the display (operating display) that appears at power-on.
PV
3
4
SP
AL1
2
Press the
key once to display the parameter
“RL” (minimum value of PV input range).
SET/ENT
SP 2
3
4
AL1
A/M
A/M
SET/ENT
SET/ENT
2
1. Names and Functions of Front Panel Parts
2. Setting PV Input Type (Setting First at Power-on)
3. Changing PV Input Type
4. Setting Control Output Type
5. Changing Alarm Type
6. Description of Multiple Setpoints and PID
key once to register the reqired
SET/ENT
9.
3
4
SP 2
SP
3
2
MAN
3
AL1
A/M
A/M
SET/ENT
SET/ENT
2
3
6. Light-loader
interface
7. A/M key
4.
1.
2.
SP 2
Press the
key for more than 3 seconds to
call up the menu “OP.PA”.
SET/ENT
8. SET/ENT
key
and
AL1
2
SET/ENT
SET/ENT
5.
Press the
key once to display the parameter
“RH” (maximum value of PV input range).
SET/ENT
SP 2
AL1
Displays
parameter
“RH”.
3
4
2
MAN
3
AL1
SET/ENT
Press the
or
key to display the required
setpoint. The figure below shows an example of
setting the maximum value of PV input range to
200.0⬚C.
AL1
Used to switch or register a parameter. Pressing the key for more than 3 seconds allows you to switch
between the operating display and the menu for operating parameter setting display alternately.
3
2
3
3
4
2
3
3
4
Instrument Input
Range Code
OFF
K
Although only figures of the UT350 front panel are cited in “2. Setting PV Input Type (Setting First at Power-on),” and
thereafter, the UT320 is identical to the UT350 in terms of front panel operation.
2
J
4
5
■ Setting of Main Parameters at the Factory before Shipment
T
6
Factory-set defaults
for heating/cooling type controllers
B
S
R
7
8
9
Thermocouple
N
2. Setting PV Input Type (Setting First at Power-on)
E
NOTE
L(DIN)
10
11
12
13
The controller displays the operating display when the power is
turned on. However, if PV input type has not been set, “IN”
NOTE
appears. In this case, first use the
key to display the input
If the display is as shown on the left,
range code to use, then press the
key to register it. Then,
press the
key to show the
range code for the PV input type you
set the maximum value (RH) and minimum value (RL) of the
use. Then, register the range code
PV input range (for voltage input, set the maximum value (SH)
setting by pressing the
key.
and minimum value (SL) of the PV input scale).
The controller is configured to the initial value of each parameter at the factory before shipment.
First check the initial values shown in “2. Lists of Parameters,” in Parameters User’s Manual and change
parameter values as necessary.
U(DIN)
14
PV
SP 2
3
4
W
SP
AL1
2
3
15
MAN
Platinel 2
A/M
16
SET/ENT
SET/ENT
PR20-40
17
W97Re3W75Re25
18
30
Example of Temperature Input
-200°C
1370°C
JPt100
Example of Voltage Input
1V
2V
4V
5V
31
(input signal)
Instrument
input range
Instrument
input range
RTD
35
Pt100
PV input range
800°C
Set a range
to be
controlled
Maximum value of
PV input range (RH)
Parameters to be set for temperature input
1. PV input type (IN): Set according to a sensor
2. Maximum value of PV input range (RH): Set the
maximum value of the range to be controlled.
3. Minimum value of PV input range (RL): Set the
minimum value of the range to be controlled.
RL
PV input range
PV input scale
0.0m3/h
36
RH
Set a range to
be controlled
50.0m3/h
Minimum value of
Maximum value of
PV input scale (SL)
PV input scale (SH)
Parameters to be set for voltage input
1. PV input type (IN): Set according to an input signal
2. Maximum value of PV input range (RH): Set the maximum value of an input signal.
3. Minimum value of PV input range (RL): Set the minimum value of an input signal.
4. Position of PV input decimal point (SDP): Set the position of the decimal point for PV input display.
5. Maximum value of PV input scale (SH): Set the maximum value of the scale to be controlled.
6. Minimum value of PV input scale (SL): Set the minimum value of the scale to be controlled.
5.
37
Standard
signal
DC voltage
0.4 to 2 V
1 to 5 V
0 to 2 V
0 to 10 V
-10 to 20 mV
0 to 100 mV
3
4
SP
2
AL1
MAN
3
A/M
A/M
SET/ENT
Press the
“FUNC”.
SET/ENT
key once to display the menu
SP
AL1
Press the
key once to display the parameter
“RH” (maximum value of PV input range).
9.
Press the
2
MAN
3
Blinks during
change.
key once to register the setpoint.
SET/ENT
Displays
menu “FUNC”.
PV
3
PV
4
SP 2
SP 2
3
6.
Displays
parameter
“RH”.
PV
AL1
A/M
SET/ENT
SET/ENT
12.
key once to display the menu
4
Press the
MAN
3
AL1
A/M
A/M
SET/ENT
SET/ENT
key once to display the menu “I/O”.
2
10.
Displays menu
“STUP”.
PV
SP 2
3
4
MAN
3
SET/ENT
3
Displays
PV.
PV
SP 2
4
2
SP 2
MAN
3
AL1
A/M
A/M
SET/ENT
SET/ENT
key once to display the parameter
13.
Press the
SET/ENT
3
4
SP
2
MAN
3
AL1
A/M
A/M
SET/ENT
SET/ENT
2
Displays target
setpoint
MAN
3
5. Changing Alarm Type
PV
4
3
The following operating procedure describes an example of changAlarm output terminals
Factory-set defaults
ing alarm-1 (factory-set default: PV high limit alarm) to PV low Alarm-1 (terminal numbers 6 - 7 ).......PV input high limit alarm
limit alarm.
Alarm-2 (terminal numbers 5 - 7 ).......PV input low limit alarm
When you have changed alarm type, the alarm setpoint will be ini- Alarm-3 (terminal numbers 4 - 7 ).......PV input high limit alarm
tialized; set the alarm setpoint again.
For details see “List of Alarm Types” in Parameters
4
SP
AL1
SET/ENT
2
Press the
key for more than 3 seconds.
This returns you to the display shown at power-on
(figure below).
Displays
menu “I/O”.
MAN
3
Press the
or
key to display the required
setpoint. The figure below shows an example of
setting the maximum value of PV input range to
200.0°C.
SP
Press the
“PWD”.
3
SP
2
SET/ENT
2
Blinks during
change.
MAN
3
key once to register the setpoint.
User’s Manual
MAN
The PV display in the figure above shows the error code
for input burnout (
) if PV input wiring is not yet
complete. The error code disappears when you wire the
PV input terminals correctly.
1.
PV
SP 2
3
SP 2
4
3
4
SP
SP
2
MAN
3
AL1
A/M
A/M
SET/ENT
SET/ENT
2
Bring the operating display into view (appears at
power-on).
Press the
“FUNC”.
SET/ENT
key once to display the menu
14.
SP 2
3
AL1
3
Displays
parameter
“RL”.
PV
4
SP 2
MAN
3
AL1
2
4
3
4
SP 2
2.
40
41
50
51
55
56
Instrument
Measurement Accuracy
Input Range
Set the data item PV Input Type "IN" to the OFF option to leave the PV input
type undefined.
-200 to 1370⬚C
-300 to 2500⬚F
-199.9 to 999.9⬚C
0 to 2300⬚F
⫾0.1% of instrument range ⫾1 digit for temperatures
-199.9 to 500.0⬚C
equal to or higher than 0⬚C
-199.9 to 999.9⬚F
⫾0.2% of instrument range ⫾1 digit for temperatures
-199.9 to 999.9⬚C
below 0⬚C
-300 to 2300⬚F
-199.9 to 400.0⬚C
-300 to 750⬚F
0.0 to 400.0⬚C
-199.9 to 750.0⬚F
⫾0.15% of instrument range ⫾1 digit for temperatures
0 to 1800⬚C
equal to or higher than 400⬚C
32 to 3300⬚F
⫾5% of instrument range ⫾1 digit for temperatures
below 400⬚C
0 to 1700⬚C
32 to 3100⬚F
⫾0.15% of instrument range ⫾1 digit
0 to 1700⬚C
32 to 3100⬚F
⫾0.1% of instrument range ⫾1 digit
-200 to 1300⬚C
⫾0.25% of instrument range ⫾1 digit for temperatures
-300 to 2400⬚F
below 0⬚C
-199.9 to 999.9⬚C
-300 to 1800⬚F
-199.9 to 900.0⬚C
⫾0.1% of instrument range ⫾1 digit for temperatures
-300 to 1300⬚F
equal to or higher than 0⬚C
⫾0.2% of instrument range ⫾1 digit for temperatures
-199.9 to 400.0⬚C
below 0⬚C
-300 to 750⬚F
0.0 to 400.0⬚C
-199.9 to 750.0⬚F
0 to 2300⬚C
⫾0.2% of instrument range ⫾1 digit
32 to 4200⬚F
0 to 1390⬚C
⫾0.1% of instrument range ⫾1 digit
32 to 2500⬚F
⫾0.5% of instrument range ⫾1 digit for temperatures
0 to 1900⬚C
equal to or higher than 800⬚C
32 to 3400⬚F
No guarantee of accuracy for temperatures below 800⬚C
0 to 2000⬚C
⫾0.2% of instrument range ⫾1 digit
32 to 3600⬚F
-199.9 to 500.0⬚C
⫾0.1% of instrument range ⫾1 digit (Note1) (Note2)
-199.9 to 999.9⬚F
-150.0 to 150.0⬚C
⫾0.2% of instrument range ⫾1 digit (Note1)
-199.9 to 300.0⬚F
-199.9 to 850.0⬚C
-300 to 1560⬚F
⫾0.1% of instrument range ⫾1 digit (Note1) (Note2)
-199.9 to 500.0⬚C
-199.9 to 999.9⬚F
-150.0 to 150.0⬚C
⫾0.2% of instrument range ⫾1 digit (Note1)
-199.9 to 300.0⬚F
0.400 to 2.000 V
1.000 to 5.000 V
⫾0.1% of instrument range ⫾1 digit
0.000 to 2.000 V
The read-out range can be scaled between -1999 and
0.00 to 10.00 V
9999.
-10.00 to 20.00 mV
0.0 to 100.0 mV
*
Performance in the standard operationg condition (at 23⫾2⬚C, 55⫾10%RH, and 50/60Hz power frequency)
Note1: The accuracy is ⫾0.3⬚C of instrument range ⫾1 digit for a temperature range from 0⬚C to 100⬚C.
Note2: The accuracy is ⫾0.5⬚C of instrument range ⫾1 digit for a temperature range from -100⬚C to 200⬚C.
*
To receive a 4-20 mA DC signal, select a standard signal of 1 to 5 V DC and connect it to a 250⍀ resistor. This resistor is optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
6.
Press the
A/M
A/M
SET/ENT
SET/ENT
key once to display the menu “I/O”.
15.
Displays target
setpoint
MAN
3
AL1
Displays
menu “I/O”.
PV
SP 2
3
SP 2
3
SET/ENT
A/M
7.
MAN
3
SP 2
AL1
A/M
A/M
SET/ENT
SET/ENT
Press the
key once to display the parameter
“IN” (PV input type).
SET/ENT
16.
Press the
SET/ENT
Displays
parameter “IN”.
PV
SP 2
3
AL1
2
3.
Blinks during
change.
MAN
3
MAN
3
SP 2
8.
AL1
A/M
A/M
SET/ENT
SET/ENT
Press the
or
key to display the required
setpoint. The figure below is an example of the
controller set to a Pt100 resistance temperature
detector (-199.9°C to 500.0°C).
PV
SP 2
3
4
SP
AL1
2
17.
Press the
“STUP”.
A/M
SET/ENT
SET/ENT
AL1
2
3
4.
4
MAN
3
4
MAN
3
You can take the same
steps for alarm-2 type
(AL2), and alarm-3 type
(AL3) that are displayed
after this.
PV
SP 2
4
MAN
3
AL1
A/M
A/M
SET/ENT
SET/ENT
2
3
3
4
MAN
SP 2
SET/ENT
SET/ENT
2
3
key once to register the setpoint.
SP 2
5.
Displays target
setpoint
Press the
“FUNC”.
SET/ENT
4
Displays
PV.
PV
AL1
* If the type of input is voltage, also configure
the PV Input Decimal Point Position (SDP),
Maximim Value of PV Input Scale (SH) and
Minimum Value of PV Input Scale (SL) that are
displayed after parameter RL.
PV
SET/ENT
3
4
SP 2
SP
4
MAN
3
Press the
key for more than 3 seconds.
This returns you to the display shown at power-on
(figure below).
PV
SP
AL1
9.
SET/ENT
Displays
PV.
PV
Blinks during
change.
A/M
3
3
3
key once to register the setpoint.
SET/ENT
SP
2
Press the
key once to display the
parameter “PWD”.
SET/ENT
A/M
SP 2
Press the
SP
3
4
SP
2
MAN
3
AL1
A/M
A/M
SET/ENT
SET/ENT
key once to display the menu
2
3
Displays target
setpoint
MAN
10. When setting an alarm setpoint, see “4. Setting
Alarm Setpoints” in Operations User’s Manual .
Displays menu
“FUNC”.
SP 2
Press the
8.
Display menu
“STUP”.
PV
9.
2
Blinks during
change.
A/M
key once to display the menu
Press the
key for more than 3 seconds.
This returns you to the display shown at power-on
(figure below).
MAN
3
AL1
PV
4
MAN
3
SP 2
SP
2
PV
SP
2
PV
4
SET/ENT
key once to register the setpoint.
SP
AL1
3
SP
SP 2
7.
Press the
or
key to display the required
setpoint. The figure below shows an example of
setting PV low limit alarm.
Displays menu
“OP.PA”.
PV
4
SP
2
4
MAN
3
PV
4
SP
AL1
2
SET/ENT
Press the
key for more than 3 seconds to
call up the menu “OP.PA”.
Press the
or
key to display the required
setpoint. The figure below shows an example of
setting the minimum value of PV input range to
0.0°C.
3
SP
2
MAN
3
Displays
parameter
“AL1”.
PV
SET/ENT
SP
2
SET/ENT
SP
SET/ENT
SP
Press the
key several times to display the
parameter “AL1” (alarm-1 type).
Displays
PV.
PV
Press the
key once to display the parameter
“RL” (minimum value of PV input range).
Displays
menu “FUNC”.
6.
MAN
3
SP 2
5.
PV
Select the unit from the UNIT parameter.
3
SET/ENT
SP 2
4
SET/ENT
SET/ENT
MAN
3
SP 2
Displays PV.
■ Instrument Input Range Codes
The controller automatically returns to the display at the time of power-on (i.e., operating display) if no key is
operated for at least one minute.
Heating side: Time proportional PID relay output (variable)
Cooling side: Time proportional PID relay output (variable)
Not specified
P = 5.0%, I = 240 seconds, D = 60 seconds.
Alarm-1: PV high limit, Alarm-2: PV low limit, Alarm-3: PV high limit
3
SET/ENT
Type
4
MAN
Press the
or
key to display the required
setpoint. The figure below shows an example of
setting to current output (4 to 20 mA DC).
SP
A/M
A/M
AL1
Input
3
3
PV
SP 2
AL1
Press the
“STUP”.
Blinks during
change.
MAN
1
Time proportional PID
relay output (variable)
Reverse action (variable)
8.
PV
MAN
3
4
4
A/M
Unspecified
Factory-set defaults
for standard type
controllers
key once to display the parameter
A/M
SP
Used to change numerical values. On setting displays for various parameters, you can change
target setpoints, parameters, and output values (in manual operation). Pressing the
key
decreases a numerical value, while pressing the
key causes it to increase. You can hold
down a key to gradually increase the speed of change.
0°C
SP 2
SET/ENT
Used to switch between the AUTO and MAN modes. Each time you press the key, it switches to
the AUTO or MAN mode alternately.
A/M
Minimum value of
PV input range (RL)
2
AL1
6.
A/M
SET/ENT
SP
3.
4.
PV
A/M
IMPORTANT
•
11.
A/M
Interface for an adapter cable used when setting and storing parameters from a PC.
This requires an optional parameter setting tool.
and
keys
•
MAN
3
2
PV
SET/ENT
Control action
PID parameter
Alarm output
4
If any of alarms 1 to 3 occurs, the respective alarm indicator lamp (AL1 to AL3) is lit (in orange).
Light-loader interface
Control output
11.
PV
Displays the setpoint (SP) or the output value (OUT) during operation.
Displays the set value of parameters on the parameter setting display.
Alarm indicator lamps
Item
2
A/M
SET/ENT
2
SP
SP 2
9.
3
To set the type of control output, see steps 7 and later in
“4. Setting Control Output Type.” To finish settings, press
key for more than 3 seconds. This returns you
the
to the display shown at power-on (figure below).
SP
Is lit in green during manual operation. MAN: Is lit when in manual mode.
Blinks during auto-tuning
SET/ENT
key
AL1
A/M
Displays PV.
Displays a parameter symbol when you set a parameter.
Displays an error code (in red) if an error occurs.
Status indicator lamp
8.
SP 2
MAN
3
PV
4.
A/M key
If the type of input is
voltage, also configure
the PV Input Decimal
Point Position (SDP),
Maximim Value of PV
Input Scale (SH) and
Minimum Value of PV
Input Scale (SL) that
follow this step.
PV
SP
keys
3.
7.
key once to register the setpoint.
4
AL1
SP
AL1
SET/ENT
When the SP number currently used for operation is 2, 3 or 4, the respective SP No. indicator lamp lighits.
When the SP number is 1, the lamp does not lighit.
6.
Press the
A/M
Function
Setpoint display
3
PV
9.
Process variable (PV)
display
3
10.
SET/ENT
MAN
3
SP 2
Displays
menu “OP.PA”.
PV
SP
5. Alarm indicator
lamps
Target setpoint (SP)
number indicator lamps
5.
Press the
key once to display the parameter
“UNIT” (PV Input Unit).
Displays
parameter
PV
“UNIT”.
SET/ENT
1. Process
variable (PV)
display
4. Status
indicator lamp
8. SET/ENT key
Name of Part
AL1
SP
1. Process
variable (PV) 2. Setpoint
display
display
2. Setpoint
display
3. Target setpoint
(SP) number
4. Status
indicator lamps
indicator
6. Light-loader
lamp
interface
9. and keys
7. A/M key
3. Target setpoint
(SP) number
indicator lamps
5. Alarm
indicator
lamps
SP 2
Displays target
setpoint
SET/ENT
SP 2
1. Names and Functions of Front Panel Parts
Displays
parameter
“UNIT”.
PV
4
MAN
3
Blinks during
change.
MAN
3
2
A/M
4
SP
AL1
SET/ENT
SP
AL1
2.
PV
SP 2
SP 2
4
Displays
parameter
“OT”.
SP
2
SET/ENT
SP
Press the
or
key to display the required
setpoint. The figure below shows an example of
setting the minimum value of PV input range to
0.0⬚C.
PV
Press the
“PWD”.
Press the
key once to display the parameter
“UNIT” (PV input unit).
Displays
PV.
PV
SP 2
Press the
setpoint.
10.
3
PV
MAN
3
Contents
3.
SP 2
AL1
4.
Bring the operating display into view (display
appears at power on).
SET/ENT
SP
AL1
1.
Press the
key several times to display the
parameter “OT” (control output type).
Displays menu
“STUP”.
PV
The following operating procedure describes an example of changing PV input terminal
the K-type thermocouple (-199.9°C to 500.0°C) to a Pt100 resistance Thermocouple/mV/V input.............................. 12 - 13
temerature detector (-199.9°C to 500.0°C) and setting the measure- RTD input .................................................. 11 - 12 - 13
ment range of 0.0°C to 200.0°C.
SP
MAN
3
Displays
parameter
“RL”.
PV
Blinks during
change.
SET/ENT
SP 2
8.
7.
key once to display the menu
The controller may automatically initialize the registered operating parameter setpoints if any change is made to the
data item PV Input Type (IN), Maximum Value of PV Input Range (RH), Minimum Value of PV Input Range (RL),
PV Input Decimal Point Position (SDP), Maximum Value of PV Input Scale (SH) or Minimum Value of PV Input
Scale (SL). After a change has been made to any of these data items, be sure to verify the registered operating
parameter setpoints to ensure that they are correct. If any data item has been changed to its default, set it to a
required value.
3. Changing PV Input Type
2.
Press the
“STUP”.
3
4
SP
AL1
2
3
MAN
A/M
SET/ENT
SP
AL1
2
MAN
3
6. Description of Multiple Setpoints and PID
A/M
SET/ENT
4. Setting Control Output Type
The following operating procedure describes an exControl output terminal Values in parentheses are setpoints
ample of changing time proportional PID relay outTime proportional PID relay (0)/on-off(3) output...........................
put (0: factory-set default) to current output (2).
1 - 2 Current (2)/time proportional PID voltage pulse (1) output...................... 16 - 17
For details on the heating/cooling control output terminals, see
“6. Terminal Wiring Diagrams” in Installation User’s Manual .
1.
Bring the operating display into view (display
appears at power on).
Displays
PV.
PV
SP 2
3
2.
PV
SP 2
4
A/M
SET/ENT
3
SP
2
3
MAN
Displays target
setpoint
Target
setpoint
(SP)
SP.NO=1
1.SP
1.P
1.I
1.D
1.Pc
1.Ic
1.Dc
SP.NO=2
2.SP
2.P
2.I
2.D
2.Pc
2.Ic
2.Dc
SP.NO=3
3.SP
3.P
3.I
3.D
3.Pc
3.Ic
3.Dc
SP.NO=4
4.SP
4.P
4.I
4.D
4.Pc
4.Ic
4.Dc
Press the
key for more than 3 seconds to call
up the menu “OP.PA”.
Displays
menu “OP.PA”.
AL1
2
3
MAN
4
PID parameter
Target setpoint
number
(SP.NO)
SET/ENT
SP
AL1
3
The UT350/UT320 controllers have a maximum of four target setpoint (SP) parameters and has PID for each of these
setpoints. The following shows the correspondence between the target setpoint numbers (SP.NO), target setpoints (SP), and
PID parameters.
For example, if you have set “2” to the target setpoint number (SP.NO), the control parameters available are target setpoint
(2.SP), proportional band (heating-side proportional band) (2.P), integral time (heating-side integral time) (2.I), derivative
time (heating-side derivative time) (2.D), cooling-side proportional band (2.Pc), cooling-side integral time (2.Ic), and cooling-side derivative time (2.Dc).
To use multiple target setpoints, see the table below to check the corresponding parameters.
Proportional
Integral time Derivative time Cooling-side
band
proportional
(heating-side (heating-side
(heating-side
band
integral time) derivative time)
proportional band)
Cooling-side Cooling-side
integral time derivative time
A/M
SET/ENT
IM 05D01D02-02E (1)
3.
User’s
Manual
Models UT350 / UT320
Digital Indicating Controllers
User’s Manual
Operations
IM 05D01D02-02E
Press the
key several times to display the
parameter “PID”.
Displays
parameter
PV
“PID”.
SET/ENT
SP 2
3
7.
Press the
setpoint.
or
key to display the required
NOTE
SP 2
4.
Press the
3
MAN
3
Take note of the parameter settings when asking the vendor for repair.
4
If AUTO and MAN have been switched using contact input, when the contact input is ON, switching between
AUTO and MAN cannot be achieved by keystroke.
SP
2
AL1
A/M
A/M
SET/ENT
SET/ENT
key once to display “1Gr.”
8.
Press the
2
MAN
3
Blinks during
change.
key once to register the setpoint.
SET/ENT
1.
SP 2
AL1
SET/ENT
5.
Press the
SET/ENT
Contents
2
3
4
SP 2
SP 2
SET/ENT
SET/ENT
The same steps can be used for integral time (1.I) and
derivative time (1.D) that are displayed after this.
key once to register the setpoints.
AL1
3
2
MAN
3
A/M
Press the
key once to display the parameter
“1.P” (proportional band for 1.SP).
SET/ENT
PV
1. Setting Target Setpoint (SP)
3
4
9.
Press the
key for more than 3 seconds.
This returns you to the display shown at power-on
(figure below).
2
Displays
parameter
“1.P”.
SP 2
AL1
A/M
A/M
SET/ENT
SET/ENT
4.
Press the
setpoint.
or
Displays PV.
PV
3
A/M
SP 2
3
2.
4
SP
AL1
AL1
2
-
6
5
4
7
7
7
Factory-set defaults
)............PV high limit alarm
)............PV low limit alarm
)............PV high limit alarm
3
2
MAN
3
AL1
2
SET/ENT
SP 2
3
AL1
Blinks during
change.
5.
Press the
SET/ENT
key once to register the setpoint.
1.
2.
Bring manual operating display into view. For
switching to manual operation, see “7. Switching
between AUTO and MAN ”.
Displays
output-value
symbol “o”.
or
SP 2
AL1
2
3
Press the
or
key to change a control output
value. You don’t need to press the
key.
Faulty RAM
(E001)
Faulty ROM
(E002)
System data error 0%
PV decimal point blinks.
Faulty calibration
value
Parameter error
None
0% or less
0% or less
or OFF
Stopped
OFF
0%
Normal action Normal action Normal action Normal action
Normal
(out of
(out of
(out of
(out of
action
accuracy)
accuracy)
accuracy)
accuracy)
0%
Preset value
OFF
output
Faulty
Contact us
for repair.
Check and set
the parameters,
as they have
been set to the
limited values.
0%
4
4
SP 2
3
4
SP 2
3
MAN lamp
ON.
4
SP
AL1
MAN lamp
ON.
2
3
MAN
A/M
SET/ENT
■ Heating-side OUT display
AL1
2
MAN
3
key to display the required
A/M
A/M
SET/ENT
SET/ENT
SP 2
AL1
2
3
3
PV
Heating-side
output
%
4
MAN
Control
output
Alarm
output
Retransmis- Commusion output nication
Displays “RJC”
and PV
alternately
Measured
with RJC=OFF
Normal
action
Normal
action
Normal
action
Normal
action
Faulty
Contact us for repair.
Normal action
Normal
action
Normal
action
Normal
action
Normal
action
Faulty
Contact us for repair.
105%
Preset
value
output
Normal
action
Normal
action
Normal
action
Dependent on the BSL
parameter Up-scale: 105%
Down-scale: -5%
Preset
value
output
Normal
action
Normal
action
Normal
action
Check wires and
sensor.
Normal
action
Normal
action
Normal
action
Normal
action
Check process.
Normal
action
Normal
action
Normal
action
Normal
action
Check process. Press
any key to erase error
indication.
Normal
action
Normal
action
Normal
action
Normal
action
Check wires and
communication parameters,
and make resetting.
Recovery at normal receipt
RJC error
PV value blinks. EEPROM
error
(E300)
A/DC error
SP 2
Symbol “C”
represents the
cooling-side
output.
A/M
SET/ENT
3
Cooling-side
output
%
4
SP
AL1
2
3
MAN
(OVER) or Excessive PV -5% or 105%
(-OVER) Out of -5 to
105%
(E200) Auto-tuning Normal action
failure
(Time-out)
SP decimal
point blinks.
(on setpoint
display unit)
■ Cooling-side OUT display
SP
PV
(B.OUT) PV burnout
error
PV
■ Manipulating the Control Output during Heating/Cooling Control
Symbol “H”
represents the
heating-side
output.
Error indication Description
(on PV display of error
unit)
SET/ENT
MAN
3
PV
MAN
3
Remedy
The following shows possible errors occurring during operations.
key. Note that the control output changes
Displays
output value.
%
SP
PV
SP
2
Retransmission Communioutput
cation
■ Possible Errors during Operation
MAN
3
A/M
Displays menu
“OP.PA”.
PV
Alarm
output
MAN lamp
ON.
A/M
SET/ENT
4
SET/ENT
SET/ENT
(E000)
(E400)
Control output cannot be changed if the controller is stopped. In this case, the preset output value (setup parameter
PO) will be output.
SET/ENT
SP 2
Displays
target setpoint.
MAN
3
Control
output
MAN
3
NOTE
Displays
target setpoint.
MAN
3
key to display the required
SP
or
SP
8. Manipulating the Control Output in Manual Operation
PV
Press the
key for more than 3 seconds to call
up the menu “OP.PA”.
A/M
SET/ENT
Press the
setpoint.
4
Either of the following two displays appears when the mode is switched to MAN during heating/cooling control.
Displays
target setpoint.
MAN
3
MAN lamp
OFF.
A/M
3
SP
2
A/M
PV
2
MAN
3
SP 2
4
Displays PV.
AL1
2.
2
4
key once to register the setpoint.
4
SP
2
A/M
SET/ENT
3
Displays
output-value
symbol “o”.
SP
AL1
Displays
output value.
%
PV
SET/ENT
Bring the operating display into view (display
appears at power on).
AL1
SP 2
4
A control output value is linked with a display value changed using the
as displayed without requiring the
key.
SP
PV
3
PV
SP 2
SET/ENT
3
The following operating procedure describes an example of setting Alarm output terminals
160.0 to alarm-1 setpoint. Check alarm type before setting the alarm Alarm-1 (terminal numbers
setpoint. To change the type of alarm, see “5. Changing Alarm Type” Alarm-2 (terminal numbers
Alarm-3 (terminal numbers
in Initial Setting User’s Manual .
When the target setpoint is set through communication, the target setpoint cannot be changed by keystroke.
Press the
SP 2
Displays PV.
PV
MAN
3
PV
SET/ENT
4. Setting Alarm Setpoints
1.
NOTE
3.
Displays
target setpoint.
PV
SP
AL1
The following operating procedure describes an example of setting 120.0 to a target setpoint. In automatic operation, the
controller starts control using set target setpoints.
Displays
target setpoint.
MAN
3
Each time you press the A/M key on the front panel of the instrument, AUTO and MAN is switched alternately.
In automatic operation
In manual operation
SET/ENT
SP 2
Bring the operating display into view (display
appears at power on).
2.
[TIP]
The PID parameter numbers set in step 4. should be
set as follows:
In case of PID for 1.SP, PID = 1Gr
In case of PID for 2.SP, PID = 2Gr
In case of PID for 3.SP, PID = 3Gr
In case of PID for 4.SP, PID = 4Gr
4
SET/ENT
Do not use the instrument generating strong magnetic field such as radio equipment and the like near the controller.
This may cause the fluctuation of the PV value.
2
MAN
3
SET/ENT
SP
1.
2
A/M
A/M
SP
NOTE
4
4
AL1
A/M
SP 2
6.
3
SP
AL1
PV
1. Setting Target Setpoint (SP)
2. Performing/Canceling Auto-tuning
3. Setting PID Manually
4. Setting Alarm Setpoints
5. Selecting Target Setpoint Numbers (SP.NO)
6. Switching between Run and Stop
7. Switching between AUTO and MAN
8. Manipulating the Control Output in Manual Operation
9. Troubleshooting
3
SP
MAN
3
Description
of error
PV
Blinks during
change.
SP
Error indication
(on PV display unit)
Displays PV.
PV
PV
■ Errors at Power On
The following table shows errors that may be detected by the fault diagnosis function when the power is turned on.
Bring the operating display into view (display appears at power on).
2nd Edition: Jul 1, 2001
This manual describes key entries for operating the controller. For operations using external contact inputs, see “6. Terminal
Wiring Diagrams” in Installation User’s Manual . If you cannot remember how to carry out an operation during
setting, press the
key for more than 3 seconds. This brings you to the display (operating display) that appears at
power-on.
IMPORTANT
PV
4
SP
AL1
7. Switching between AUTO and MAN
Faulty
communication line
Normal action
Remedy
All indications off Runaway (due None
to defective
power or
noise)
0% or less OFF
or OFF
0% or
less
Stopped
Faulty if power off/on does
not reset start the unit.
Contact us for repair.
All indications off Power off
0%
0%
Stopped
Check for abnormal power.
None
OFF
A/M
SET/ENT
PV
SP 2
3
Also configure the Alarm-2 Setpoint (A2) and Alarm3 Setpoint (A3) parameters that follow this step.
4
SP
AL1
2
MAN
3
3.
Blinks during
change.
A/M
SET/ENT
Press the
“A1”.
SET/ENT
key twice to display the parameter
PV
2. Performing/Canceling Auto-tuning
SP 2
4
NOTE
SET/ENT
Bring the operating display into view (display
appears at power on).
Displays PV.
4.
Press the
or
key to display the required
setpoint. Tuning for 1.SP is AT = 1.
PV
PV
SP 2
3
4
AL1
2
MAN
3
SP 2
Displays
target setpoint.
SP
AL1
SP 2
3
4
SP
AL1
MAN
3
AL1
A/M
A/M
SET/ENT
SET/ENT
2
4
Displays
target setpoint.
MAN
3
The following is an example when the DB parameter is set at 12.4%.
If you hold down the
key with the heating-side output under manipulation (i.e., cooling-side output C = 0.0%), the
heating-side output (H =) decreases. Consequently, both the heating-side and cooling-side outputs change to 0.0%. If you
keep the
key held down longer, you enter the state of manipulating the cooling-side output, and its value begins to
increase.
key with the cooling-side output under manipulation (i.e., heating-side output H =
Inversely, if you hold down the
0.0%), the cooling-side output (C =) decreases. Consequently, both the heating-side and cooling-side outputs go to 0.0%. If
you keep the
key held down longer, you enter the state of manipulating the heating-side output, and its value begins to
increase.
2
NOTE
A/M
A/M
SET/ENT
SET/ENT
Press the
key for more than 3 seconds to call
up the menu “OP.PA”.
SET/ENT
-12.4
Blinks during
change.
Bring the operating display into view (display appears
at power on).
Displays PV.
4.
Press the
setpoint.
or
SP 2
3
SP 2
4
Displays
target setpoint.
AL1
Displays menu
“OP.PA”.
3
2.
Press the
key for more than 3 seconds to call
up the menu “OP.PA”.
SET/ENT
5.
Press the
SET/ENT
4
SP 2
3
MAN
3
AL1
A/M
A/M
SET/ENT
SET/ENT
Press the
key five times to display the
parameter “AT”.
Displays
parameter
PV
“AT”.
SP 2
3
6.
2
SP 2
3
key once to register the setpoint.
PV
SP 2
4
MAN
3
AL1
A/M
A/M
SET/ENT
SET/ENT
3.
4
SP 2
MAN
3
AL1
SET/ENT
SET/ENT
3
4
2
MAN
3
2
MAN
3
Is the instrument
defective?
Yes
Bring the operating display into view (display
appears at power on).
Displays PV.
MAN
3
4
SP
2
3
MAN
AL1
2
3
A/M
A/M
SET/ENT
SET/ENT
Yes
Yes
Check wiring on the
power supply
terminals.
Check the key lock
setting.
No
Is display
faulty?
Yes
Turn off power, and
then turn it on again.
No
Is I/O
signal faulty?
Is
communication
link faulty?
No
Yes
Check the
instrument’s I/O
specifications.
Yes
Check the
instrument's suffix
code.
MAN
Switching between the RUN and STOP states can be performed only using external contact input.
2.
Check the specifications
of I/O counterpart for
wrong polarity.
No
Normal?
No
When the controller is shipped from the factory, it is configured so that switching between the RUN and STOP
states cannot be performed. To make the switching possible, configure the DIS setup parameter as “DIS = 4”.
Press the
key for more than 3 seconds to call
up the menu “OP.PA”.
Displays menu
“OP.PA”.
PV
SP 2
4
Displays
target setpoint.
Is key
operation
faulty?
Check the supply
voltage.
3
18
PV
SP 2
4
AL1
AL1
2
3
MAN
A/M
A/M
SET/ENT
3
4
20
Start of operation
when OFF
SP
SP
3
SP 2
No
Totally
inoperable?
• The UT350/UT320 controllers have a universal output.
The type of control output can be set/changed using the parameter “OT”.
At this point, the controller must be wired correctly according to the selected type of control output. Check the wiring
first if the controller provides no control output. To do this, refer to “6. Terminal Wiring Diagrams,” in Installation
User’s Manual .
With the parameters “OH” and “OL”, it is possible to set/change the high and low limits of control output. The control
output may not change at all, however, because of restrictions on these parameters. Also check the restrictions on these
parameters.
• The control output can only be changed when the controller is in the MAN mode.
If the MAN lamp is off (i.e., the controller is in the AUTO mode), you cannot change the control output using key
operation.
Correct
errors.
Is
key lock
enabled?
Yes
No communication
capability.
No
Does the code
include a communication
option?
Check the
communication-related
parameters.
● The control output does not change soon after the target setpoint SP has been
changed.
• If this happens, check the setpoint of the parameter “C.MD”. In cases where fixed-point control is selected as the PID
control mode (C.MD = 1), tracking based on the I-term works to prevent the control output from changing suddenly
even if the target setpoint SP is varied.
The control output therefore may appear to be working incorrectly at first; however it gradually adapts itself to the new
target setpoint.
Check
communication wiring.
SET/ENT
SP
2
4
Press the
key for more than 3 seconds. This
returns you to the display shown at power-on
(figure below).
SP2 lamp
PV
ON.
NOTE
3. Setting PID Manually
3
3
Displays
parameter
“SP.NO”.
6.
SET/ENT
6. Switching between Run and Stop
If you know the values to be set or if suitable PID constants cannot be obtained by auto-tuning, follow the procedure below
to set values.
SP 2
SP 2
MAN lamp
blinks.
Auto-tuning is complete when the MAN lamp goes off.
PV
PV
AL1
SP
2
Press the
key several times to display the
parameter “SP.NO”
SET/ENT
SP
A/M
A/M
4
● The controller does not provide any control output or the control output does not
change at all.
PV
A/M
SET/ENT
3
SP
2
■ Troubleshooting Flow
4
During auto-tuning, the panel indications become
as shown below.
SP
AL1
9. Troubleshooting
MAN
3
• The alarm function of the controller continues to work normally. (Alarms with the stand-by feature temporarily return
to their stand-by state, however.)
• Setting parameters that have already been configured retain their settings.
• Auto-tuning is cancelled.
• After recovery from a power failure, control action resumes in the same mode as the one before the occurrence of the
power failure. The control output begins with the preset output value.
• The UT350/UT320 controllers have a universal input.
The type of PV input can be set/changed using the parameter “IN”. At this point, the controller must be wired correctly
according to the selected type of PV input. Check the wiring first if the controller fails to show the correct PV. To do
this, refer to Initial Settings User’s Manual .
With the parameters “RH”, “RL”, “SDP”, “SH” and “SL”, it is possible to scale the input signal and change its number
of decimal places. Also check that these parameters are configured correctly.
Change in manipulated output when the dead band is positive
SP
2
● Power failures of 20 ms or longer
● The controller does not show the correct measured input (PV).
If the operating display does not appear after turning on the controller’s power, follow the measures in the procedure below.
If a problem appears complicated, contact our sales representative.
Displays menu
“OP.PA”.
PV
AL1
SET/ENT
AL1
Blinks during
change.
PV
SP
AL1
4
MAN
3
A/M
SP
SP 2
2
To cancel auto-tuning, set AT = OFF.
SET/ENT
The controller is not affected at all and continues normal operation.
12.4
Heating-side
manipulated output
SET/ENT
SET/ENT
PV
3
SP
MAN
3
SET/ENT
5.
● Momentary power failures shorter than 20 ms
If your control tasks are not successful, check the preset parameters and controller wiring before concluding the controller to
be defective. The following show some examples of troubleshooting you should refer to in order to avoid the possibility of
other problems.
DB=12.4
PV
PV
2
0
Cooling-side
manipulated output
key to display the required
SP
Press the
key once to register the setpoint.
(This starts auto-tuning.)
If the
key is pressed when AT = OFF, autotuning will be cancelled. In this case, PID contains
the value existing before auto-tuning.
Dead band:
Operating parameter DB
If a target setpoint number has been switched using contact input, when the contact input is on, that number cannot
be selected by keystroke.
When using target setpoint ramp setting function, PV tracking works if the target setpoint number is switched.
1.
■ If a Power Failure Occurs during Operation
■ Troubleshooting When the Controller Fails to Operate Correctly
MAN
3
Output (%)
The following operating procedure describes an example of changing a target setpoint number (SP.NO) from 1 to 2.
AL1
MAN lamp
OFF.
1.
3
SP
2
A/M
3.
Displays PV.
PV
● Controller behavior and control output manipulation when the dead band is positive
5. Selecting Target Setpoint Numbers (SP.NO)
When on-off control is being used, auto-tuning cannot be carried out. Moreover, do not perform auto-tuning when
contolling any of following processes.
• Control processes with quick response such as flow control or pressure control
• Processes where even temporary output on/off results in inconvenience
• Processes where a large output change at control element results in inconvenience
• Processes where variations in PV may exceed an allowable range, adversely affecting product quality
2.
Displays
parameter
“A1”.
Press the
key for more than 3 seconds.
This returns you to the display shown at power-on
(figure below).
SP
Auto-tuning should be carried out after setting a target setpoint (SP). Make sure the controller is in automatic operation
mode (AUTO) and in running state (RUN) before carrying out auto-tuning. See “7. Switching between AUTO and MAN.” to
change to AUTO and “6. Switching between RUN and STOP,” to change to RUN.
1.
3
6.
2
3
When the controller is stopped, input and outputs are
as follows:
PV input
Control output Preset output value (factory-set default: 0%)
MAN
18
SET/ENT
20
Stop of operation
when ON
No
Yes
Yes
Alarm output ON in the event of an alarm
When the controller is stopped, control output relay is
“STOP.”
Check the specifications
of communication
counterpart.
Correct?
Displays PV.
Ask the vendor for repair.
Find the cause.
Disable
key lock.
IM 05D01D02-02E (2)
User’s
Manual
■ List of Alarm Types
Models UT350 / UT320
Digital Indicating Controllers
User’s Manual
Parameters
IM 05D01D02-03E
The table below shows the alarm types and alarm actions.
In the table, codes 1 to 10 are not provided with stand-by actions, while codes 11 to 20 are provided with stand-by actions.
Determine PV input type first.
Settings herein are described in “2. Setting PV Input Type
(Setting First at Power-on)”, in Initial Settings User’s Manual .
Power on
PV
PV
SP 2
2nd Edition: Jul 1, 2001
3
4
SP 2
SP
AL1
3
4
Blinks during
change.
PV
SP 2
SP
2
MAN
3
AL1
3
C
4
Alarm type
3
MAN
AL1
2
Contact
“Open/close” shows status of relay contact, closes
if alarm
and “lit” and “unlit” shows status of lamp
occurs
No alarm
SP
2
Alarm type code
Alarm action
After PV input type (IN), input/output
parameters such as PV input unit (UNIT),
maximum value of PV input range (RH),
and minimum value of PV input range
(RL) will be displayed.
Display example
Display example
Yes
Display?
IN = OFF
OFF
A/M
A/M
SET/ENT
SET/ENT
PV high limit
1.
This manual contains a parameter map as a guideline for setting parameters, and lists of parameters for recording User
Settings.
Use the
or
key to set a numerical value.
See Instrument Input Range Codes in
Initial Settings User’s Manual .
2.
Press the
the value.
SET/ENT
Open (unlit)
A
key to register
Closed (lit)
PV
Hysteresis
PV low limit
Closed (lit)
?
key.
If you become unsure of key operation during parameter
setting, hold down the
key for more than 3 seconds.
This returns you to the display at power-on
(i.e., operating display).
4
PV
SP 2
SP
AL1
4
3
4
SP
2
3
MAN
AL1
2
3
MAN
Output
value
%
2
Deviation low
limit
MAN
3
A/M
key to register it.
key on an operating display (for more than 3 seconds) brings you to the
Closed (lit)
2
3
3
SET/ENT
key
A/M
SET/ENT
A/M
A/M
SET/ENT
SET/ENT
De-energized on
Closed
deviation high
(unlit)
limit alarm
Cooling-side output display
SET/ENT
SP display
OUT display
key
Cooling-side
output-value
symbol “C”
SP display
SP 2
3
4
SP
2
key on the setup parameter setting display (for more than 3 seconds)
SET/ENT
Cooling-side OUT display
C
B
Press this key for
more than 3 seconds
to move to the
operating
display.
Menu
Operating Parameter Setting Display
or
A
Menu
LL communication
interface selection
Alarm-1 setpoint
SET/ENT
Controll function
related
key
Pressing the
key when
PID = 1Gr causes PID
for 1.SP to appear.
SET/ENT
PV input bias
Derivative time / heatingside derivative time
Manual reset
Setpoint ramp-down rate
Cooling-side
proportional band
Output high limit/heatingside output high limit
Cooling-side integral time
Output low limit/coolingside output high limit
Cooling-side
derivative time
Direct/reverse
action switching
Description of Operating Parameter Menu Display
Displays the
operating
parameter
menu symbol
“OP.PA”.
Not displayed for
ON/OFF control
SP 2
3
Treated
as normal
AL1
2
Zone PID reference
point-1
Displayed when
parameter ZON=ON
A/M
Alarm-1 type
Input
Unspecified
J
Alarm- 2 hysteresis
Minimum value of PV input
scale (displayed at voltage input)
T
Alarm- 3 hysteresis
Presence/absence of PV input
reference junction compensation
Alarm-1 delay timer
Selection of PV input
burnout action
Alarm- 2 delay timer
Control output type
Alarm- 3 delay timer
Retransmission
output type
Description of Setup Parameter Menu Display
Displays a menu such as
“FUNC” or “I/O”.
PV
Description of Operating Parameter Setting Display
Preset output / heating-side
preset output
Cooling-side preset output
PV
3
4
PID control mode
SP
AL1
2
3
Maximum value of
retransmission output scale
Displayed
for heating
/cooling
control
SP 2
DI function selection
Displayed
for heating
/cooling
control
AL1
2
SELECT display-2
registration
Heater burnout
current measurement 2
Anti-reset windup
SELECT display-4
registration
Nothing appears.
A/M
ON/OFF rate
detection band
Ramp-rate time unit
Key lock
Protocol selection
Password setting
Baud rate
W
Platinel 2
PR20-40
W97Re3W75Re25
SET/ENT
Description of Setup Parameter Setting Display
Displays a parameter
symbol.
SET/ENT
JPt100
RTD
PV
Pt100
3
4
SP
AL1
2
3
MAN
Displays a setpoint.
A/M
The setpoints of the ORB, ORH and ORL parameters are only
effective when a sensor grounding alarm is used.
The OR parameter represents the moving average (for 5 cycle times)
of the control output and is not a setpoint.
U(DIN)
MAN
3
SP 2
SET/ENT
4
SP
SELECT display-1
registration
MAN
Displays a
setpoint.
3
B
S
R
N
Thermocouple
E
L(DIN)
Minimum value of
retransmission output scale
Zone PID selection
A/M
Type
K
Cooling-side control
output cycle time
Note 1: The fault diagnosis output turns on in case of
input burnout, A/D converter failure, or reference junction compensation (RJC) failure. The
control output in case of input burnout or A/D
converter failure is set to the value of the PO
(Preset Output Value) setup parameter. In case
of RJC failure, the controller continues control
under the condition of “RJC = OFF”.
Note 2: The FAIL output is on during normal operation
and turns off in case of failure.
■ Instrument Input Range Codes
Maximum value of PV input
scale (displayed at voltage input)
Control output cycle
time / heating-side control
output cycle time
Output value
Time
Minimum value of PV
input range
Not displayed
when OT
parameter
set to 4 to 6.
SELECT display-3
registration
ON/OFF rate low limit
Low limit of
alarm setpoint
PV input decimal point position
(displayed at voltage input)
Alarm-1 hysteresis
SP 2
Heater burnout
current measurement 1
PV input unit
Nothing appears.
SET/ENT
Displays a
parameter
symbol.
Heater burnout
current setpoint 2
Abnormal
The alarm
output turns on.
31
Open (unlit)
Alarm setpoint
PV input type
(PV INPUT terminals)
Maximum value of PV
input range
MAN
3
Displayed for
heating/cooling
control
Dead band
Output low
limit
SP
Normal
Alarm setpoint
Hysteresis
Closed (lit)
29
It is effective in the following cases where;
- the power is turned on
- the target setpoint is changed
- the target setpoint number is switched
(however, except for remote setpoint)
30
Open (unlit)
key
Target setpoint
limiter lower limit
Alarm-3 type
SP
Hysteresis
Closed (lit)
Output high
limit
Output value
Power-on
SET/ENT
4
Displayed for
heating/cooling
control
Heater burnout
current setpoint 1
ON/OFF rate high limit
⬚C
key
key
Alarm-2 type
PV
Displayed when
integral time is OFF
Setpoint ramp-up rate
Displayed for
ON/OFF control
SET/ENT
SET/ENT
Proportional band / heatingside proportional band
Integral time / heatingside integral time
ON/OFF control hysteresis/
heating-side/cooling-side
ON/OFF control hysteresis
SET/ENT
SET/ENT
PV input filter
28
25
The alarm output does not
turn on in this region even
if the PV value is below the
low limit of the alarm setpoint.
Target setpoint
limiter upper limit
Pressing the
Pressing the
Pressing the
key when
key when
key when
PID = 2Gr causes PID PID = 3Gr causes PID PID = 4Gr causes PID
for 2.SP to appear.
for 3.SP to appear.
for 4.SP to appear.
SET/ENT
FL is displayed if you
press the
key
when PID = MENU.
PID parameter
display number
or
B
Heater burnout alarms 1 and 2
Heater burnout
alarm 2
Open (unlit)
Stand-by Action
20
PV
24
Alarm setpoint
Hysteresis
Closed (lit)
Alarm setpoint
When shipped from the
factory, this parameter
appears first after
power-on.
22
Open (unlit)
Input/output
related
Alarm-2 setpoint
Alarm setpoint
Heater burnout
alarm 1
23
Hysteresis
Closed (lit)
Password input
SUPER function
21
key
(No password is required
when PWD = 0.)
10
Closed
(unlit)
Open (lit)
15
key
SET/ENT
Target setpoint
number selection
SP low
limit
19
Alarm setpoint
Hysteresis
De-energized
on PV low limit
The controller stops when in a FAIL state.
The control output is set to “OFF” or “0%”
and alarm output is set to “OFF”.
SP
Setup Parameter Setting Display
key
Auto-tuning
key
SET/ENT
Menu
Alarm-3 setpoint
Changing the registered value of a setup parameter
may cause the registered value of an operating parameter to be initialized automatically. Thus, when
you have changed a setup parameter, always check
that the registered value of the operating parameter
is appropriate. If it is initialized to default, reset it to
the required value.
key
Press this key for
more than 3 seconds
to move to the
operating
display.
key
SP high
limit
Open (lit)
5
Deviation
setpoint
PV
NOTE
Press this key for more
than 3 seconds to
move to the operating
parameter setting
display.
Closed
(unlit)
PV
Open (lit)
Sensor grounding
Sensor grounding alarm
alarm
display.
18
9
De-energized
on PV high limit
14
Fault diagnosis
Fault diagnosis output
output (Note 1)
FAIL output
(Note 2)
8
4
MAN
3
PV
Deviation setpoint
Target SP
Cooling-side
output
%
PV
AL1
SET/ENT
13
Hysteresis
4
MAN
key on the operating parameter setting display (for more than 3 seconds)
Not displayed when
OT parameter set to 4 to 6.
Displayed in automatic
operation
Hysteresis Closed Hysteresis
(lit)
Open
(unlit)
Hysteresis
Open (unlit)
Deviation setpoint
Heating-side OUT display
SP 2
AL1
You cannot return to the operating parameter setting display from the setup parameter setting
SET/ENT
17
Open
(unlit)
SP
returns you to the operating display.
SET/ENT
PV
7
Target SP
PV
A/M
5. Pressing the
Closed
(lit)
Deviation setpoint
Target SP
PV
returns you to the operating display.
SET/ENT
Hysteresis
Open
(unlit)
Hysteresis
SET/ENT
operating parameter setting display.
SET/ENT
3
Output-value
symbol “o“
Target
Setpoint
PV
SP 2
4. Pressing the
key
3
Deviation setpoint
SET/ENT
2. A numerical value is changed by
SET/ENT
SP 2
SP
Deviation within
high and low
limits
Closed (lit)
Open (unlit)
PV
Target SP
Heating-side
output
%
PV
AL1
SET/ENT
3. Pressing the
Deviation high
limit
Heating-side output display
Heating-side
output-value
symbol “H”
key to change a displayed value (decimal point blinking) and
3
Operating Display for Heating/Cooling Control
Basic Key Operation Sequence
(2) Pressing the
12
PV
Hysteresis
1. Basic Key Operation Sequence and Parameter Map
SET/ENT
Deviation high
and low limits
Open (unlit)
Closed
(lit)
Target SP
Operating Display
or
16
PV
Target SP
2
1. Basic Key Operation Sequence and Parameter Map
2. Lists of Parameters
(1) Using the
6
Closed
(unlit)
Deviation
setpoint
11
Alarm setpoint
Alarm setpoint
SET/ENT
Open (lit)
Hysteresis
Contents
1. Setting display can be switched (moved) using the
Contact
opens
if alarm
occurs
Hysteresis
De-energized
on deviation low
limit alarm
1
A/M
SET/ENT
Alarm type
Contact
“Open/close” shows status of relay contact, closes
if alarm
and “lit” and “unlit” shows status of lamp
occurs
MAN
3
Hysteresis
No
Alarm type code
Alarm action
Contact
opens
if alarm
occurs
SET/ENT
Standard
signal
DC voltage
0.4 to 2 V
1 to 5 V
0 to 2 V
0 to 10 V
-10 to 20 mV
0 to 100 mV
Instrument Input Instrument
Range Code
Input Range
Set the data item PV Input Type
OFF
“IN” to the OFF option to leave
the PV input type undefined.
-200 to 1370°C
1
-199.9 to 999.9°C
2
3
-199.9 to 500.0°C
-199.9 to 999.9°C
4
-199.9 to 400.0°C
5
0.0 to 400.0°C
6
0 to 1800°C
7
0 to 1700°C
8
0 to 1700°C
9
-200 to 1300°C
10
-199.9 to 999.9°C
11
-199.9 to 900.0°C
12
-199.9 to 400.0°C
13
0.0 to 400.0°C
14
0 to 2300°C
15
0 to 1390°C
16
0 to 1900°C
17
18
30
31
35
36
37
40
41
50
51
55
56
0 to 2000°C
-199.9 to 500.0°C
-150.0 to 150.0°C
-199.9 to 640.0°C
-199.9 to 500.0°C
-150.0 to 150.0°C
0.400 to 2.000V
1.000 to 5.000V
0.000 to 2.000V
0.00 to 10.00V
-10.00 to 20.00mV
0.0 to 100.0mV
key
Parity
ON/OFF rate
Stop bit
Target setpoint-1
Data length
Target setpoint-2
Address
Displayed only for
controllers with
communication
functions
Target setpoint-3
Target setpoint-4
To switch the parameter display, press the
SET/ENT
Minimum response time
key.
This parameter
is not to be set.
SET/ENT
key
SET/ENT
key
IM 05D01D02-03E (1)
2. Lists of Parameters
* Parameters relating to PV or setpoints should all be set in real numbers.
For example, use temperature values to define target setpoints and
alarm setpoints for temperature input.
■ Operating Parameters
Parameter
Symbol
(LL)
Name of Parameter
LL communication
interface selection
Alarm 1-setpoint
(A1)
Alarm 2-setpoint
(A2)
Setting Range and Description
Initial Value
OFF: Communication is carried out via the
RS485 communication terminals.
ON: Communication is carried out via the light-loader
adapter.
with communication : OFF
without communication : ON
PV alarm / SP alarm: -100.0 to 100.0% of PV
input range
Deviation alarm: -100.0 to 100.0% of PV input
range span
Output alarm: -5.0 to 105.0%
An alarm common to the 1.SP to 4.SP parameters.
PV high limit/SP high limit alarm:
100.0% of PV input range
Deviation alarm: 0.0% of PV
input range span
Other PV/SP low limit alarm:
0.0% of PV input range
Output high limit alarm: 100.0%
Output low limit alarm: 0.0%
Alarm 3-setpoint
User Setting
* The “User Setting” column in the table below is provided for the customer to record setpoints.
■ Setup Parameters
* The “Target Item in CD-ROM” column in the table below provides references from User’s Manual (Reference) (CD-ROM
Version) which describes items in more detail and items that are not contained in this manual.
● Control Function-related Parameters
Target Item
in CD-ROM
Cooling-side derivative
time
OFF, 1 to 6000 second
60 second
Deadband
-100.0 to 50.0%
In heating/cooling control, a reagion where
both of the heating- and cooling-side outputs
are presented, or none of them is presented,
can be set.
3.0%
Parameter
Symbol
—
(1.DB)
(SPH)
Ref.4.1(1)
Alarm-1 type
Zone PID reference
point-1
0.0 to 100.0% of PV input range.
Note that 1.RP ⱕ 2.RP.
(AL1)
100% value of
PV input range
Alarm-2 type
(1.RP)
(AL2)
—
(AT)
“Super” function
(SC)
OFF: No auto-tuning
1: Auto-tuning for 1.SP 2: Auto-tuning for 2.SP
3: Auto-tuning for 3.SP 4: Auto-tuning for 4.SP
AUTO: Performs auto-tuning to all groups 1 to 4.
Refer to the table below for recording setpoints when two sets or more of PID parameters are used.
Parameter
OFF
—
OFF: Disable
1: Overshoot suppressing function
Suppresses overshoots generated by abrupt changes
in the target setpoint or by disturbances.
2: Hunting suppressing function (Stable mode)
Suitable to stabilize the state of control when the load
varies greatly, or the target setpoint is changed.
Enables to answer the wider characteristic changes
compared with Response mode.
3: Hunting suppressing function (Response mode)
Enables quick follow-up and short converging time of
PV for the changed target setpoint.
(SP.NO)
PID parameter display
number
(PID)
PV input filter
0: Uses target setpoint via communication
1: Selects target setpoint 1 (1.SP).
2: Selects target setpoint 2 (2.SP).
3: Selects target setpoint 3 (3.SP).
4: Selects target setpoint 4 (4.SP).
MENU: Move to FL parameter display
1Gr to 4Gr: Display of each PID
parameter
Alarm-3 type
Ref.2.1(5)
n.Dc
n.DB
Ref.2.1(6)
n.RP
(BS)
Setpoint ramp-up-rate
(UPR)
Setpoint ramp-downrate
(DNR)
(OH)
(OL)
(H)
Output high limit
Heating-side output high limit
(in heating/cooling control)
Output low limit
Cooling-side output high limit
(in heating/cooling control)
ON/OFF control hysteresis
Heating-side/cooling-side
ON/OFF control hysteresis
(in heating/cooling control)
Direct/reverse action
switching
Alarm-1 hysteresis
(HY1)
(RDV)
■ Auto-tuning
OFF
Ref.1.1(1)
0.0% of PV input range
span
OFF
Ref.4.1(4)
OFF
Ref.2.1(3)
Setting of
AT Parameter
Interval of auto-tuning
—
1
The setpoints when autotuning is started
Determines the values of 1.P, 1.I and 1.D parameters by auto-tuning.
0
Ref.2.1(1)
These are not setpoints.
The current value of the
heater burnout detector
is shown on the display of
the HC1 or HC2 parameter.
ON/OFF rate detection
band
0.0 to 100.0% of PV input range span
1.0% of PV input range
span
ON/OFF rate high limit
ORL + 1 digit to 105.0%
100.0%
(AR)
-5.0% to ORH - 1 digit
ON/OFF rate
This is not a setpoint.
Target setpoint-1
0.0 to 100.0% of PV input range
However, between target setpoint limiter
lower limit (SPL) and upper limit (SPH).
(OR)
Output
Point of on-off action
(Target setpoint)
Output
0.0%
AUTO (0), 50.0 to 200.0%
Used when the control output travels up to 100% or down
to 0% and stays at this point.
The larger SP, the sooner PID computation
(integral computation) stops.
0: hour, 1: minute
Time unit of setpoint ramp-up (UPR) and setpoint
ramp-down (DNR)
0: PC link communication
1: PC link communication (with sum check)
2: Ladder communication
3: Coordinated master station
4: Coordinated slave station
7: MODBUS (ASCII)
8: MODBUS (RTU)
10: Coordinated slave station (loop-1 mode)
11: Coordinated slave station (loop-2 mode)
0: 600, 1: 1200, 2: 2400, 3: 4800, 4: 9600 (bps)
AUTO
Anti-reset windup
(Excess integration
prevention)
Baud rate
Parity
(PRI)
Stop bit
Hysteresis
Off
Ref.3.3(4)
0.0%
The moving average (for 5
cycle times) of the control
output is shown.
0.0% of PV input range
(DLN)
PV value
(ADR)
the target setpoint is changed (example: change in “1.SP” from 100°C to 150°C);
the target setpoint number is switched (example: switch from “1.SP” to “3.SP”);
the power is turned on or the controller is recovered from power failure;
a change is made from manual operation to automatic operation; or
a change is made from the STOP state to the RUN state.
—
Ref.4.1(1)
Target setpoint-3
(3.SP)
Target setpoint-4
(4.SP)
● PID-related Parameters
The following parameters are displayed when “1Gr” is set to PID parameter display number (PID). In this case, the corresponding target setpoint is 1.SP
(target setpoint-1).
To set PID corresponding to target setpoint 2 to 4, set “2Gr”, “3Gr”, or “4Gr” to PID. The relevant parameters will then be displayed.
Setting Range and Description
Initial Value
Proportional band/Heatingside proportional band
(in heating/cooling control)
0.1 to 999.9%
In heating/cooling control: 0.0 to 999.9%
(heating-side ON/OFF control applies when 0.0)
5.0%
Integral time
Heating-side integral time
(in heating/cooling control)
Derivative time
Heating-side derivative time
(in heating/cooling control)
Manual reset
OFF, 1 to 6000 second
240 second
OFF, 1 to 6000 second
60 second
-5.0 to 105.0%
(enabled when integral time “1.I” is OFF)
The manual reset value equals the output value
when PV = SP is true.
For example, if the manual reset value is 50%,
the output value is 50% when PV = SP
becomes true.
50.0%
0.0 to 999.9%
(Cooling-side ON/OFF control applies
when 0.0)
OFF, 1 to 6000 second
5.0%
User Setting
Target Item
in CD-ROM
Minimum response
time
2.SP
Ref.4.1(1)
in case of the above conditions [2] to [5].
(C.S3)
Parameter
Symbol
Reference point 1
(1.RP)
Minimum value of PV
input range (RL)
PV input value
Zone 3:
Operated with 3rd group of
PID constants
Zone 2:
Operated with 2nd group of
PID constants
Zone 1:
Operated with 1st group of
PID constants
11 - 12 - 13 terminals
PV input unit
1
Ref.3.1(1)
OFF, 201 to 1015
Select the desired parameter from among the operating and setup
parameters, then register the number (D register No.) accompanying that
parameter.
For example, registering “231” for C.S1 allows you to change alarm-1
setpoint in operating display.
Numbers for registering alarm SP parameter for operating display:
Alarm-1 setpoint: 231
Alarm-2 setpoint: 232
Alarm-3 setpoint: 233
Above numbers are alarm setpoint parameters for target setpoint-1 (1.SP).
See User’s Manual (Reference) (CD-ROM).
OFF
OFF: No key lock
1: Change to any parameter prohibited
Prohibits any operating parameter or setup parameter from being
changed.
The setpoint of the LOCK parameter itself can be changed, however.
2: Change to and display of operating parameters prohibited
Turns off the display for setting operating parameters, thus
prohibiting any change to the parameter settings.
(Hold down the SET/ENT key for more than 3 seconds to show the
password check display.)
3: Disables the A/M key on the instrument’s front panel.
OFF
0: Password not set
1 to 9999
0
Key lock
Ref.2.1(2)
(LOCK)
ON
Ref.4.1(2)
Ref.2.1(4)
Password setting
0
Ref.4.1(4)
Ref.7.1(2)
Ref.7.1(1)
(PWD)
0
■ Useful Operating Displays (SELECT Display)
Registering frequently changed parameters in the SELECT display after ordinary operating displays will allow you to change settings easily.
A maximum of four displays can be registered.
4
Setting method:
Set the parameter numbers (D register numbers) you wish to register
for setup parameters C.S1 to C.S4.
1
communication
function
1
7, 8: Fixed at 7, when the P.SL parameter is set to MODBUS (ASCII).
Fixed at 8, when the P.SL parameter is set to MODBUS (RTU)
or Ladder Communication.
1 to 99
However, the maximum number of stations connectable
is 31.
0 to 10 (⫻ 10 ms)
Ref.6.1(1)
(C.S4)
Alarm parameter for target setpoint-1
Useful
operating display
(SELECT display)
Ordinary operating displays (example)
Registration number
Alarm-1 setpoint parameter
231
Alarm-2 setpoint parameter
232
Alarm-3 setpoint parameter
233
PV
PV
SP 2
3
PV
SP 2
4
AL1
2
AL1
MAN
3
A/M
key
4
SP 2
SP display
3
4
SP
2
3
MAN
AL1
key
SET/ENT
A/M
2
3
MAN
A/M
SET/ENT
SET/ENT
For any registration number other than those above, see User’s Manual
(Reference) (CD-ROM version).
3
SP
SP
8
SET/ENT
OUT display
Alarm-1 setting
display (example)
1
key
SET/ENT
0
■ Heating/Cooling Control (for a Heating/Cooling Controller Only)
Max. value of PV input
range
(RH)
Min. value of PV input
range
(RL)
OFF, 1 to 18, 30, 31, 35 to 37, 40, 41, 50, 51, 55, 56
See Instrument Input Range Codes in Initial Settings
User’s Manual .
⬚C: degree Celsius
⬚F: Fahrenheit
Initial Value
User Setting
Target Item
in CD-ROM
OFF
—
(This parameter is not shown for voltage input.)
Set the PV input range, however RL < RH
-Temperature input
Set the range of temperature that is actually controlled.
- Voltage input
Set the range of a voltage signal that is applied.
The scale across which the voltage signal is actually controlled
should be set using the parameters Maximum Value of PV Input
Scale (SH) and Minimum Value of PV Input Scale (SL).
⬚C
Max. value of
instrument
input range
Min. value of
instrument
input range
In heating/cooling control, the controller outputs the result of computation after splitting it into heating-purpose and cooling-purpose signals.
In addition, the controller can perform PID control or on-off control on the heating and cooling sides separately. When performing on-off
control, set the proportional band to “0”.
The controller splits the result of computation (0 to 100%) into heating-side and coolSP
Communication
PV
ing-side signals, as described below.
• 0% to 50% of the computation result is presented as a 0% to 100% cooling-side
output.
PID computation
Manual MV output
• 50% to 100% of the computation result is presented as a 0% to 100% heating-side
output.
0% to 100%
Heating/cooling
Heating/cooling control provides two methods in which either none of the heating- and
computation
cooling-side outputs are presented or both of the heating- and cooling-side outputs are
0% to 50%
presented, as shown in the following figures.
—
(SH)
(SL)
(RJC)
PV input decimal point
position (displayed
at voltage input)
Max. value of PV input
scale
(displayed at voltage input)
Min. value of PV input
scale
(displayed at voltage input)
Presence/absence of
PV input reference
junction compensation
Selection of PV input
burnout action
Control output
type
(OT)
0 to 3
Set the position of the decimal point of voltage-mode PV input.
0: No decimal place
1: One decimal place
2 , 3: Two, three decimal places
-1999 to 9999, however SL < SH
Set the read-out scale of voltage-mode PV input.
OFF
1: Up scale
2: Down scale
0 Time proportional PID relay contact output (terminals 1 - 2 - 3 )
1 Time proportional PID voltage pulse output (terminals 16 - 17 )
2 Current output (terminals 16 - 17 )
3 ON/OFF control relay contact output (terminals 1 - 2 - 3 )
Output (%)
100
100
Heating-side
output
Cooling-side
output
Heating-side
output
50% to 100%
Cooling-side
output limiter
Heating-side
output limiter
Cooling-side MV
output 0% to 100%
Heating-side MV
output 0% to 100%
—
0
1
—
50
0
100(%)
Deadband (positive)
Value of control output before split into heating- and
cooling-side outputs
0
50
100(%)
Deadband (negative)
Value of control output before split into heating- and
cooling-side outputs
—
Precautions in Heating/Cooling Control
• Keep the ratio of the heating-side proportional band (P) to the cooling-side proportional band (Pc) equal to or below 5.
• If neither the heating side nor the cooling side is performing on-off control, setting the integral time (I or Ic) of one side to “0” results in
the Integral Time parameters of both sides being set to “OFF”,
irrespective of the integral time setting of the other side.
—
■ Cycle Time
100.0
—
0.0
OFF, ON
Output (%)
Cooling-side
output
0
(BSL)
Note: Set the maximum and minimum values, as close as possible to those of the actual range to be controlled, in the Maximum Value of PV Input Range
(RH) and Minimum Value of PV Input Range (RL) parameters. Otherwise, the controller may fail to determine the optimum values when autotuning is carried out.
Setting Range and Description
—
(UNIT)
Time
240 second
0: None
1: Even
2: Odd
1, 2
Name of Parameter
PV input type (PV INPUT
terminals)
(IN)
(SDP)
Reference point 2
(2.RP)
SELECT display-4
registration
0
● Input-/Output-related Parameters
Using a zone PID, you can automatically switch between groups of PID constants according to the temperature zone. You can set a maximum
of three temperature zones.
Setpoint
(C.S2)
Ref.2.1(8)
0.0%
(TEST)
■ PID Switching (Zone PID)
Maximum value of PV
input range (RH)
OFF Disables the external contact input.
1 DI1: 2.SP (on)/1.SP (off), DI2: AUTO (on)/MAN (off)
2 DI1: Hides (on)/shows (off) the LOCK setup parameter.
DI2: Unused.
3 See the table below.
4 DI1: 2.SP (on)/1.SP (off), DI2: STOP (on)/RUN (off)
(RP.T)
If the target setpoint before switching is smaller than the target setpoint 2.SP=640°C
after switching, the controller operates according to the settings of the
140°C
Setpoint Ramp UP (UPR) and Ramp Time Unit (TMU) parameters. If the
temperature difference
target setpoint before switching is greater than the target setpoint after switch70°C/min
ing, the controller operates according to the settings of the Setpoint Ramp
(140°C/2 min) rate of
Down (DNR) and Ramp Time Unit (TMU) parameters. The figure on the 1.SP=500°C
temperature change
right shows an example when the Target Setpoint Number (SP.NO) param2-minute interval of
eter is switched. The 1.SP and 2.SP parameters are set to 500°C and 640°C,
temperature rise
respectively. Thus, there is a temperature difference of 140°C between the
Switching from 1.SP to 2.SP parameter
1.SP and 2.SP parameters. This example shows how the temperature is
changed by as much as this temperature difference over a period of two minutes. In this
NOTE
example, the UPR parameter is 70°C and the TMU parameter is 1 minute.
When using target setpoint ramp setting function, PV tracking works
Setting Method:
[1] Set the Zone PID Selection (ZON) parameter to
“ON”.
[2] Define a reference point.
When using two zones, define only reference point 1
(1.RP) between the minimum and maximum values of
the PV input range.
When using three zones, define reference points 1 and
2 (1.RP and 2.RP) in the same way as noted above.
SELECT display-2
registration
SELECT display-3
registration
If this parameter symbol appears, press the SET/ENT key to return to the FUNC menu.
Caution: Do not change the setpoint of the TEST parameter, otherwise the controller will be disabled.
1.SP
Ref.2.2(1)
100.0% of
PV input range
0.0% of
PV input range
SET/ENT
Data length
■ Target Setpoint Ramp Setting Function
[1]
[2]
[3]
[4]
[5]
(C.S1)
30 second
(STP)
Address
Ref.3.3(4)
SELECT display-1
registration
30 second
(BPS)
Point of on-off action
(Alarm setpoint)
On
Hysteresis
Off
(2.SP)
(1.Ic)
-5.0 to 105.0%
In heating/cooling control: Heating side 0.0 to 105.0%
In Stop mode, fixed control output can be generated.
0.0 to 105.0%
In Stop mode, cooling-side fixed control output can be
generated.
0: Standard PID control (with output bump at SP change)
1: Fixed point control (without output bump at SP change)
Choose “fixed point control” when controlling pressure or flow rate.
OFF: SP selection
ON: Zone PID
Protocol selection
● When hysteresis is set in an alarm setpoint
Target setpoint-2
Cooling-side integral
time
Preset output/Heating-side
preset output
(in heating/cooling control)
Cooling-side preset
output
Ramp-rate time unit
setting
(P.SL)
(ORL)
(1.Pc)
1 to 1000 second
Determines the values of all PID parameters in use by auto-tuning.
Use this function to prevent the target setpoint from changing suddenly. The ramp setting function works when:
Cooling-side
proportional band
Cooling-side control
output cycle time
1
DI2
OFF
OFF
ON
ON
(ZON)
Determines the values of 2.P, 2.I and 2.D parameters by auto-tuning.
PV value
(1.MR)
1 to 1000 second
(CTc)
■ Hysteresis (for Target Setpoints (On-Off Control) and Alarm Setpoints)
On
(ORH)
(1.D)
(CT)
(TMU)
(ORB)
(1.I)
Control output cycle time
Heating-side control output cycle
time (in heating/cooling control)
—
(DY3)
The AT parameter settings numbered 1 to 4 in the table above are dependent on how many zones have been set. For example, if you have set
two zones, you can use AT parameter settings 1 and 2. Likewise, if you have set three zones, you can use AT parameter settings 1, 2 and 3.
Ref.3.3(5)
DI1
OFF
ON
OFF
ON
1.SP
2.SP
3.SP
4.SP
0.00 to 99.59 (min, sec.) (enabled when alarm-3 type
“AL3” is 1 to 20 or 28 to 31)
Hysteresis can be set in on-off control setpoints and alarm setpoints as well. With the hysteresis settings, it is possible to prevent relays from
chattering.
OFF
RET=1, 2: 0.0% of PV input range to RTH - 1 digit
RET=3: 0.0% to RTH - 1 digit
Heating/cooling
type: 4
䊊 SP Selection when DIS = 3 is set
on
off
Alarm-3 delay timer
Zone PID selection
Determines the values of 4.P, 4.I and 4.D parameters by auto-tuning.
Median value of each zone
width
—
(DY2)
Determines the values of 3.P, 3.I and 3.D parameters by auto-tuning.
AUTO
Delay timer
0.00 to 99.59 (min, sec.) (enabled when alarm-2 type
“AL2” is 1 to 20 or 28 to 31)
(C.MD)
Auto-tuning is turned off (disabled).
3
Max. value of
retransmission output
scale
Min. value of
retransmission output
scale
DI function selection
(DIS)
Alarm-2 delay timer
PID control mode
-
(HC2)
(1.P)
0.00
Example of hysteresis set in PV high limit alarm
Heater burnout current
measurement 2
Name of Parameter
(RTL)
An alarm is output when the delay timer expires after the
alarm setpoint is reached.
0.00 to 99.59 (min, sec.) (enabled when alarm-1 type
“AL1” is 1 to 20 or 28 to 31)
Time
Remarks
Auto-tuned Setpoint
● When hysteresis is set in a target setpoint
(HC1)
Parameter
Symbol
Hysteresis
Off
Alarm output
Auto-tuning is
complete when the
3rd peak arrives.
OFF
2
(HB2)
(1.SP)
(RET)
Alarm setpoint
(PO)
Heater burnout current
setpoint 2
ON/OFF rate low limit
Retransmission output
type
Ref.3.3(2)
Ref.4.1(1)
Auto-tuning is a function with which the controller
automatically measures the process characteristics
to automatically set the optimum PID constants. This
Setpoint
function does not work when the controller is performing on-off control. The UT350/UT320 employ
the “Limit Cycle Method.” As shown in the figure PV input value
on the right, the controller temporarily changes its
On
On
On
control output in a step-waveform manner. Then, it Control output
Off
Off
Time
calculates the optimum proportional band (P), intePID control based on
Start
of
PID
constants
determined
gral time (I) and derivative time (D) from the resultauto-tuning
by auto-tuning
ing response to set them in their respective parameters. If the Output High Limit (OH) and Output Low Limit (OL) parameters are already configured, the control output turns on and off only
between the output’s high and low limits during auto-tuning.
(HB1)
Heater burnout current
measurement 1
Point of
on-off action
(Alarm setpoint)
1
PV
(POc)
100%
Heating/cooling control:
100.0%
0.0%
Heating/cooling control:
100.0%
ON/OFF control: 0.5% of PV
input range span
Heating/cooling control: 0.5%
Deviation
(PV-SP)
OFF, or 1 to 50 A
Output
Ref.3.3(4)
PV value
OFF
● Auto-tuning Using Zone PID (see “■ PID Switching (Zone PID)” later in this manual)
+
0%
Heater burnout current
setpoint 1
0.5% of PV
input range span
Output alarm:
0.5%
2
Hysteresis
Direct
action
-
—
(RTH)
Alarm-1 delay timer
100%
Reverse
action
0.0% of
PV input range
0.0 to 100.0% of PV input range span
Output alarm: 0.0 to 100.0%
Hysteresis for PV high limit alarm
Delay timer
Control output
(DR)
Target Item
in CD-ROM
—
1
(HY3)
None
OFF, 0.0 to100.0% of PV input range span
Used to select PID constants according to a deviation from
the setpoint. The 4th group of PID constants is used when
the controller fails to keep track of the deviation.
User Setting
100.0% of
PV input range
OFF, 1 to 25, 28 to 31
1: PV high limit (energized, no stand-by action)
2: PV low limit (energized, no stand-by action)
3: Deviation high limit (energized, no stand-by action)
4: Deviation low limit (energized, no stand-by action)
5: Deviation high limit (de-energized, no stand-by action)
6: Deviation low limit (de-energized, no stand-by action)
These Alarm Type parameters are common to the
parameters 1.SP to 4.SP. See “List of Alarm Types” on the
back for other alarm types.
Alarm-3 hysteresis
4
0: reverse action, 1: direct action
0.0 to 100.0% of PV input range where, SPL < SPH
Places a limit on the range within which the target
setpoint is changed.
(HY2)
None
Initial Value
On
(DY1)
Ref.4.1(1)
-5.0 to 105.0%
Heating-side limiter in heating/cooling
control: 0.0 to 105.0% (OL < OH)
-5.0 to 105.0%
Cooling-side limiter in heating/cooling control: 0.0 to
105.0% (OL < OH)
In ON/OFF control: 0.0 to 100.0% of PV input
range span
In heating/cooling control: 0.0 to 10.0%
(OT)
Setting Range and Description
Alarm-2 hysteresis
Reference deviation
MENU
-100.0% to 100.0% of PV input
range span
Used to correct the PV input range.
OFF
0.0% + 1 digit of PV input range span
to 100.0% of PV input range span
Set ramp-up-rate or ramp-down-rate
per hour or minute.
Sets unit in ramp-rate-time unit (TMU).
(AL3)
n.Pc
n.Ic
(FL)
PV input bias
n=4
n.D
n.MR
OFF
1
OFF, 1 to 120 second.
Used when the PV input fluctuates.
n=3
n.P
n.I
Note: Use “SUPER” function (SC) 2 or 3 in PID control or PI control.
“SUPER” function 2 or 3 is not available in the following control:
1) ON/OFF control
2) P control (control for proportional band only)
3) PD control (control for proportional band and derivative item only)
4) Heating/cooling control
Do not use hunting suppressing function when control processes
with response such as flow or pressure control.
Target setpoint
number selection
n=2
The following 4 to 12 are displayed only for heating/ cooling type controllers.
4 Heating-side relay output (terminals 1 - 2 - 3 ),
cooling-side relay output (terminals 4 - 7 )
5 Heating-side pulse output (terminals 16 - 17 ),
cooling-side relay output (terminals 4 - 7 )
6 Heating-side current output (terminals 16 - 17 ),
cooling-side relay output (terminals 4 - 7 )
7 Heating-side relay output (terminals 1 - 2 - 3 ),
cooling-side pulse output (terminals 14 - 15 )
8 Heating-side pulse output (terminals 16 - 17 ),
cooling-side pulse output (terminals 14 - 15 )
9 Heating-side current output (terminals 16 - 17 ),
cooling-side pulse output (terminals 14 - 15 )
10 Heating-side relay output (terminals 1 - 2 - 3 ),
cooling-side current output (terminals 14 - 15 )
11 Heating-side pulse output (terminals 16 - 17 ),
cooling-side current output (terminals 14 - 15 )
12 Heating-side current output (terminals 16 - 17 ),
cooling-side current output (terminals 14 - 15 )
OFF: Does not work.
1: PV, 2: SP, 3: OUT, 4: Loop power supply for sensor (15 V)
In position proportional control, a valve opening signal (0 to 100%) is
transmitted if setpoint “3” is selected.
In heating/cooling control, an output value before allocation to heating
and cooling control (0 to 100%) is transmitted if setpoint “3” is selected
(0 to 50%: Cooling-side output; 50 to 100%: Heating-side output).
RET=1, 2: RTL + 1 digit to 100.0% of PV input range
RET=3: RTL + 1 digit to 100.0%
(SPL)
—
—
Control output
type
Target setpoint
limiter lower limit
(A3)
Auto-tuning
Name of Parameter
Target setpoint
limiter upper limit
(1.Dc)
Continued
ON
1
—
0
—
On
On
A cycle time can only be set if the type of control output is time proportional PID relay output or time proportional voltage pulse output.
A cycle time refers to one period consisting of on- and off-state time
lengths. The ratio of the on-state time to the off-state time differs according to the value of the control output. The figure on the right shows
on-to-off time ratios of the control output when the cycle time is set to
10 seconds. Setting a shorter cycle time allows the controller to perform
elaborate control at short time intervals. This significantly reduces the
on- and off-state times, however it shortens the service life of a relay.
Off
Cycle time
Off
Cycle time
Relay’s Behavior when Cycle Time = 10 sec
For 20% of Control Output
10 sec
On-state duration: 2 sec
Off-state duration: 8 sec
For 50% of Control Output For 80% of Control Output
10 sec
On-state duration: 5 sec
Off-state duration: 5 sec
10 sec
On-state duration: 8 sec
Off-state duration: 2 sec
IM 05D01D02-03E (2)