FIRE CONTROL PANEL
MAG2/4
USER MANU
AL
MANUAL
MAG2 Soft. Version 2.1
MAG4 Soft.Version 2.0
READ THIS MANUAL BEFORE CONNECTING THE EQUIPMENT
AND KEEP IT SAFE FOR FUTURE REFERENCE.
To call our technical support line dial
+44 (0) 121 786 1881
INSTALLER Instructions
Contents
Page
General Information ................................................................................................... 2
Using the Mag 2/4 controls ........................................................................................ 3
Indicators / Outputs ................................................................................................... 3
Engineers Facilities ..................................................................................................... 3
Installing the Panel ..................................................................................................... 4
Testing the Panel ........................................................................................................ 4
Engineers Facilities ..................................................................................................... 6
Connecting the Additional Facilities .......................................................................... 7
Specification ............................................................................................................... 8
Notes .......................................................................................................................... 9
Connection Circuits MAG 2/4 ................................................................................ 10
Guarantee ................................................................................................................. 11
Fire Alarm Record .................................................................................................... 12
Service Record .......................................................................................................... 13
Fire Alarm Event Log ............................................................................................... 13
WARNING
This manual contains information on limitations regarding product use and function and information
on the limitations as to liability of the manufacturer. The entire manual should be carefully read.
General Information
The system is to be installed by a qualified person to the latest Fire Alarm and Installation Regulations
which are mandatory in the applicable country of installation.
Before commencing the installation of this Fire Alarm Panel, ensure it is sited in a position, which is
visible to the Fire Brigade when entering the premises, and where ease of access is provided for users
and service engineers. Space must be available to easily open external and internal doors.
The Electrical Supply to the panel must be isolated and must not be capable of being accidentally
switched off. A ‘Lockable Switch fuse Unit’ positioned within 2 meters of the panel should be
clearly labelled FIRE ALARM - DO NOT SWITCH OFF.
EN 54-2 compatible panels.
All specifications are subject to change without notice.
2
Using the MAG 2/4 Controls
• Refer to the instructions on the inside of the outer door.
Indications / Outputs
NORMAL:
• The green LED next to the ‘power Supply 230V AC’ will be illuminated.
FIRE:
• Two integrated red status FIRE LED’s and a zone identification LED will flash
together on receipt of a FIRE condition and become steady after the Silence Alarm
button is pressed.
• An internal buzzer will operate until silenced.
• The external sounders will operate.
• The FIRE relay will energize.
FAULT:
• A yellow General Fault LED will always illuminate together with an external or
internal identification LED.
• An internal buzzer will sound.
• The FAULT relay will de-energize.
Faults are monitored as follows:
• Zone fault - open or short circuit. Detector head removed.
• Sounder Circuit One fault - open or short circuit, reverse connected sounder, or
bad sounder parameters.
• Sounder Circuit Two fault - open or short circuit, reverse connected sounder, or
bad sounder parameters.
• A.C. Loss or Battery charger fault. (“A.C. Loss” means Mains Supply)
• Battery Loss.
• Low Battery condition.
• 24V DC Supply fault.
• Processor fault.
• Auxiliary supply fault.
• Short circuit to earth.
All fuses are monitored and will cause a fault condition should they fail. Selecting an ‘Engineers
Facility’ will indicate and announce a Fault condition at the panel.
NOTE: FAULT CONDITIONS WILL NOT BE ANNOUNCED INSTANTLY. THERE WILL
BE A SHORT DELAY WHICH WILL VARY FROM CONDITION TO CONDITION. FAULTS
WHEN CLEARED WILLAUTOMATICALLY RESET AT THE PANEL.
Engineers Facilities:
MAG 2/4 has the ability to select various facilities to assist the engineer during installation and
testing of the system. These facilities include:
Zone Test
- Individual zones can be tested and activated without the need to return
to the panel to effect a RESET. This is done automatically by the panel.
Isolate Sounders
- System can be tested without operating the Sounder circuits.
Disable / Enable Zone - Each zone can be disabled / enabled.
3
Installing the Panel
• Decide the best location for the panel position, with an ambient temperature between 0 degrees C
and 40 degrees C., away from heating systems, environmental dust and potential water ingress.
• Remove all packaging.
• Inspect the panel for any damage.
• Carefully remove the outer cover, by inserting unscrewing the two allen screws. Stow the cover in
a safe position.
• Inspect the internal PCB and make sure the internal components are firmly in place.
• Observe the main PCB chassis and the associated securing screw, located in the front of the
terminal blocks.
• Unfasten the chassis securing screw and remove the chassis. Stow in a safe location.
• Choose which cable entry points to knock out and carefully remove the knock-outs.
• Observe the top center fixing location at the back of the panel.
• Stow the back box in a safe position.
• Drill the wall to suit the back box center fixing position, plug and insert a fixing screw.
• Temporally hang the back box from the fixing screw and mark out the two bottom left and right
fixing locations.
• Remove the back box from the center fixing screw position and drill and plug the bottom fixing holes.
• Hang the back box from the center fixing position and fix securing screws through the bottom
fixing holes.
• Tighten all the fixing screws.
• Route the external cables onto the back box, make off connection glands etc., BUT DO NOT
make any connections at this stage. ENTER THE MAINS CABLE THROUGH ITS OWN
CABLE ENTRY POINT AND KEEP MAINS WIRING AWAY FROM SYSTEM AND
OTHER LOW VOLTAGE WIRING.
• Re-fit the PCB chassis and re-connect the chassis mains connection.
• Connect the mains supply and earth to the main terminal block BUT DO NOT apply the main
electrical supply at this stage.
• Position the standby battery in an upright position.
The panel is now ready for testing.
Testing the Panel
• Connect the battery leads from the black power supply box to the positive and negative battery
terminals.
• Apply the mains power.
• If the buzzer and indicator LED’s are operating, press the RESET button.
If in the Normal Operating Mode other LED’s are illuminated and the buzzer is sounding, carefully
check that fuses and connections are sound. Refer to the part of the internal connections or circuitry
the associated yellow LED’s apply to. The connection diagram on the inside of the external cover will
assist in identifying the LED.
NOTE: The battery might show a ‘Low Battery Fault’ initially until it has had time to charge up to the
required level.
If by some chance the fault will not cancel, and only on the advice of our Technical Support
4
Department, return the P.C.B. CHASSIS ONLY to your supplier. DO NOT return the plastic
box.
Once the panel is found to operate satisfactorily in the NORMAL MODE, it is time to
connect the external circuits.
It has been assumed that prior to making the connection at the panel, the integrity of the
system ALL wiring has been comprehensively tested, including insulation to earth.
• Isolate the mains supply and disconnect the battery connection.
• Fit the Active End of Line Device to the last detection device of zone one.
• Ensure all terminations are made correctly and all detector heads are plugged into their bases.
• Connect Detector circuit ONE to the panel terminal block.
• Power up the panel with the mains and battery.
• Press RESET button.
The panel should be in the ‘NORMAL MODE.’
NOTE: If General Fault and zone 1 FAULT LED’s illuminate, there is a wiring / connection problem.
Check the polarity of the connection, the connection of the devices and whether a head is removed.
Check the EOL proper polarity and position.
• Operate ALL detection devices applicable to this zone, to ensure correct receipt of a fire signal
and the correct operation of the panel controls. Refer to the User Instructions on the inside of the
panel.
• Repeat the connection process for zone two as stated above. ENSURE the supply voltages are
initially disconnected prior to each stage.
ONCE THE CONNECTION OF THE ZONES ARE COMPLETED, CONNECT AND TEST
ANY OF THE OTHER AUXILIARY CIRCUITS BEFORE CONNECTING THE EXTERNAL
SOUNDER CIRCUITS.
Relay Connection - The onboard relay volt free change over terminals are for low voltage use
only.
MAINS SUPPLY MUST NOT BE APPLIED TO THESE TERMINALS.
Once the zone and auxiliary circuits have been connected and tested to function correctly, it
is time to connect the first external sounder circuit:
• Isolate the mains supply and disconnect the battery connection.
• Remove the End of Line Monitoring Resistor from the terminal block of sounder circuit 1 (SND 1)
and fit to the last sounder of circuit one.
• Check all sounder connections are made.
• Connect sounder circuit ONE to the panel terminal block.
• Apply mains and battery power.
• Press RESET
The panel should be in the ‘NORMAL MODE.’
Activate a zone Call Point. The sounders should operate. Press the reset button.
Repeat the connection process for the second external sounder circuit, as stated above. ENSURE the
supply voltages are initially disconnected prior to each stage.
NOTE: If General Fault and SOUNDER FAULT / DISABLE LED.’s illuminate, there is a wiring /
connection problem. Check the polarity of the connection of each of the devices, the polarity of the
connection of the devices to the Panel terminal block or whether an earth fault exists.
5
Engineers Facilities:
To Disable Zone 1:
Press ENABLE / DISABLE button:
Zone 1 lamp will flash.
DISABLE / ENABLE lamp will flash.
Press ENABLE / DISABLE button:
The zone lamp will become steady.
Press RESET:
At this point the zone 1 is disabled.
To Enable Zone 1:
Press ENABLE / DISABLE button TWICE:
Zone 1 lamp will flash.
DISABLE / ENABLE lamp will flash.
Press RESET.
At this point the zone 1 is disabled.
To Disable Zone 2:
Press ENABLE / DISABLE button:
Zone 1 lamp will flash.
ENABLE / DISABLE lamp will flash.
Press TEST / SCROLL button:
Zone 2 lamp will flash.
ENABLE / DISABLE lamp will flash.
Press ENABLE / DISABLE button:
Zone 2 lamp will become steady.
ENABLE / DISABLE lamp will flash.
Press RESET:
At this point the zone 2 is disabled.
To Enable Zone 2:
Press ENABLE / DISABLE button:
Zone 1 lamp will flash.
ENABLE / DISABLE lamp will flash.
Press TEST / SCROLL button:
Zone 2 lamp will be steady.
ENABLE / DISABLE lamp will flash.
Press ENABLE / DISABLE button:
Zone 2 lamp will flash.
ENABLE / DISABLE lamp will flash.
Press RESET:
At this point zone 2 is enabled.
To ‘One Man’ Test a Zone:
Press TEST / SCROLL button:
TEST AND ZONE yellow LED’s will flash.
Zone 1 is in Test Mode.
Flashing LED will move down to zone 2.
Zone 2 is in Test Mode.
Press TEST / SCROLL button:
The “One Man” Test Mode will exit when pressing the TEST / SCROLL button again, or at any time,
by pressing RESET.
6
Disable Sounders:
Press DISABLE / ENABLE button:
Press TEST / SCROLL button again:
Press TEST / SCROLL button
once again:
Press ENABLE / DISABLE button:
Press RESET:
DISABLE / ENABLE lamp will flash.
Zone 1 lamp will flash.
Zone 2 lamp will flash.
SOUNDER FAULT / DISABLE lamp will flash.
DISABLE / ENABLE lamp will flash.
SOUNDER FAULT / DISABLE lamp changes to steady.
ENABLE / DISABLE lamp flashes.
At this point zone the sounders are disabled.
To enable Sounders:
Press DISABLE / ENABLE button:
Press TEST / SCROLL button:
Press TEST / SCROLL button
once again:
Press ENABLE / DISABLE button:
Press RESET:
DISABLE / ENABLE lamp will flash
Zone 1 lamp will flash.
Zone 2 lamp will flash.
SOUNDER FAULT / DISABLE lamp will be steady.
DISABLE / ENABLE lamp will flash.
SOUNDER FAULT / DISABLE lamp change to flashing.
ENABLE / DISABLE lamp flashes.
At this point zone the panel has reset.
Connecting The Additional Facilities
Class Change:
Connect a ‘non latching’ switch to the class change terminals at the top of the MAINBOARD.
Operation of the switch will cause the external sounders to pulse one second on followed by one
second off.
Once the panel connections and facilities have been functionally tested, replace and secure
the front cover of the box, remembering to connect the earth bonding lead to the continuity
terminal.
7
Specification
Maximum number of detectors per zone
Up to 32 conventional detectors and unlimited
number of manual call points.
Thresholds for zone conditions
• 0 - 2 mA
• 2 - 6 mA
• 6 - 110 mA
• 110 mA - Short circuit
Open circuit fault condition.
Normal condition.
Fire Alarm condition.
Short circuit condition.
Power Supply
Main Power supply
230V AC ± 10%
0.315A fuse
1 x 12V Sealed Lead Acid Battery
Up to 7Ah internally
2A fuse
Standby Power supply
Maximum current available for system
devices (with fully charged battery)
0.7 A
Current consumption - mains failure
50 mA
Outputs
Sounder Circuit 1
24V / 0.315A
0.3A fuse
24V / 0.315A
0.3A fuse
volt free changeover contacts
12V / 1A or 24V / 0.5A
Max voltage 125V
Max current 2A
Sounder Circuit 2
Fault Relay
Auxiliary output
24V DC 0.3A fuse
Cabling
Maximum 2.5mm diameter
Environment
Working temperature
Storage temperature
Humidity
8
0 to 40 degrees C
-20 to 60 degrees C
0 to 95%
Notes
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
........................................................................................................................................................
9
Connection Circuit MAG 2
Connection Circuit MAG 4
10
Guarantee
During the guarantee period the manufacturer shall, at its sole discretion, replace or repair any defective
product when it is returned to the factory. All parts replaced and/or repaired shall be covered for the
remainder of the original guarantee, or for ninety (90) days, whichever period is longer. The original
purchaser shall immediately send manufacturer a written notice of the defective parts or workmanship,
which written notice must in all cases be received prior to expiry of the guarantee.
International Guarantee
Foreign customers shall enjoy the same guarantee rights as those enjoyed by any customer in Bulgaria,
except that manufacturer shall not be liable for any related customs duties, taxes or VAT, which may be
payable.
Guarantee Procedure
This guarantee will be granted when the appliance in question is returned. The manufacturer shall accept
no product whatsoever, of which no prior notice has been received.
Conditions for waiving the guarantee
This guarantee shall apply to defects in products resulting only from improper materials or
workmanship, related to its normal use. It shall not cover:
§
Damages resulting from transportation and handling;
§
Damages caused by natural calamities, such as fire, floods, storms, earthquakes or lightning;
§
Damages caused by incorrect voltage, accidental breakage or water; beyond the control of the
manufacturer;
§
Damages caused by unauthorized system incorporation, changes, modifications or surrounding
objects:
§
Damages caused by peripheral appliances (unless such peripheral appliances have been
supplied by the manufacturer:
§
Defects caused by inappropriate surrounding of installed products;
§
Damages caused by failure to use the product for its normal purpose; Damages caused by
improper maintenance;
§
Damages resulting from any other cause, bad maintenance or product misuse.
In the case of a reasonable number of unsuccessful attempts to repair the product, covered by this
guarantee, the manufacturer’s liability shall be limited to the replacement of the product as the sole
compensation for breach of the guarantee. Under no circumstances shall the manufacturer be liable for
any special, accidental or consequential damages, on the grounds of breach of guarantee, breach of
agreement, negligence, or any other legal notion.
Waiver
This Guarantee shall contain the entire guarantee and shall be prevailing over any and all other
guarantees, explicit or implicit (including any implicit guarantees on behalf of the dealer, or
adaptability to specific purposes), and over any other responsibilities or liabilities on behalf of the
manufacturer. The manufacturer does neither agree, nor empower, any person, acting on his own behalf,
to modify or alter this Guarantee, nor to replace it with another guarantee, or another liability with
regard to this product.
Unwarranted Services
The manufacturer shall repair or replace unwarranted products, which have been returned to its factory,
at its sole discretion under the conditions below. The manufacturer shall accept no products for which no
prior notice has been received.
The products, which the manufacturer deems repairable, will be repaired and returned. The manufacturer
has prepared a price list and those products, which can be repaired, shall be paid for every repaired
appliance.
The closest equivalent product, available at the time, shall replace the products manufacturer deems
unrepairable. The current market price shall be charged for every replaced product.
11
Fire Alarm Record
Installation Address: ......................................................................................................................
......................................................................................................................
......................................................................................................................
Contact Person:
......................................................................................................................
Telephone:
......................................................................................................................
Fax:
......................................................................................................................
Date Completed:
......................................................................................................................
Commissioned By: ......................................................................................................................
Contract Reference: ......................................................................................................................
Service Intervals:
ZONE
Monthly / Quarterly / Half Yearly / Annually
LOCATION
NUMBER
DETECTOR TYPE and
SOUNDERS
QUANTITY PER ZONE
Zone Quantity and
Related Circuit
Ion
Ph
RoR
F/T
C.P.
Circuit 1
Circuit 2
1
2
3
4
TOTALS:
System Installed By: .....................................................................................................................
......................................................................................................................
Telephone:
......................................................................................................................
Fax:
......................................................................................................................
12
Service Record
Date
Completed
Zones Tested
Faults Rectified
Signature of
Engineer
1.....2.....
Name:
1.....2.....
Name:
1.....2.....
Name:
1.....2.....
Name:
1.....2.....
Name:
1.....2.....
Name:
1.....2.....
Name:
1.....2.....
Name:
1.....2.....
Name:
1.....2.....
Name:
1.....2.....
Name:
Next Visit
Due
Fire Alarm Event Log
DATE
TIME
FIRE
yes/no
ZONE FAULT yes/no and TYPE
number
13
ACTION TAKEN
NAME