Download Altivar 61 - Schneider Electric
Transcript
Altivar® 61 Variable Speed Drive Controllers Simplified Manual Operation on an IT system and corner grounded system 30072-452-65 4/2009 WARNING RISK OF ELECTRIC SHOCK ATV61HC•••Y drives must not be connected on a corner grounded system. Failure to follow these instructions can result in death, serious injury or equipment damage. IT system: Isolated or impedance grounded neutral. Use a permanent insulation monitor compatible with non-linear loads, such as a Merlin Gerin type XM200. Altivar 61 drive controllers feature built-in common mode RFI (EMC) filters. When an ATV61HC••Y drive controller is operating on an isolated or resistance grounded electrical distribution system, the filters must be isolated (disconnected). For any other drive controller referenced in this manual the filter should be isolated (disconnected). Corner Grounded System: The ATV61HC••Y drive controllers must never be connected on a corner grounded electrical distribution system. When any other drive controller referenced in this manual is connected to a corner grounded electricaldistribution system the filters must be isolated (disconnected). 48 © 2009 Schneider Electric USA All Rights Reserved