Altivar® 61 Variable Speed Drive Controllers Simplified Manual
Macro configuration
Table 10:
30072-452-65
4/2009
Codes, adjustment range, and factory settings (continued)
Code
Name/Description
tUn
[Auto tuning]
Adjustment range Factory setting
[No] (nO)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• During auto tuning, the motor operates at rated current.
• Do not service the motor during auto tuning.
Failure to follow these instructions will result in death or serious injury.
DANGER
UNINTENDED EQUIPMENT OPERATION
• The following motor parameters must be correctly configured before starting auto tuning:
[Rated motor volt.] (UnS), [Rated motor freq.] (FrS), [Rated mot. current] (nCr),
[Rated motor speed] (nSP), and [Rated motor power] (nPr).
• If one or more of these parameters is modified after auto tuning has been performed, Auto
tuning (tUn) will be set to [No] and the procedure must be repeated.
Failure to follow these instructions will result in death or serious injury.
•
nO
•
YES
[No] (nO): Auto-tuning not performed.
[Yes] (YES) : Auto-tuning is performed as soon as possible, then the parameter automatically
changes to [Done] (dOnE).
• [Done] (dOnE): Use of the values given the last time auto-tuning was performed.
dOnE
Important:
• It is essential that all motor parameters—[Rated motor volt.] (UnS),
[Rated motor freq.] (FrS), [Rated mot. current.] (nCr), [Rated motor speed] (nSP),
[Rated motor power] (nPr)—are configured correctly before starting auto-tuning.
If one or more of these parameters is modified after auto-tuning has been
performed, [Auto tuning] (tUn) will return to [No] (nO) and the procedure must be
repeated.
• Auto-tuning is performed only if no stop command has been activated. If a freewheel
stop or fast stop function has been assigned to a logic input, this input must be set
to 1 (active at 0).
• Auto-tuning takes priority over any run or prefluxing commands, which will take
effect after the auto-tuning sequence.
• If auto-tuning is unsuccessful, the drive displays [No] (nO) and, depending on the
configuration of [Autotune fault mgt] (tnL) (consult the CD-ROM supplied with the
drive), may switch to [Auto-tuning] (tnF) detected fault.
• Auto-tuning may last for 1 to 2 seconds. Do not interrupt; wait for the display to
change to [Done] (dOnE) or [No] (nO).
NOTE: During auto-tuning the motor operates at rated current.